Company Information

Miller Home Inspection

425-501-2382
millerhomeinspection@gmail.com
https://miller-home-inspection.business.site/

Inspected by: Harold Miller

WA State Inspector #: 209

Published Report


How to Read This Report

Getting the Information to You

This report is designed to deliver important and technical information in a way that is easy for anyone to access and understand. If you are in a hurry, you can take a quick look at our "Summary Page” and quickly get critical information for important decision making. However, we strongly recommend that you take the time to read the full Report, which includes digital photographs, captions, diagrams, descriptions, videos and hot links to additional information.

The best way to get the layers of information that are presented in this report is to read your report online, which will allow you to expand your learning about your house. You will notice some words or series of words highlighted in blue and underlined – clicking on these will provide you with a link to additional information.

This report can also be printed on paper or to a PDF document.

Chapters and Sections

This report is divided into chapters that parcel the home into logical inspection components. Each chapter is broken into sections that relate to a specific system or component of the home. You can navigate between chapters with the click of a button on the left side margin.

Most sections will contain some descriptive information done in black font. Observation narrative, done in colored boxes, will be included if a system or component is found to be significantly deficient in some way or if we wish to provide helpful additional information about the system or the scope of our inspection. If a system or component of the home was deemed to be in satisfactory or serviceable condition, there may be no narrative observation comments in that section and it may simply say “tested,” or “inspected.”

Observation Labels

All narrative observations are colored, numbered and labeled to help you find, refer to, and understand the severity of the observation. Observation colors and labels used in this report are:

  • Major Concern:
    Repair items that may cost significant money to correct now or in the near future, or items that require immediate attention to prevent additional damage or eliminate safety hazards.
  • Repair:
    Repair and maintenance items noted during inspection. Please note that some repair items can be expensive to correct such as re-finishing hardwood floors, but are considered simply repair items due to their cosmetic nature.
  • Recommended Maintenance:
    These are repair items that should be considered "routine home ownership items," such as servicing the furnace, cleaning the gutters or changing the air filters in the furnace.
  • Improve:
    Observations that are not necessarily defects, but which could be improved for safety, efficiency, or reliability reasons.
  • Monitor:
    Items that should be watched to see if correction may be needed in the future.
  • Due Diligence:
    Observation such as a buried oil tank that may require further investigation to determine the severity and / or urgency of repair.
  • Future Project:
    A repair that may be deferred for some time but should be on the radar for repair or replacement in the near future.
  • Note:
    Refers to aside information and /or any comments elaborating on descriptions of systems in the home or limitations to the home inspection.
  • Description:
    Detailed description of various aspects of the property noted during the inspection.

Summary Page

The Summary Page is designed as a bulleted overview of all the observations noted during inspection. This helpful overview is not a substitution for reading the entire inspection report. The entire report must be read to get a complete understanding of this inspection report as the Summary Page does not include photographs or photo captions.

Summary

Major Concerns

  • G1-1 Garage:

    Extensive repairs are needed to the detached garage. Hire a licensed general contractor to further evaluate and repair. Examples of observations noted during inspection include:

    • Multiple garage openings are over-spanned / inadequately supported. Properly sized structural beams are needed.
    • Rot decay at the trim casing the overhead door openings.
    • Roof sags where inadequately supported.
    • North overhead door is missing the upper roller assembly.
    • Electrical service from home to garage/ and inside garage is substandard.
    • Roof is nearing end of useful life- Budget to replace.
  • RCG-1 Roof, Chimney and Gutters:

    The home's roof is done in a three tab composition shingle. The roof looks to be well past its reliable service life. Roof replacement is recommended to ensure reliable roof performance. Hire a qualified roofing contractor to further evaluate and replace this roof. Examples of specific observations noted during inspection include:

    • Excessive granule loss
    • Damaged shingle surfaces.
    • Multiple missing shingle tabs.
    • Substandard roof to wall flashing details.
    • Damaged ridge shingles.
    • No base and counter flashings at the chimney.
  • I1-2 Interior:

    Floor settlement was apparent in the rear laundry room. It is common in older buildings to have some amount of settlement, however, there is a lot of settlement here. I recommend additional inspection of this structure by a qualified general contractor or structural engineer. The scope and urgency for structural repairs in older buildings can be difficult to gauge well and even subjective; you may find contractors with differing points of view on the same issue. Implement repairs as recommended to prevent on-going movement and if possible to correct some of the settlement. Examples of observations noted during inspection include:

    • Structural support beam drops to the rear of the structure.
    • Inadequate structural support conditions.
    • Inadequate earth to wood clearances
    • Conditions concealed by sub floor insulation.
  • CS-1 Crawl Space:

    Overall, numerous repairs are needed to the crawl space below this house. I have made a series of detailed observations in the base of this report but given the extent of repairs I recommend further evaluation of this crawl space by a licensed general contractor as additional repairs could be needed that are latent or concealed. Examples of deficiencies noted in crawl space.

    • Animal droppings contaminating vapor barriers (cat, racoon, or similar)
    • Garbage/ debris in crawl space.
    • Inadequate plastic vapor barriers/ Missing, contaminated, damaged in places.
    • Areas of damaged and missing sub floor insulation from animals.
    • Earth to wood contacts at structural members in multiple locations.
    • Damage at sub structure from wood destroying organisms.

Repairs

  • G-1 Grounds:

    Downspouts are discharging adjacent to the foundation. This can cause foundation settlement or crawl space moisture problems. Make sure all downspouts discharge is directed away from the foundation. Splash blocks can often be adequate. The ideal system involves discharge of downspouts into a tight-line system that diverts water at least 5 feet away from the foundation.

  • ED-5 Exteriors and Decks:

    No tempered glass bug or logo was noted in the windows in the stairwell. Tempered or laminated glass is recommended in these locations for improved safety. Hire a glazing specialist to further evaluate and repair.

  • ED-6 Exteriors and Decks:

    Cracked glass was observed at a couple locations. Repair all unsound window glazing.

  • EDFW-2 Electric Distribution and Finish Wiring:

    The open electrical splice in the attic needs to be contained inside of a listed junction box. It is not recommended to splice onto wiring without use of a listed junction box. Additionally the wiring is under-sized which can create a fire hazard in itself. This is a sign of amateur wiring work which could indicate additional wiring defects that are latent and concealed. Have this further evaluated and repaired as recommended by a licensed electrician.

  • EDFW-5 Electric Distribution and Finish Wiring:

    The kitchen lighting has two intermittently functioning bulbs. It seems as if there is a connection issue at the fixture. Repair or replace.

  • HCFV-1 Heating, Cooling, Fireplaces and Ventilation:

    Unable to confirm operation of the gas heater. The pilot was working, but the unit/ blower fan failed to respond properly to the thermostat. Recommend an additional inspection by a licensed HVAC contractor and repairs. Note; This is a Williams Gas Wall Furnace. Williams Comfort Products still produces units like the one found in this home.

  • HCFV-4 Heating, Cooling, Fireplaces and Ventilation:

    The bathroom wall heater would not produce heat and the fan was running constantly. Repair or replace.

  • HCFV-5 Heating, Cooling, Fireplaces and Ventilation:

    The upstairs loft heater is missing a thermostat control knob. Replace.

  • K-3 Kitchen:

    An anti-tip device is needed to prevent this range from tipping during operation of the oven door. This is a small clip that secured the back adjustable feet of the range to the floor.

  • CS-3 Crawl Space:

    The plastic vapor barrier in the crawl space is incomplete, damaged, and contaminated in places. Use 6 mil black plastic to cover all exposed earth. This helps to reduce humidity and eliminate conducive pest conditions in the crawl space. Adjust the current vapor barrier or add more plastic as needed. Remove and replace all contaminated vapor barriers.

  • CS-4 Crawl Space:

    The screens for the crawl space vents are done in metal louvered covers. These can restrict air flow. Use 1/4 inch wire mesh screen and be sure all openings are well sealed to prevent rodent entry. Do not apply multiple layers of screen as this will restrict air flow. Make sure that sub floor insulation is not blocking vents and that they are placed around the foundation for adequate cross ventilation/ air circulation.

  • CS-6 Crawl Space:

    The sub-floor insulation in the crawl space has been damaged by what appears to be animals. Remove all damaged/ contaminated insulation and re-insulate. This work should be done in conjunction with exclusion measures.

Recommended Maintenance Items

  • ED-2 Exteriors and Decks:

    Localized siding repairs are needed to the exterior. There are multiple pieces of cracked siding. In the upper rear gable there are loose pieces of siding. Hire a licensed general contractor to further evaluate and repair all damaged siding as needed.

  • ED-3 Exteriors and Decks:

    A few minor areas for re-caulking were noted on the exterior - see around window frames. Preventative caulking maintenance can help keep these spots weather proof.

  • ED-4 Exteriors and Decks:

    Localized paint failure was noted at the exterior see especially where exposed to the weather. Implement localized painting as needed.

  • RCG-2 Roof, Chimney and Gutters:

    Failing mortar was noted at the masonry chimney above the roof line. This condition risks increased water entry and penetration into the masonry chimney which can lead to water damage, loose bricks and eventually a failing structure. Hire a licensed masonry contractor to further evaluate and repair the masonry chimney as recommended.

  • HCFV-2 Heating, Cooling, Fireplaces and Ventilation:

    Annual servicing of the gas forced air furnace is recommended for safe and reliable heat. I could not find recent service records on the furnace. The furnace was tested during inspection and was operational. The design life of these forced air furnaces is 15-20 years. I recommend having it serviced and keeping it on an annual service schedule until updated.

Improves

  • EDFW-3 Electric Distribution and Finish Wiring:

    The use of GFCI (Ground Fault Circuit Interruption) protection is inconsistent with modern minimum standards for safety - see kitchen countertops. GFCI protection is recommended for the electrical receptacles in the following locations: the two dedicated kitchen appliance circuits, all receptacles within 6 feet of a sink, bathrooms, exterior, garage, unfinished basements, laundry and all wet and damp locations. GFCI's protect against electrocution by limiting the duration of an electrical shock. These are an important modern safety feature that have proven to save lives. Hire a licensed electrician to further evaluate and update GFCI protection for improved safety.

  • EDFW-4 Electric Distribution and Finish Wiring:

    You may want to hire a licensed electrician to eliminate all open grounds. This is a common condition in older buildings (prior to 1962) where three prong receptacles have been installed on an older two wire system. (Related to the notes regarding the knob and tube wiring) This creates a safety hazard as it is false advertising; appliances that rely on an equipment ground to discharge a fault can be plugged into ungrounded circuits. This disables the important safety feature of an equipment ground. Proper repair can include:

    • Running an equipment grounding conductor or a new three-wire circuit
    • Filling the third prong of the receptacle or restoring a two-prong receptacle or
    • Installing GFCI protection for this circuit and labeling the open ground receptacles

    If GFCI protection is used, the outlets on this circuit should be labeled so it is clear they are protected.

  • K-2 Kitchen:

    A ductless exhaust fan was noted for the cook-top. Installation of a fan that ducts to the exterior is recommended to remove moist air and odors to the exterior. Please note that if you switch to a gas range or cooktop in the future, a fan that vents to the exterior is still not required, as long as there is some ventilation in the kitchen, but is more strongly recommended. Gas ovens produce carbon monoxide while running and should really have an exhaust vent to the exterior.

  • K-4 Kitchen:

    The gas range cooktop exhibited slow ignition. It is an older model and I would suggest upgrading with a new range / oven.

  • CS-5 Crawl Space:

    No positive connections were noted connecting some of the posts to the beams or the posts to the footings in the frame of the house. This is a standard practice in older construction, but makes the home more susceptible to seismic damage. Positive connections are recommended for improved seismic protection.

Monitors

  • G-2 Grounds:

    Inadequate clearance between the wood skirting and the soils was noted. This is conducive to wood destroying organisms as it can trap moisture against these materials. It is not evident if the plywood has been treated to prevent rot and damage by wood destroying organisms. Over time you will probably have to replace these materials if damage develops.

  • ED-7 Exteriors and Decks:

    Many of the wood windows in this home are exposed to the weather and will require regular painting and sealing maintenance to preserve the windows and prevent decay.

  • HCFV-3 Heating, Cooling, Fireplaces and Ventilation:

    No heat source was noted in parts of the home, like the bedrooms. An adequate heat supply is recommended for all finished square footage. It is hard to evaluate how comfortable the present heating sources will keep the home during the colder weather months during a summer home inspection. In some cases the lender may require heat sources to be installed as a condition of lending. You will have a better sense of whether additional heat sources will be needed after living in the home over the winter months. If areas are not comfortable, then you may want to hire a licensed electrician or heating contractor to install a heat source as needed.

  • P-2 Plumbing:

    Some of the waste plumbing system in this building is done with old metal pipe, while some of the waste pipe has been updated with plastic. No leaks were noted at the time of inspection, but updating and on-going repairs could be needed at any time. Old metal pipes are subject to internal corrosion which can make it impossible to spot older weaker pipe until it starts to leak. During any renovations to the home be sure to have this old piping evaluated and updated as recommended by a licensed plumber. As a general rule the old cast iron pipe often lasts a very long time - even as much as 100 years. Galvanized and copper waste pipe can have a shorter useful service life - sometime 50 years. The service life from this pipe has a lot to do with water quality and occupant behavior - use of cleaning chemicals like Drain-O can be tough on metal pipes.

Due Diligences

  • P-1 Plumbing:

    An evaluation of the sewer line below the ground is beyond the scope of this inspection. Due to the age and location of the building, a sewer scope is recommended to further evaluate the sewer line and the below ground connections between the house and the municipal sewer line. Sewer scopes are done using video cameras and can reveal the materials, condition and reliability of the sewer line.

  • I1-3 Interior:

    The stairs to the 2nd floor are old non-conforming stairs. Modern stairs have specific safety requirements regarding the size and configuration of the stair treads, risers, guardrails and handrails. This is typical of older stairs and it will not be cost effective to correct. Use caution when navigating these stairs. Improvements could be made to the handrail/ guardrail systems to improve the safety of the stairs. Consult with a qualified general contractor about options for improvements as feasible.

Future Projects

  • G-3 Grounds:

    Typical cracks were noted in walkway flatwork. No immediate repair appears necessary, though water will continue to deteriorate the surface until it is repaired or replaced.

  • EDFW-1 Electric Distribution and Finish Wiring:

    This home still appears to employ some knob and tube wiring. This is an old soldered style of wiring that would not meet today's standards. Some insurance companies will not insure homes with this type of wiring. During testing today I noted numerous ungrounded outlets as well as a few knob and tube circuits. I recommend consulting with a licensed electrician about ways to improve this system and take pressure off existing knob and tube. Installation of additional circuits and of arc fault protected breakers can help make the system safer and more reliable. Complete removal and replacement of all knob and tube is recommended but considerably more expensive and not always necessary. Many homes of this age in this area still employ at least a few knob and tube circuits. You need to update to a level you feel comfortable with.

  • I1-4 Interior:

    Some of the windows in this home are old wood windows that require maintenance and repair. They are in fairly typical condition for old wood windows where needed repairs include: windows that are painted shut, missing sash weights, cracked panes of glass and missing glazing. You need to decide how you want to approach the windows in this home as they are generally older and inefficient and do not comply with modern standards for safety glass. Repairs can be made on an as needed basis and efficiency can be added with storm windows and curtains. Existing windows that have character are often worth preserving and restoring, where windows that are in worse condition and have less character may be good candidates for replacement.

The Full Report

General Comments

Building Characteristics, Conditions and Limitations

Style of Home: Bungalow

Type of Building : Single Family (1 1/2 story)

Approximate Square Footage: 959

Approximate Year of Original Construction: 1930

Unless the wiring in the building has been fully updated, this building likely has wiring that predates the late 1980's. Branch circuit wiring installed in buildings built prior to the late 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring. It is beyond the scope of this inspection to determine if any such incompatible components are installed. Based on the age of this building, be aware that such components may be present.

In 1978, federal laws were past to prohibit use of lead and asbestos in building materials. Manufacturers of building materials were allowed to sell existing stocks of materials that were manufactured with lead and asbestos, so even buildings constructed as late as the mid-1980's could possibly contain lead or asbestos. Identification and testing for lead and asbestos and other environmental testing is beyond the scope of this home inspection. If you wish to seek additional information, I recommend contacting an environmental lab or industrial hygienist.

Attending the Inspection: Buyer and Buyer's Agent

Occupancy: Unoccupied

Animals Present: No

Weather during the inspection: Cloudy

Approximate temperature during the inspection: Below 65[F]

Ground/Soil surface conditions: Wet

For the Purposes of This Report, the Front Door Faces: East

This house was vacant / unoccupied at the time of inspection. Vacant and unoccupied houses present unique challenges for home inspection, especially the piping and wiring systems which have not be subject to regular use prior to the inspection. While these systems can be tested during inspection, this one-time test is different than regular use and it is difficult to know how these systems will respond to regular use after the inspection. For example, septic systems may initially function and then fail under regular daily use. Plumbing traps may operate with no signs of leaks and then let go when being actively used for a few days. Shower pans may only leak when someone is standing in the shower and taking a shower. Seals for plumbing fixtures can dry up and leak when not is use. Sewer lines with roots may allow water flow, but then fail when waste and tissue are flushed; it can take a few days for that to backup. Please understand we are trying our best to look for clues of past or existing problems to paint a realistic best-guess as to the reliability of these systems during inspection.

Grounds

Drainage and Site Information

Clearance to Grade: Siding Too Close to Soils - Monitor

Downspout Discharge: Above grade, Next to Foundation

(G-1) Repair:

Downspouts are discharging adjacent to the foundation. This can cause foundation settlement or crawl space moisture problems. Make sure all downspouts discharge is directed away from the foundation. Splash blocks can often be adequate. The ideal system involves discharge of downspouts into a tight-line system that diverts water at least 5 feet away from the foundation.

(G-2) Monitor:

Inadequate clearance between the wood skirting and the soils was noted. This is conducive to wood destroying organisms as it can trap moisture against these materials. It is not evident if the plywood has been treated to prevent rot and damage by wood destroying organisms. Over time you will probably have to replace these materials if damage develops.

Driveways/Walkways/Flatwork

Walkways: Concrete

(G-3) Future Project:

Typical cracks were noted in walkway flatwork. No immediate repair appears necessary, though water will continue to deteriorate the surface until it is repaired or replaced.

Exteriors and Decks

Exterior Elevations

Siding and Trim

Trim Material: Wood

Siding Material: Wood

(ED-2) Recommended Maintenance:

Localized siding repairs are needed to the exterior. There are multiple pieces of cracked siding. In the upper rear gable there are loose pieces of siding. Hire a licensed general contractor to further evaluate and repair all damaged siding as needed.

(ED-3) Recommended Maintenance:

A few minor areas for re-caulking were noted on the exterior - see around window frames. Preventative caulking maintenance can help keep these spots weather proof.

(ED-4) Recommended Maintenance:

Localized paint failure was noted at the exterior see especially where exposed to the weather. Implement localized painting as needed.

Eaves

Open rafters

Exterior Doors

Glass panel doors

Exterior Window Frames

Wood, Vinyl

(ED-5) Repair:

No tempered glass bug or logo was noted in the windows in the stairwell. Tempered or laminated glass is recommended in these locations for improved safety. Hire a glazing specialist to further evaluate and repair.

(ED-6) Repair:

Cracked glass was observed at a couple locations. Repair all unsound window glazing.

(ED-7) Monitor:

Many of the wood windows in this home are exposed to the weather and will require regular painting and sealing maintenance to preserve the windows and prevent decay.

Fuel Storage and Distribution

Gas Meter

Present

Gas Shutoff Location: East side of structure

Gas Pipe Materials: Steel


Gas, Propane and Oil Piping

Gas Piping Materials Noted: Steel

Garage

Garage General

Garage Type: Detached

Garage Doors and Automatic Openers

Overhead Garage Door Type: Wood, Metal

Automatic Garage Opener: Present

(G1-1) Major Concern:

Extensive repairs are needed to the detached garage. Hire a licensed general contractor to further evaluate and repair. Examples of observations noted during inspection include:

  • Multiple garage openings are over-spanned / inadequately supported. Properly sized structural beams are needed.
  • Rot decay at the trim casing the overhead door openings.
  • Roof sags where inadequately supported.
  • North overhead door is missing the upper roller assembly.
  • Electrical service from home to garage/ and inside garage is substandard.
  • Roof is nearing end of useful life- Budget to replace.

Garage Floor

Garage Slab: Concrete

Roof, Chimney and Gutters

Roof Materials

Method of Roof Inspection: Walked on roof

Roof Style: Gable, Low slope

Flashings: Non-Standard

Roof Covering Materials: Three-tab composition shingle

Approximate Age of Roof Covering: 20+ Years

(RCG-1) Major Concern:

The home's roof is done in a three tab composition shingle. The roof looks to be well past its reliable service life. Roof replacement is recommended to ensure reliable roof performance. Hire a qualified roofing contractor to further evaluate and replace this roof. Examples of specific observations noted during inspection include:

  • Excessive granule loss
  • Damaged shingle surfaces.
  • Multiple missing shingle tabs.
  • Substandard roof to wall flashing details.
  • Damaged ridge shingles.
  • No base and counter flashings at the chimney.

Chimneys

Present

Chimney Material: Masonry

Chimney Flue Liners: None noted

(RCG-2) Recommended Maintenance:

Failing mortar was noted at the masonry chimney above the roof line. This condition risks increased water entry and penetration into the masonry chimney which can lead to water damage, loose bricks and eventually a failing structure. Hire a licensed masonry contractor to further evaluate and repair the masonry chimney as recommended.

Gutters and Downspouts

Gutter and Downspout Materials: Aluminum

Electric Service

Electric Service Voltage

Service Voltage: 120/240

Electric Service

Service Entrance: Above Ground

Meter Base Amperage: 200

Electric Service Equipment

Service Entrance (SE) conductor Size: Aluminum, 4/0, 200 amps

Main Panel Amperage: 200 amps

Electric Service Amperage: 200 amps

Main Electric Panel Location: Utility room

Panel Manufacturer: Square D


Electrical Grounding System

Grounding Rod Noted

Ground rod connections were noted at the exterior. The ground rods looked to be fully driven and connections looked standard,

Electrical Bonding System

Bonding Noted on Water Pipes, Bonding Noted on Gas Pipes

Electric Distribution and Finish Wiring

Branch Wiring

Wire Material: Copper

Wiring Method: Non-metallic sheathed cable, Knob and tube

(EDFW-2) Repair:

The open electrical splice in the attic needs to be contained inside of a listed junction box. It is not recommended to splice onto wiring without use of a listed junction box. Additionally the wiring is under-sized which can create a fire hazard in itself. This is a sign of amateur wiring work which could indicate additional wiring defects that are latent and concealed. Have this further evaluated and repaired as recommended by a licensed electrician.

(EDFW-1) Future Project:

This home still appears to employ some knob and tube wiring. This is an old soldered style of wiring that would not meet today's standards. Some insurance companies will not insure homes with this type of wiring. During testing today I noted numerous ungrounded outlets as well as a few knob and tube circuits. I recommend consulting with a licensed electrician about ways to improve this system and take pressure off existing knob and tube. Installation of additional circuits and of arc fault protected breakers can help make the system safer and more reliable. Complete removal and replacement of all knob and tube is recommended but considerably more expensive and not always necessary. Many homes of this age in this area still employ at least a few knob and tube circuits. You need to update to a level you feel comfortable with.

Receptacles and Fixtures

Inspection Method: Random Testing

Electric Receptacles: Open Grounds in Old House

(EDFW-5) Repair:

The kitchen lighting has two intermittently functioning bulbs. It seems as if there is a connection issue at the fixture. Repair or replace.

(EDFW-3) Improve:

The use of GFCI (Ground Fault Circuit Interruption) protection is inconsistent with modern minimum standards for safety - see kitchen countertops. GFCI protection is recommended for the electrical receptacles in the following locations: the two dedicated kitchen appliance circuits, all receptacles within 6 feet of a sink, bathrooms, exterior, garage, unfinished basements, laundry and all wet and damp locations. GFCI's protect against electrocution by limiting the duration of an electrical shock. These are an important modern safety feature that have proven to save lives. Hire a licensed electrician to further evaluate and update GFCI protection for improved safety.

(EDFW-4) Improve:

You may want to hire a licensed electrician to eliminate all open grounds. This is a common condition in older buildings (prior to 1962) where three prong receptacles have been installed on an older two wire system. (Related to the notes regarding the knob and tube wiring) This creates a safety hazard as it is false advertising; appliances that rely on an equipment ground to discharge a fault can be plugged into ungrounded circuits. This disables the important safety feature of an equipment ground. Proper repair can include:

  • Running an equipment grounding conductor or a new three-wire circuit
  • Filling the third prong of the receptacle or restoring a two-prong receptacle or
  • Installing GFCI protection for this circuit and labeling the open ground receptacles

If GFCI protection is used, the outlets on this circuit should be labeled so it is clear they are protected.

Ceiling Fans

Ceiling Fans: Present and Tested

Smoke and Carbon Monoxide Alarm Systems

CO Alarms Noted:On Main Floor

CO Alarms: Present

Smoke Alarms Noted:On Main Floor

Smoke Alarms: Present

During the home inspection, I try and test a representative sample of the smoke alarms by using the test button on the alarms. This is NOT an accurate test of the sensor just a test to see if the unit is powered. For reliability, fire marshals recommended updating smoke alarms every 10 years and changing batters bi-annually. The latest data indicate that we should be using photo-electric technology in our smoke alarms for improved fire detection and to reduce problems with false alarms which can lead to disabling of this important safety system. Unfortunately, the alarms have to be removed to determine if they are photo-electric or ionization types. It is surprisingly complex to accurately test a smoke alarm system and determine the reliability, age, and type of sensor technology used, especially as many homes can have half a dozen or more alarms throughout the house. A complete evaluation of smoke alarms is beyond the scope of this inspection. For optimal fire safety, I recommend taking control of these important safety devices and learning about how to service and maintain your smoke alarm system to keep the building occupants safe.

(EDFW-6) Note:

Carbon monoxide alarms were found and noted during inspection. Be sure to check these regularly. The standard is 1/ floor and 1 outside all sleeping areas.

Heating, Cooling, Fireplaces and Ventilation

Heating System

Energy Source: Natural gas

Heating Method: Gas forced air furnace

This house has a gas forced air furnace. A critical component to all combustion equipment like this is the heat exchanger. This is the welded clam-shell piece of metal inside the furnace that contains the products of combustion so that moisture, carbon monoxide and other products of combustion do not mix with interior air and get safely vented to the exterior. Heat exchangers on modern furnaces have an average life expectancy of 15-20 years. Unfortunately, heat exchangers are buried inside of heating equipment; they are not visible and specifically excluded from a home inspection.

Manufacturer: Williams

Capacity: 60,000 btu's

Age: 60 years estimated.

Last Service Record: None

(HCFV-1) Repair:

Unable to confirm operation of the gas heater. The pilot was working, but the unit/ blower fan failed to respond properly to the thermostat. Recommend an additional inspection by a licensed HVAC contractor and repairs. Note; This is a Williams Gas Wall Furnace. Williams Comfort Products still produces units like the one found in this home.

(HCFV-2) Recommended Maintenance:

Annual servicing of the gas forced air furnace is recommended for safe and reliable heat. I could not find recent service records on the furnace. The furnace was tested during inspection and was operational. The design life of these forced air furnaces is 15-20 years. I recommend having it serviced and keeping it on an annual service schedule until updated.

Heating and Cooling Distribution Systems

Heat Source in Each Room: Incomplete

(HCFV-3) Monitor:

No heat source was noted in parts of the home, like the bedrooms. An adequate heat supply is recommended for all finished square footage. It is hard to evaluate how comfortable the present heating sources will keep the home during the colder weather months during a summer home inspection. In some cases the lender may require heat sources to be installed as a condition of lending. You will have a better sense of whether additional heat sources will be needed after living in the home over the winter months. If areas are not comfortable, then you may want to hire a licensed electrician or heating contractor to install a heat source as needed.

Additional Heat Sources

Description: Wall-mounted forced air electric heaters

(HCFV-4) Repair:

The bathroom wall heater would not produce heat and the fan was running constantly. Repair or replace.

(HCFV-5) Repair:

The upstairs loft heater is missing a thermostat control knob. Replace.

Plumbing

Water Service Supply

Pipe Material: Copper

Water Supply: Public water

Water Pressure: OK

Pressure Reducing Valve: None noted

Main Water Shut-off Location: Meter

Distribution Pipe

Pipe Insulation: Present

Supply Pipe Materials: Copper

Functional Flow: Average

Waste Pipe and Discharge

Discharge Type: Public sewer

Please note that when the sewage discharge type is listed here, it is listed based on public records and disclosure. It is always possible that the system is not as it is listed; for example, a property could be listed as a public sewer system when in fact it is on a private septic system. This is unlikely, but is another reason why we recommend further evaluation of all sewage discharge systems.

(P-2) Monitor:

Some of the waste plumbing system in this building is done with old metal pipe, while some of the waste pipe has been updated with plastic. No leaks were noted at the time of inspection, but updating and on-going repairs could be needed at any time. Old metal pipes are subject to internal corrosion which can make it impossible to spot older weaker pipe until it starts to leak. During any renovations to the home be sure to have this old piping evaluated and updated as recommended by a licensed plumber. As a general rule the old cast iron pipe often lasts a very long time - even as much as 100 years. Galvanized and copper waste pipe can have a shorter useful service life - sometime 50 years. The service life from this pipe has a lot to do with water quality and occupant behavior - use of cleaning chemicals like Drain-O can be tough on metal pipes.

(P-1) Due Diligence:

An evaluation of the sewer line below the ground is beyond the scope of this inspection. Due to the age and location of the building, a sewer scope is recommended to further evaluate the sewer line and the below ground connections between the house and the municipal sewer line. Sewer scopes are done using video cameras and can reveal the materials, condition and reliability of the sewer line.

Water Heater

Manufacturer: Rheem

Data Plate: This shows the data plate for the water heater

This shows the listing plate on the water heater.

System Type: Tank

Size: 50 gal

Age: 2013

Energy Source: Gas

Straps : Present

Drain Pan: Present

Expansion Tank: Present

Temperature Pressure Relief Valve: Present - Not Tested

The temperature and pressure relief valve is arguably one of the most important safety devices in your house. Should the thermostats fail inside your water heater, the TPRV allows excess pressure to "blow off," which will prevent catastrophic build up of temperature and pressure which can make water heaters explosive. I do not test the "blow off valve" during inspection as there is a risk it could stick open and testing could cause the need for a repair. Manufacturers of these relief valves recommend that these be tested annually. You need to decide for yourself if this is the type of annual testing you wish to perform.

Exterior Hose Bibs

Operating

Laundry and Additional Plumbing

Washer

Not included

(LAP-1) Note:

Apparently, the washer and dryer appliances are not included in this sale.

Dryer

Power Source: Electric

Exhaust Duct: Ducted to Exterior

Interior

General Interior Photos

Floors and Floor Materials

Floor Materials: Softwood

Floor Settlement: Moderate (Additional Inspection Recommended - Show Examples)

(I1-2) Major Concern:

Floor settlement was apparent in the rear laundry room. It is common in older buildings to have some amount of settlement, however, there is a lot of settlement here. I recommend additional inspection of this structure by a qualified general contractor or structural engineer. The scope and urgency for structural repairs in older buildings can be difficult to gauge well and even subjective; you may find contractors with differing points of view on the same issue. Implement repairs as recommended to prevent on-going movement and if possible to correct some of the settlement. Examples of observations noted during inspection include:

  • Structural support beam drops to the rear of the structure.
  • Inadequate structural support conditions.
  • Inadequate earth to wood clearances
  • Conditions concealed by sub floor insulation.

Walls, Ceilings, Trim and Closets

Wall and Ceiling Materials: Drywall

Wall Insulation and Air Bypass

Wall Insulation: Not Visible

Stairs and Railings

Old Non-Conforming Stairs

(I1-3) Due Diligence:

The stairs to the 2nd floor are old non-conforming stairs. Modern stairs have specific safety requirements regarding the size and configuration of the stair treads, risers, guardrails and handrails. This is typical of older stairs and it will not be cost effective to correct. Use caution when navigating these stairs. Improvements could be made to the handrail/ guardrail systems to improve the safety of the stairs. Consult with a qualified general contractor about options for improvements as feasible.

Windows

Window Glazing: Single pane, Single pane and storm windows

Interior Window Frame: Wood, Vinyl

Window Styles: Double hung, Sliding, Single hung

(I1-4) Future Project:

Some of the windows in this home are old wood windows that require maintenance and repair. They are in fairly typical condition for old wood windows where needed repairs include: windows that are painted shut, missing sash weights, cracked panes of glass and missing glazing. You need to decide how you want to approach the windows in this home as they are generally older and inefficient and do not comply with modern standards for safety glass. Repairs can be made on an as needed basis and efficiency can be added with storm windows and curtains. Existing windows that have character are often worth preserving and restoring, where windows that are in worse condition and have less character may be good candidates for replacement.

Kitchen

General Kitchen Photos


Sinks and Faucets

Tested

Cabinets and Countertops

Countertop Material: Plastic laminate

Cabinet Material: Wood

Ventilation Method

Ductless Fan - Electric

(K-2) Improve:

A ductless exhaust fan was noted for the cook-top. Installation of a fan that ducts to the exterior is recommended to remove moist air and odors to the exterior. Please note that if you switch to a gas range or cooktop in the future, a fan that vents to the exterior is still not required, as long as there is some ventilation in the kitchen, but is more strongly recommended. Gas ovens produce carbon monoxide while running and should really have an exhaust vent to the exterior.

Appliances

Refrigerator: Operating

Dishwasher: None noted

Range/ Oven /Cook-tops: Gas, No Anti-Tip

(K-3) Repair:

An anti-tip device is needed to prevent this range from tipping during operation of the oven door. This is a small clip that secured the back adjustable feet of the range to the floor.

(K-4) Improve:

The gas range cooktop exhibited slow ignition. It is an older model and I would suggest upgrading with a new range / oven.

General Kitchen Condition

Standard

Family Bathroom

General Bathroom Photos


Sinks and Cabinets

Tested

Toilet

Tested

Bathtub / Shower

Tested

Bathroom Ventilation

Type: Fan and window

General Bath Condition

Standard

Attic

Attic Access

Viewed at access, Limited Access - Vaulted Ceiling - Partial

Roof Framing and Sheathing

Rafters: Rafters

Sheathing: Skip sheathing, OSB Panels

Attic Insulation

Insulation Type: Not visible, (mostly)

Crawl Space

General Crawl Space

(CS-1) Major Concern:

Overall, numerous repairs are needed to the crawl space below this house. I have made a series of detailed observations in the base of this report but given the extent of repairs I recommend further evaluation of this crawl space by a licensed general contractor as additional repairs could be needed that are latent or concealed. Examples of deficiencies noted in crawl space.

  • Animal droppings contaminating vapor barriers (cat, racoon, or similar)
  • Garbage/ debris in crawl space.
  • Inadequate plastic vapor barriers/ Missing, contaminated, damaged in places.
  • Areas of damaged and missing sub floor insulation from animals.
  • Earth to wood contacts at structural members in multiple locations.
  • Damage at sub structure from wood destroying organisms.

The photos provided here show representative images of this crawl space at the time of inspection.

Crawl Space Access

Method of Inspection: Crawled

During inspection of the crawl space, every effort is made to inspect the entire space. Visual inspection of crawl spaces is difficult and limited as access is often restricted by pipes, ducts and sub-floor insulation as well as limited clearances.

Vapor Barrier

Vapor Barrier Material: Plastic on earth, Incomplete

(CS-3) Repair:

The plastic vapor barrier in the crawl space is incomplete, damaged, and contaminated in places. Use 6 mil black plastic to cover all exposed earth. This helps to reduce humidity and eliminate conducive pest conditions in the crawl space. Adjust the current vapor barrier or add more plastic as needed. Remove and replace all contaminated vapor barriers.

Crawl Space Ventilation

Ventilation Method: Screens (Louvered Vents Restrict Ventilation)

(CS-4) Repair:

The screens for the crawl space vents are done in metal louvered covers. These can restrict air flow. Use 1/4 inch wire mesh screen and be sure all openings are well sealed to prevent rodent entry. Do not apply multiple layers of screen as this will restrict air flow. Make sure that sub floor insulation is not blocking vents and that they are placed around the foundation for adequate cross ventilation/ air circulation.

Posts and Footings

(CS-5) Improve:

No positive connections were noted connecting some of the posts to the beams or the posts to the footings in the frame of the house. This is a standard practice in older construction, but makes the home more susceptible to seismic damage. Positive connections are recommended for improved seismic protection.

Insulation

Insulation Type: Fiberglass

Approximate R-Value: R-19

(CS-6) Repair:

The sub-floor insulation in the crawl space has been damaged by what appears to be animals. Remove all damaged/ contaminated insulation and re-insulate. This work should be done in conjunction with exclusion measures.

Moisture Conditions

No water was visible or present at the time of inspection

Structure and Basement

Foundation

Evidence of Seismic Protection: None Found - Old House, (Post & Pier)

Building Configuration: Crawl space

Foundation Description: Post and pier

Floor, Wall and Ceiling Framing

Wall Framing: Not visible

Wall Sheathing: Not visible

Floor Framing: Partly visible, 2x8

Sub-Floor Material: Shiplap, Partly visible, Glimpsed through insulation

Ceiling Framing: Not visible

(SB-1) Note:

Please note that the floor frame system was not visible as this sub-floor is well-insulated. I had to just spot check framing for damage.

Checking Out Procedure

Check Out List

Oven:Off

Lights:Client and Realtor Still In House

Heating and Cooling:Restored to Pre-inspection temperatures

Appliances:Off / finishing cycle

Signed Contracts