How to Read This Report
This digital report or a printed version of this report should only be viewed in full color where the photos are discernible and on a device where the report page width is no less than 8.5" wide. Please note, Right and Left of the building are determined as facing the front of building shown on the report cover. The client has the duty and obligation to read the entire report. Feel free to reach out to the inspector should you have any questions or concerns.
This report is designed to inform the client of obvious major structural deficiencies, inoperative conditions and the presence of noticeable, detrimental moisture issues for areas inspected. Additionally, the inspection report may advise regarding notable safety concerns and appropriate upgrades recommended by the inspector that you should consider and act on when appropriate. Please note, undesirable conditions pertaining to this inspection may be present and unreported for concealed areas and areas with limited or blocked access.
Photos
Photos included in this report are intended to help describe a reported item or area only. The photos, while representative, may not encompass the full scope of work required to correct the item or area listed. Repairs should be based on actual condition of property and not solely on the photos included in this report. Note, when viewing photos in the online report, clicking on a photo will zoom in and enlarge the photo. Clicking on a photo a second time will enlarge and zoom in on the photo one more time.
Repairs
Repairs or corrections needed at the inspected property should be completed by competent qualified professions familiar with the type of work being performed. Obtain competitive bids as needed. Obtain further evaluation when needed.
Getting the Information to You
This report is designed to deliver important and technical information in a way that is easy to access and understand. The best way to get the layers of information that are presented in this report is to read your report online in the HTML format, which will allow you to expand your learning about the inspected property. You will notice some words or series of words highlighted in blue and underlined – clicking on these will provide you with a link to additional information, if desired. Other text colors, if present, have no real meaning. Please read all written text.
This report can also be printed on paper or to a PDF document.
Chapters and Sections
This report is divided into chapters that parcel the home into logical inspection components. Each chapter is broken into sections that relate to a specific system or component of the home. You can navigate between chapters with the click of a button on the left side margin when viewing the report online.
Observation Labels
Narrative observation labels are defined here. Some of the following observation labels may not appear in all reports. Hazardous, Key Concerns and Further Evaluation observation label types, if used, will appear in the report and in the summary. All other observation labels, when used, appear only in the report and will not appear in the summary. All narrative observation label types are labeled, and numbered to help differentiate each reported narrative observation. When narrative observation labels are given a color, the specific color used has no meaning. Some observation labels are given a specific icon to group the observation types. The specific icon used also has no meaning.
Observation labels and colors used for reporting are:
- Key Concerns:Observations listed as key concerns need repair or correction and will typically include inoperative equipment, common and significant corrections needed for plumbing, electrical, heating/cooling, structure, interior and exterior areas including the roof covering. When used, this observation will appear in the report and in the summary.
- Further Evaluation:Observations listed as further evaluation need a more extensive or technically exhaustive evaluation and warrant further investigation by a specialist. For areas where corrections may not be straight forward or where a proper plan should be developed to implement corrections, then further evaluation is recommended. To obtain further evaluation is to hire a specialist that is highly experienced in the repair or correction of a specific item or area. Some observations listed under other labels that also require further evaluation will appear under the other label only. When used, this observation will appear in the report and in the summary.
- Periodic Maintenance Needed:Observations listed as periodic maintenance needed are items or areas that need repair or correction and are expected to have maintenance performed at some interval. Maintenance neglect may be from lack of maintenance knowledge or lack of adequate funding for periodic maintenance. Some irregular or substandard installations may need more frequent maintenance until properly replaced. Start dates and intervals for periodic maintenance are a matter of personal judgment. When used, this observation will appear only in the report.
- Safety Concerns:Observations listed as safety concerns are items or areas listed to help reduce the risk of personal injury and should be considered for repair, correction or upgrade. Safety standards and expectations change. Consideration should be given to evaluate and act upon your risk exposure to help reduce the risk of personal injury. Some observations listed under other labels that are also safety concerns will appear under the other label only, such as electrical repairs, which almost always pose some safety risk. Some safety concerns may also be considered improvements but will fall under the safety concerns label if deemed more appropriate. When used, this observation will appear only in the report.
- Routine Correction Needed:Observations listed as routine correction need repair or correction and are not unusual for the type and age property inspected. These routine items are typically not recurring and once properly corrected should not require repetitive correction. When used, this observation will appear only in the report.
- Monitor:Observations listed as monitor are typically items or areas that need subsequent observations and should be monitored over time to obtain historical data. These items may or may not require correction in the future based upon their performance over time. If you are unable to do the monitoring, the inspector recommends you appropriately schedule monitoring by a qualified competent contractor. Some observations listed under other labels that also may require monitoring will appear under the other label only. When used, this observation will appear only in the report.
- Improve:Observations listed as improve are items or areas that were ready for repair or correction that involve improvement or upgrade. This label is used for predictable expected opportunities to better the property condition or installation deficiencies that may or may not affect equipment function. Some observations listed under other labels that also may be considered improvements will appear under the other label only. When used, this observation will appear only in the report.
- Note:Notes are general remarks or comments elaborating on descriptions of systems, limitations, restrictions, or other similar conditions present during the inspection. Notes do not appear in the summary.
- Inspector Informational Note:Inspector informational note regarding inspection process.
- Description:Descriptive information for various aspects of the property, equipment, items, or areas noted during the inspection. Descriptions do not appear in the summary.
- Deck Description:Description of observed deck conditions and issues.
Summary Page
For convenience, the report contains a summary. The inspector uses the Summary to list non Periodic Maintenance issues that, in his opinion, he would expect to be completed before marketing the home for sale. Be advised, the summary contains only text from the observations listed as Key Concerns, Further Evaluation Needed, Hazardous and when applicable, New Construction Builder Punch List Items. The summary does not show any photos or photo captions that may be listed with an observation. The summary provides the least information for the observations listed.
The report body contains the most information and includes full descriptions, digital photographs, captions, and when applicable, diagrams, videos and hot links to additional information. Refer to the report body when making actual corrections, upgrade or repairs. Please understand that you have a duty and obligation to read the full report.
Summary
Key Concerns
- P-1 PLUMBING:
Water Heater
Water heater temperature and pressure relief valve had discharge extension piping that was not rated for hot water and this pipe should be properly replaced.
- PVC piping is not rated for use with hot water and should not be used at water heater for temperature and pressure relief valve discharge piping.
Refer to discharge piping general guidelines. Proper correction is needed for correct function and safety.
- E-1 ELECTRICAL:
Main Breaker Panel Garage at Upper Area
Corrections were needed at electrical distribution panel.
Refer to the full report for additional information and photos regarding obvious corrections recommended for this electrical panel. Make proper corrections as needed for safety and function now.
- E-2 ELECTRICAL:
Electrical Receptacle Outlet Damaged Basement
One or more damaged electrical receptacles were observed. Properly correct damaged electrical receptacles where needed for function and safety.
- The electrical receptacle in the basement hall was loose and damaged. Replace where needed.
- E-3 ELECTRICAL:
Lighting/fans - Make lighting/fans functional and safe where needed.
- Some lighting was inoperative when inspected.
- Some lighting was not fully functional when inspected.
- Some light fixtures were damaged.
Check all lighting/fans making functional and safe where needed.
Representative Photos Provided
- D-1 DECK:
Deck areas were observed ready for corrections now to improve the structure of the deck and to improve the safety aspects for the fall prevention measures installed at deck areas. Refer to the full report for additional information and photos regarding obvious corrections recommended now for any deck areas. A competent deck contractor should check all deck areas. Make deck areas functional, safe and structurally sound where needed.
Further Evaluations
- G2-1 Gas:
Gas Service Appeared Off
The gas supply appeared to be off during the inspection. Installed accessible gas appliances were inspected but not observed in operation.
- Further evaluation of the gas system should be completed by a competent qualified contractor.
- Determine, if possible, the reason that the gas system was shut down or inoperative.
- Take steps to prevent recurrence.
- Properly put the gas system back in service correcting as needed for function and safety.
- Verify all appliances, piping and fixtures requiring gas are fully functional and safe correcting where needed.
The Full Report
INTERIOR
Interior Access / Ceilings / Walls / Floor Coverings
Doors
Glazing/Glass
Stairs/Railings Interior
PLUMBING
Supply Piping
Waste Piping
Apparent Vent Piping
Exterior Hose Faucets
Water Heater
Equipment Observed
ELECTRICAL
Electrical Inspection
Electrical Service
MAIN PANEL
Branch Wiring
AFCI
GFCI
Receptacle Outlets
Lighting/Ceiling Fans
Switches
Smoke Alarms
STRUCTURE
Attic Access
Roof Framing
Ceiling Framing
Wall Framing
Underfloor Access
Underfloor Description
Floor System
SIDING and TRIM
Exterior Elevations
Siding
Masonry Siding
Siding - Cement Fiber
Siding - Concrete Tile
Siding - Stucco
Siding - Vinyl
DECK
Deck or Wooden Porch Areas Overall Condition Statement
Deck or Wooden Porch Location, Attributes and Restrictions
Deck or Wooden Porch Structure
About the Inspection Process
Home Inspection: Scope and Purpose of a Home Inspection
The Scope and Purpose of a Home Inspection
Purchasing property involves risk
The purpose of a home inspection is to help reduce the risk associated with the purchase of a structure by providing a professional opinion about the overall condition of the structure. A home inspection is a limited visual inspection and it cannot eliminate this risk. Some homes present more risks than others. We cannot control this, but we try to help educate you about what we don’t know during the inspection process. This is more difficult to convey in a report and one of many reasons why we recommend that you attend the inspection.
A home inspection is not an insurance policy
This report does not substitute for or serve as a warranty or guarantee of any kind. Home warranties can be purchased separately from insuring firms that provide this service.
A home inspection is visual and not destructive.
The descriptions and observations in this report are based on a visual inspection of the structure. We inspect the aspects of the structure that can be viewed without dismantling, damaging or disfiguring the structure and without moving furniture and interior furnishings. Areas that are concealed, hidden or inaccessible to view are not covered by this inspection. Some systems cannot be tested during this inspection as testing risks damaging the building. For example, overflow drains on bathtubs are generally not tested because if they were found to be leaking they could damage the finishes below. Our procedures involve non-invasive investigation and non-destructive testing which will limit the scope of the inspection.
This is not an inspection for code compliance
This inspection and report are not intended for city / local code compliance. During the construction process structures are inspected for code compliance by municipal inspectors. Framing is open at this time and conditions can be fully viewed. Framing is not open during inspections of finished homes, and this limits the inspection. All houses fall out of code compliance shortly after they are built, as the codes continually change. National codes are augmented at least every three years for all of the varying disciplines. Municipalities can choose to adopt and phase in sections of the codes on their own timetables. There are generally no requirements to bring older homes into compliance unless substantial renovation is being done.
This is just our opinion
Construction techniques and standards vary. There is no one way to build a house or install a system in a house. The observations in this report are the opinions of the home inspector. Other inspectors and contractors are likely to have some differing opinions. You are welcome to seek opinions from other professionals.
The scope of this inspection
This inspection will include the following systems: exterior, roof, structure, drainage, foundation, attic, interior, plumbing, electrical and heating. The evaluation will be based on limited observations that are primarily visual and non-invasive. This inspection and report are not intended to be technically exhaustive.
Your expectations
The overall goal of a home inspection is to help ensure that your expectations are appropriate with the house you are proposing to buy. To this end we assist with discovery by showing and documenting observations during the home inspection. This should not be mistaken for a technically exhaustive inspection designed to uncover every defect with a building. Such inspections are available but they are generally cost-prohibitive to most home buyers.
Home Inspection: Home Inspection Agreement
Inspection Agreement
Major Structural and Electromechanical Inspection
HomePro Inspection, Inc. agrees to conduct an inspection for the purpose of informing the CLIENT of major deficiencies in the condition of the property in accordance with the Standards as set forth by the American Society of Home Inspectors (ASHI) and the State of Tennessee. The inspection and written report are performed and prepared for the sole, confidential and exclusive use and possession of the CLIENT; the report is nontransferable.
The written report will include the following only:
- general exterior, including roof, siding, windows, chimney, drainage and grading
- structural condition of foundation & frame
- electrical, plumbing, hot water heater, heating and air conditioning
- general interior, including ceilings, walls, floors, windows, insulation and ventilation
Maintenance and other items may be discussed but they are not a part of the inspection. The report is not a compliance inspection or certification for past or present governmental codes or regulations of any kind and is only based on the inspector’s opinions.
It is understood and agreed that the inspection will be of readily accessible areas of the building and is limited to visual observations of apparent conditions existing at the time of the inspection only. Latent and concealed defects and deficiencies are excluded from the inspection; equipment, items and systems will not be moved or dismantled. When the inspection is for only one or a limited number of systems or components, the inspection is limited to only those systems or components that were inspected. Detached structures are not included. HomePro Inspection, Inc. will be under no obligation under any circumstances for any further follow-up inspection.
ENVIRONMENTAL HAZARDS including Asbestos, Mold, Fungus, Lead, Radon, Cockroaches, Rodents, Pesticides, Treated Lumber, Mercury, Carbon Monoxide, Urea Formaldehyde, Toxic Wastes, Polluted Water, Contaminants and all Pollutants and Hazardous Materials or other similar environmental hazards are not part of this Home Inspection. In addition, no inspection for household insects or unwanted animals will be done.
This report does not address Subterranean Systems or system components for Sewage Disposal, Water Supply, or Fuel Storage or Delivery. Auxiliary systems such as Alarm, Security, Intercom, other low voltage wiring, Generator, Private Water, Sprinkler, Elevator, Central Vacuum, Refrigerators, Laundry Equipment, Solar, Swimming Pools, Hot Tubs, Saunas, Space Heaters, Window Air Conditioners and or any system not considered a part of the major building systems are not a part of the inspection process.
The parties agree that the HomePro Inspection, Inc., and its employees and agents, assume no liability or responsibility for the cost of repairing or replacing any unreported defects or deficiencies, either current or arising in the future, or for any property damage, consequential damage or bodily injury of any nature. THE INSPECTION AND REPORT ARE NOT INTENDED AS A GUARANTEE OR WARRANTY, EXPRESSED OR IMPLIED INCLUDING REGARDING THE ADEQUACY, OR PERFORMANCE OF ANY INSPECTED STRUCTURE, ITEM OR SYSTEM. THE HOMEPRO INSPECTION, INC. IS NOT AN INSURER OF ANY INSPECTED CONDITIONS.
It is understood and agreed that should HomePro Inspection, Inc. and/or its agents or employees be found liable for any loss or damages resulting from a failure to perform any of its obligations, including but not limited to negligence, breach of contract or otherwise, then the liability of HomePro Inspection, Inc. and/or its agents or employees, shall be limited to a sum equal to the amount of the fee paid by the CLIENT for the Inspection and Report.
The parties agree that the faxed or digital copy of the agreement is to be relied upon in lieu of the original.
Acceptance and understanding of this agreement are hereby acknowledged:
Be Proactive Regarding Maintenance:
How much should you budget to maintain a home in the Chattanooga area?
As a general rule, a proper home maintenance budget should be about 2-5% of the value of the home annually. This maintenance budget would include periodic maintenance, general repairs, lawn care, housekeeping and saving any excess funds to budget for predictable replacement of the water heater, central heating/cooling and the roof covering. Should you choose to perform any of these tasks yourself, you should have fewer out of pocket expenditures to properly maintain your home.
General Comments
Building Characteristics, Conditions and Limitations
Type of Building : Single Family Home
Site Built
Approximate Square Footage: 2900
Approximate Year of Original Construction: 2009
INTERIOR
Interior Access / Ceilings / Walls / Floor Coverings
Interior Access: Furniture, Property, Rugs, Nearly Empty of Furnishings
Access and visibility was limited at interior areas as furnishings, personal property and area rugs were present.
Home was nearly empty of furnishings when inspected.
________________________________________________________________________________________________________________________________________________________________
Ceilings
Interior Ceiling Materials: Drywall
Interior Ceiling Condition:
- Serviceable, fulfilling its function
Low Ceiling
________________________________________________________________________________________________________________________________________________________________
Wall Area
Interior Wall Materials: Drywall
Interior Wall Condition:
- Some wear noted.
- Recondition to your standard.
________________________________________________________________________________________________________________________________________________________________
Flooring
Interior Flooring Materials: Wood, Engineered Flooring, and Tile
- Some wear noted, recondition to your standard
Doors
Doors at Interior: Some door operation could be improved
Doors Correct as Needed
Doors at Interior
Check all doors. Properly correct interior doors to your standard and to meet your needs.
________________________________________________________________________________________________________________________________________________________________
Glazing/Glass
Insulated glass was present.
Not Identified Tempered
Exterior glass at stairs observed subject to fall impact. The window glass did not appear to be tempered for safety, and should be considered for an upgrade. Tempered safety glazing minimizes possible injury to persons who may fall into the glass. Evaluate your risk exposure, properly correcting as needed.
Stairs/Railings Interior
Diagram: Correction Needed Railing & Stairs
Handrail: Wobbled No Mid Post, Wrong Height, Not Full Run
Railings: Risers ≥4", Return Not Present
Stairs: Steep 7 3/4+", Uneven, Tread <11", Stringer Spaced Far
Stairs Repair/Replace
Evaluate your risk exposure. Consider proper repair or replacement of steps and railings where needed now for safety and function.
GARAGE
GARAGE
GARAGE TYPE: Attached
Garage Location: Upper Garage
Garage Floor Location: Below Ground
Garage Restrictions: Stored Items
Stored items were present at garage when it was inspected limiting view and access to some areas of garage.
Garage Separation from Living Space: Drywall Present Ceiling/Wall
Drywall was observed installed on ceiling framing and the wall framing that separated the garage and living space.
Should a fire occur at an attached garage area, properly installed drywall on framing, where needed, can offer some assistance to slow the spread of fire and smoke from the garage area to living areas. Properly maintain this area as needed.
________________________________________________________________________________________________________________________________________________________________
GARAGE OVERHEAD DOOR: Two Installed
Overhead Door Material: Metal
Overhead Door Insulation: Partially Insulated
Overhead Door Operation: Tested Using Operator
________________________________________________________________________________________________________________________________________________________________
GARAGE OVERHEAD DOOR OPERATOR: Testing Garage Overhead Door Operators
Testing Electric Operators for Garage Overhead Doors
Garage overhead door operators require periodic maintenance to maintain safe operation. Electric overhead door operators are checked for function and safety when inspected.
Modern garage overhead door operators have two safety reversal means; contact reversal and non-contact reversal.
Contact reversal is when the garage overhead door hits an obstruction that should cause the operator to reverse for safety.
Non-contact reversal is when the electronic eyes detect an obstruction, without the garage overhead door hitting an object, that should cause the operator to reverse for safety.
The contact reversal of the garage door operator is tested using a 1.5 inch obstruction on the floor at the center point of the overhead door. If the contact reversal requires correction, this is typically accomplished by a simple adjustment on the operator but other corrections could also be necessary. See overhead door operator owners manual for additional details.
If the electronic eyes area installed properly, the non-contact reversal is tested by obstructing the path between the electronic eyes while the operator is closing the garage overhead door. The installation height of the electronic eyes varies slightly by manufacture. Most manufacturers typically advise installing the electronic eyes no more than six inches above the floor at the overhead door track. If the electronic eyes are out of alignment, the operator will not close the garage overhead door without pushing and holding the wired, wall mounted, push-button until the garage overhead door is fully closed. If the electronic eyes require adjustment, this is typically accomplished by remounting or correcting the aim of the electronic eyes but other corrections could also be needed. See overhead door operator owners manual for additional details.
Overhead Door Operator: Two Installed
Electronic Eyes / Non Contact Reversal: Eyes Functional
Upper Garage Both Overhead Door Operators
Overhead door operator, non contact reversal means, electronic eyes, tested functional.
Contact Reversal: Contact Failed
Upper Garage Both Overhead Door Operators
Overhead door operator contact reversal means failed pinning an obstruction. It is not uncommon for the garage overhead door operators to require minor adjustment periodically. See overhead door operator owners manual for how to adjust the operator force for correct function. Correct as needed now for improved safety.
GARAGE cont
GARAGE AREA
GARAGE TYPE: Attached
Garage Location: Lower Garage
Garage Floor Location: Below Ground
A space below ground level is referred to as a basement-type area. The garage floor was partly or entirely below exterior soil level and is, therefore, a basement-type garage. Maintain this area as you would any other basement-type area.
Garage Restrictions: Excess Stored Items
Excess stored items were present at garage when it was inspected limiting view and access to most areas of garage. Obtain reasonable access and reinspect area prior to settlement. Make corrections if needed.
Garage Separation from Living Space: Drywall Missing Ceiling/Wall
Ceiling and wall area separating the garage area from the living space area was exposed or not completely covered with drywall. Should a fire occur at an attached garage area, properly installed drywall on framing, where needed, can offer some assistance to slow the spread of fire and smoke from the garage area to living areas. Consider this area for an appropriate improvement or upgrade.
Garage Separation from Living Space: Fire Sprinklers
Garage Floor: Saw Cut
________________________________________________________________________________________________________________________________________________________________
GARAGE OVERHEAD DOOR: One Installed
Overhead Door Material: Metal
Overhead Door Insulation: Partially Insulated
Overhead Door Operation: Improve Operation
Lower Garage Overhead Door
Inspector was able raise and lower the overhead door, but the overhead door should operate better. The garage overhead door should be properly serviced correcting as needed for proper function and safety.
Overhead Door Operator: None
KITCHEN
Inspection Process
Kitchen Inspection Process
Kitchen Inspection Process
Kitchen inspection was of the readily accessible and visible portions of the kitchen. The kitchen inspection includes the countertops and a representative number of cabinets. Kitchen faucets, when functional, are run for longer than one minute checking for observable leaks and hot/cold orientation.
The following built-in kitchen appliances, where installed, were inspected and on/off operated testing the main function of each appliance using the normal operating controls:
- Cooktop / Oven / Range (cook surface with integral oven)
- Microwave
- Garbage Disposal
- Trash Compactor
Installed dishwashers are run through a normal cycle. Obvious functional issues and leaks observed around the dishwasher are reported, if present.
Ventilation equipment, such as range hoods, are inspected, on/off operated and are reported as ductless, ducted or recirculating. It is beyond the scope of this inspection to determine the effectiveness of the kitchen exhaust fan, such as to verify air flow quantity or discharge location.
Appliance inspection does not cover clocks, timers, self cleaning function, calibration, automatic functions or optional equipment on appliances.
Refrigerators are considered personal property and are not evaluated. Refrigerator presence or absence is noted. Faucets for refrigerator ice makers are not tested whether the refrigerator is present or not as there is no basin to catch the water from the ice maker faucet.
Equipment that appears to be shut down, inoperable or intentionally taken out of service is noted but will not be operated by the inspector. Shut down equipment may be unplugged, breaker off, water off, gas off or otherwise taken out of service.
Installation conditions and functional issues for this area requiring correction should be performed by a competent qualified contractor.
Kitchen
Kitchen Area: Main Level
Kitchen
Countertop: Granite
- Serviceable, fulfilling its function
Cabinets: Wood
- Some wear noted, recondition to your standard
Floor Covering: Wood
- Some wear noted, recondition to your standard
Sink: Double Bowl Stainless Steel
- No leaks were observed at the faucet, the visible supply lines, or the waste drain beneath the sink.
- Signs of past leakage were observed. Maintain the area to meet your needs.
- Personal property beneath the sink restricted the view of the area.
Disposal: Present and appeared functional
Dishwasher: Present and ran through a normal cycle without incident
Range: Range (Electric Top/Oven)
Present and On/Off Tested functional
Microwave: Present and On/Off Tested functional
Kitchen Exhaust: Ductless in microwave appeared functional.
Refrigerator: Present but not evaluated
Trash Compactor: Not Present
BATHROOM
Inspection Process
Testing Limitations
Bathroom Inspection Process
The following opinion was based on an inspection of the readily accessible and visible portions of bathroom areas.
Hand washing faucets, when functional, are run for approximately one minute checking for observable leaks at the faucet and beneath the sink as well as checking Hot/Cold orientation.
Bathing area faucets, when functional, are run for approximately five minutes checking for observable leaks and Hot/Cold orientation.
Toilets, when functional, are flushed twice. Inspector checks for leaks around toilet, checks that toilet fills and shuts off, and checks to see if toilet appears securely mounted.
Effectiveness and discharge locations for mechanical bathroom exhaust vents are not confirmed during inspection.
Installation conditions and functional issues for this area requiring correction should be performed by a competent, qualified contractor.
Bathroom
Full Bathroom
Location Full Bathroom: Upstairs at Hall
Bathing Area: Combination tub and shower
- No leaks were observed around the faucet, and the water containment area appeared serviceable.
Hand Washing: Vanity with basin
- No leaks were observed at the faucet, the visible supply lines, or the waste drain beneath the sink.
Toilet: Water tank type
- No leaks were observed around the toilet, and it appeared secured in place.
Ventilation:
- Fan on/off tested operative. Consider exhausting to exterior if needed.
Floor Covering: Tile
- Some wear noted, recondition to your standard
Bathroom
Full Bathroom
Location Full Bathroom: Main Level attached to a bedroom
Bathing Area: Hydro massage tub and separate shower
- No leaks were observed around the faucet, and the water containment area appeared serviceable.
- Properly maintain tile work to meet your needs.
- The hydro massage tub was filled and operated, appearing functional.
Hand Washing: Two basins in vanity
- No leaks were observed at the faucet, the visible supply lines, or the waste drain beneath the sink.
- Signs of past leakage were observed. Maintain the area to meet your needs.
Toilet: Water tank type
- No leaks were observed around the toilet, and it appeared secured in place.
Ventilation:
- Fan on/off tested operative. Consider exhausting to exterior if needed.
- Multiple fans were present and appeared to be operative.
Floor Covering: Tile
- Wear was noted, properly recondition to meet your needs
Bathroom
Half Bathroom
Location 1/2 Bathroom: Main Level
Hand Washing: Pedestal type
- No leaks were observed at the faucet, the visible supply lines, or the waste drain beneath the sink.
Toilet: Water tank type
- No leaks were observed around the toilet, and it appeared secured in place.
Ventilation:
- Fan on/off tested operative. Consider exhausting to exterior if needed.
Floor Covering: Wood
- Some wear noted, recondition to your standard
Bathroom
Full Bathroom
Location Full Bathroom: Basement
Bathing Area: Shower
- The shower was run only briefly as no shower curtain/door was present.
Hand Washing: Pedestal type
- No leaks were observed at the faucet, the visible supply lines, or the waste drain beneath the sink.
Toilet: Water tank type
- No leaks were observed around the toilet, and it appeared secured in place.
Ventilation:
- Fan on/off tested operative. Consider exhausting to exterior if needed.
Floor Covering: Engineered Flooring
- Serviceable, fulfilling its function
Bathing Area: Shower Head (Leak at Shower Head)
Location Full Bathroom Basement
Shower Area
A leak was observed at the shower head piping. Properly correct as needed.
LAUNDRY
Laundry Connections
Laundry: Connections Available
Clothes washer and dryer connections were available.
Laundry appliances were not observed connected to the laundry connections during the inspection. Laundry faucets are not operated when the basin beneath the faucets is inadequate to contain the faucet flow without a hose being connected to the faucets. Verify your clothes dryer exhaust is functional, safe, and properly installed to meet the requirements of the clothes dryer manufacturer.
Laundry Sink
Sink/Faucet: No Leaks
PLUMBING
Supply Piping
Supply Piping: Mostly PEX with Some Copper
Water Flow at Supply Piping: Adequate
Adequate functional supply water flow was observed during inspection for water outlets operated.
Waste Piping
Waste Piping: Functional Flow Plastic
Material: Plastic
Functional waste water flow observed during inspection for water outlets operated.
Apparent Vent Piping
Plastic - No Adverse
Material: Plastic
No adverse conditions were observed, maintain to meet your needs.
Exterior Hose Faucets
Two
Performance: Functional Multiple
Exterior Hose Faucets
Exterior hose faucets were turned on and off briefly and appeared to function normally.
Water Heater
Water Heater
Discharge Piping: General Guidelines
Water Heater - Temperature and Pressure Relief Valve - Discharge Piping General Guidelines
Consult a knowledgeable, competent, qualified plumbing contractor for specific requirements in your area.
Valve Manufacturer WARNING: To avoid water damage and/or scalding due to valve operation, a properly installed discharge line must be connected to valve outlet and run to a safe place of disposal.
- Discharge line shall serve a single relief device and shall not connect to piping serving any other relief device or equipment.
- The discharge line shall be installed in a manner that does not cause personal injury or structural damage.
- The discharge line shall be installed to a termination point that is readily observable by the building occupants.
- The discharge line shall be installed to allow complete drainage of both the valve and the discharge line.
- No reducing coupling or other restriction shall be installed in the discharge line.
- The discharge line must pitch downward from the valve and terminate not more than 6 inches (152 mm) above and not less than two times the discharge pipe diameter above the floor or flood level rim of the waste receptor.
- A proper air gap should be present above the floor or flood level rim of the waste receptor where the discharge pipe drains. The discharge piping should not drain into an indirect waste receptor such as a leak pan beneath a water heater.
- The discharge line must terminate through plain (unthreaded) pipe.
- Discharge line material must conform to local plumbing code or A.S.M.E. requirements. PVC piping is not rated for hot water and shall not be used.
- Excessive length - more than 30 feet (9.14m), use of more than four elbows or bends in discharge piping, or reduction of discharge line size will cause a restriction and reduce the discharge capacity of the valve.
- No shut-off valve shall be installed between the relief valve and tank, or in the discharge line.
Water Heater
Water heater temperature and pressure relief valve had discharge extension piping that was not rated for hot water and this pipe should be properly replaced.
- PVC piping is not rated for use with hot water and should not be used at water heater for temperature and pressure relief valve discharge piping.
Refer to discharge piping general guidelines. Proper correction is needed for correct function and safety.
Equipment Observed
Plumbing Equipment Observed Present But Not Tested or Evaluated: ________________________________________________________________________________________________________________________________________________________________
Thermal Expansion: About Thermal Expansion
Regarding Plumbing System Thermal Expansion:
Thermal expansion occurs when a tanked water heater operates without any plumbing valves open for a period of time. If the property water meter has a check or backflow preventer valve installed it will prevent the expanding contained water from flowing backwards through the water meter. This expansion causes the water heater pressure relief valve to open briefly releasing a small amount of water if an expansion control device is not present or not working properly. If the pressure relief valve on the water heater opens and does not seal closed properly then active leaks and subsequent damage may occur.
Tank Present
A plumbing thermal expansion tank was observed near the water heater. Maintain this area as you would any other portion of the plumbing system correcting when needed.
________________________________________________________________________________________________________________________________________________________________
Pressure Reducer: About Pressure Reducing Valves
Regarding Plumbing System Pressure Reducing Valves:
The pressure reducer or pressure regulator in a plumbing system is designed to reduce the water pressure to a reasonable level in an effort to help prevent damage to the plumbing system. For most areas if the utility water pressure is greater than 80 PSI (pounds per square inch) a pressure reducer is needed. For some areas with extremely high utility pressure multiple pressure reducers may be needed installed in series. Pressure reducers are typically factory set for 50 PSI and property water pressure is expected to be between 30 PSI and 80 PSI. Inspector notes presence of pressure reducer when observed. Pressure readings for plumbing system are not part of the inspection performed.
Pressure Reducer Location: Basement Garage
________________________________________________________________________________________________________________________________________________________________
CENTRAL SYSTEM
Central Heat/Cool
Split System - Heat Pump
Central Heating/Cooling
Split, Forced Air Heat Pump System served: System served upstairs area
Brand Furnace: U.S. Alumacoil / Location: Equipment Closet upstairs
Size: 2.5 ton / Year of Manufacture: 2017 / Fuel: Electric Heat Pump
Heat pumps typically have a service life of 12-18 years when properly maintained
Filter Type: Disposable / Thermostat Type: Digital - Thermostat was located within area served.
Cooling Brand: Goodman / Location: Exterior
Year of Manufacture: 2017 / Fuel: Electric
Heat pumps typically have a service life of 12-18 years when properly maintained
Condensate disposal method: Gravity drain piping - service annually
________________________________________________________________________________________________________________________________________________________________
Cooling Function: Functional
________________________________________________________________________________________________________________________________________________________________
Heat Pump Single Fuel: Warm Day Backup Functional
Electric Heat Pump System - Backup heating was operated on a warm day.
For heating function, the electric single fuel heat pump system was operated only in the back up heating mode due to warmer outdoor ambient air temperature. Backup heating was briefly operated on heat pump. System engaged and was found to be functional.
Central Heat/Cool
Split System - Heat Pump
Central Heating/Cooling
Split, Forced Air Heat Pump System served: System served main level and basement area
Brand Furnace: Coleman Evcon / Location: Basement Garage at lower area
Size: 2.5 ton / Year of Manufacture: 2018 / Fuel: Electric Heat Pump
Heat pumps typically have a service life of 12-18 years when properly maintained
Filter Type: Disposable / Thermostat Type: Digital - Thermostat was located within area served.
Cooling Brand: Coleman Evcon / Location: Exterior
Year of Manufacture: 2018 / Fuel: Electric
Heat pumps typically have a service life of 12-18 years when properly maintained
Condensate disposal method: Condensate pump was present, service annually
________________________________________________________________________________________________________________________________________________________________
Cooling Function: Functional
________________________________________________________________________________________________________________________________________________________________
Heat Pump Single Fuel: Warm Day Backup Functional
Electric Heat Pump System - Backup heating was operated on a warm day.
For heating function, the electric single fuel heat pump system was operated only in the back up heating mode due to warmer outdoor ambient air temperature. Backup heating was briefly operated on heat pump. System engaged and was found to be functional.
Central Ductwork
Distribution Ductwork
Ductwork Information: About your central heating and cooling ductwork
Regarding calculating the load of a central system:
Several factors are considered when performing a load evaluation for central heating and cooling systems to determine the appropriate size system for the area served. Factors such as installed ductwork, insulation, ceiling height, basement area served (if present), shade, climate zone, as well as the size, number, and placement of windows, must be taken into account before sizing a system. The inspector does not calculate the load of a central heating and cooling system during the performed inspection. The inspector also does not confirm that the installed ductwork is appropriately sized to serve the installed central heating and cooling equipment.
Properly maintain the ductwork system to meet your comfort needs and ensure the system operates efficiently.
Ductwork: Single Unit Serving Multiple Floors
Ductwork System served main level and basement area
A single central heat/cool system was installed serving multiple floor levels. When one central system serves multiple floor levels, expect some temperature disparity between floor levels. Seasonal adjustment of vent diffusers may help. A heating contractor may also be hired to modify the system. Monitor your comfort level and correct as desired to meet your needs.
Gas
Gas Fuel Piping
Gas Service Appeared Off
The gas supply appeared to be off during the inspection. Installed accessible gas appliances were inspected but not observed in operation.
- Further evaluation of the gas system should be completed by a competent qualified contractor.
- Determine, if possible, the reason that the gas system was shut down or inoperative.
- Take steps to prevent recurrence.
- Properly put the gas system back in service correcting as needed for function and safety.
- Verify all appliances, piping and fixtures requiring gas are fully functional and safe correcting where needed.
Space Heating
Fireplace
Fireplace Use Nonessential
Regarding Fireplace Use:
Fireplace use was nonessential. The installed fireplace was not the sole heating system for the inspected property and does not have to function if you do not desire to use the fireplace area. Typically, deficient fireplaces are not listed in the summary of the report. Properly repair fireplace area for function and safety if use is desired.
Type: Prefabricated or Manufactured Fireplace
Unvented/Ventless/Vent Free/Room Vented
Regarding Room Vented Fireplaces, also known as Unvented, Ventless, or Vent Free Fireplaces, or Firebox Enclosures
Room-vented firebox enclosures do not have a flue that exhausts to an exterior area. Gas log set heaters installed inside this type of fireplace burn using the oxygen in the room. Gas log set heaters installed in room-vented fireplaces should be equipped with special devices that automatically shut off the gas to the heater should nearby oxygen reach unhealthy levels. Additionally, manufacturers often recommend homeowners leave a window open an inch or two while operating a gas log set heater to introduce fresh air into the room. For improved safety, the inspector recommends not sleeping in an area when a gas log set heater is in use and not using a gas log set heater as the primary heat source for the area served. Properly maintain any fireplace as needed for proper function and safety.
Gas Log Set Heater: Present, Not Operated, Gas Service was off to Home
ELECTRICAL
Electrical Inspection
Electrical System Inspection
What is an electrical system?
The electrical system consists of an electrical service, distribution equipment, and branch wiring. The electric metering equipment is usually at the electrical service. Distribution equipment typically consists of one or more installed breaker panels, with branch wiring extending to all equipment, receptacles, lighting outlets, and devices, such as light switches. The inspection report focuses on wiring operating between 100-250 Volts. While the system's Amperage and Voltage are recorded, it is not measured during the inspection. Most low-voltage wiring is excluded from the performed inspection. Low-voltage items, such as heating and cooling thermostats, are used to determine the function of such equipment.
There are now a wide variety of lighting bulbs or lamps that will fit into lighting fixtures. Some choices may not be appropriate for some lighting fixtures. It is beyond the scope of this inspection to verify that each lamp or bulb is suitable for the installed lighting fixture. The inspector recommends reviewing the bulb or lamp installations for each fixture, making corrections as needed for safety and proper function. Common errors include installing 100-watt bulbs in fixtures rated for 60-watt maximum bulbs, and using interior-rated bulbs in exterior or damp locations. Other types of errors also exist.
The following opinion was based on an inspection of the readily accessible and visible portions of the electrical system. The Inspector is responsible for checking a representative number of installed lighting fixtures, switches, and receptacles. A competent, licensed electrical contractor should correct electrical installation issues and address any functional issues that require correction. Most, if not all, electrical corrections should be considered a safety concern.
Electrical Service
MAIN PANEL
Main Electrical Panel
Service Entrance Conductors: Aluminum, Stranded
Index: Index
Wiring: Remark White 240V Breaker
Main Breaker Panel Garage at Upper Area
Corrections were needed at electrical distribution panel.
Refer to the full report for additional information and photos regarding obvious corrections recommended for this electrical panel. Make proper corrections as needed for safety and function now.
Branch Wiring
Material: Copper
Wiring Method: Non Metallic Sheathed Cable
AFCI
AFCI Residential
What is Arc Fault Circuit Interrupter (AFCI) Protection?
AFCI protection is designed to break the electrical circuit when it detects electric arcs that are a signature of loose connections in home wiring. Loose connections, which can develop over time, can sometimes become hot enough to ignite house fires.
Most, but not all, homes will have a need for additional AFCI protection based on varied municipal enforcement and the numerous changes for which areas require AFCI protection. Evaluate your risk exposure. Consider adding AFCI protection where needed for improved safety, particularly where construction was completed 2002 or later.
Modern Locations Where AFCI Protection is Known to Improve Safety:
Dwelling Units. All 120-volt, single-phase, 10-, 15-, and 20-ampere branch circuits supplying outlets or devices installed in the following locations:
Kitchens,
Family Rooms,
Dining Rooms,
Living Rooms,
Parlors, Libraries,
Dens,
Bedrooms,
Sunrooms,
Recreation Rooms,
Closets,
Hallways,
Laundry Areas,
or similar areas.
Testing AFCI Function
The inspector uses push button at AFCI breakers, where installed, to confirm AFCI protection trips. Once tripped, the inspector checks indexed electrical circuits to determine where AFCI protection is present or missing.
Obvious locations lacking AFCI protection are listed in the body of the report.
Obvious broken, non working and improperly wired AFCI receptacles or breakers are listed in the summary of the report. Evaluate your risk exposure.
AFCI Protected Areas: Bedroom Only
AFCI protection was observed installed for bedroom outlets only.
AFCI Modernize Add More
Consider modernizing electrical installation adding further AFCI protection for improved electrical and fire safety. If installation of additional AFCI protection is desired, consult a knowledgeable, competent, qualified electrical contractor for specific requirements in your area.
GFCI
GFCI Residential
What is Ground Fault Circuit Interrupter (GFCI) Protection?
GFCI protection is an electrical safety device that interrupts an electrical circuit when the current passing through a conductor is not equal and opposite in both directions, therefore indicating an improper flow of current such as leakage of current to ground or current flowing to another powered conductor. The device's purpose is to reduce the severity of injury caused by an electric shock.
Most, but not all, buildings will have a need for additional GFCI protection based on varied municipal enforcement and the numerous changes for which areas require this type of protection. The list below is based off the 2023 standard that may or may not have been adopted by the local municipality. Evaluate your risk exposure. Consider additional GFCI protection where needed for improved safety.
Modern Locations Where GFCI Protection is Known to Improve Safety in Dwelling Units.
(A) Dwelling Units
All 125-volt through 250-volt receptacles installed in the following locations and supplied by single phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit-interrupter protection for personnel:
(1) Bathrooms
(2) Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use.
(3) Outdoors
(4) Crawl spaces - at or below grade level
(4) Basements
(5) Kitchens
(6) Areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking
(7) Sinks - where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink
(8) Boathouses
(9) Bathtubs or shower stalls - where receptacles are installed within 1.8 m (6 ft) of the outside edge of the bathtub or shower stall
(10) Laundry areas
(12) Indoor damp and wet locations
Some exceptions apply, see current standard for a list of exceptions.
(B) Pertains to Other Than Dwelling Units
(C) Crawl Space Lighting Outlets. GFCI protection shall be provided for lighting outlets not exceeding 120 volts installed in crawl spaces.
(D) Specific Appliances. GFCI protection shall be provided for the branch circuit or outlet supplying the following appliances rated 150 volts or less to ground and 60 amperes or less, single- or 3-phase:
(1) Automotive vacuum machines
(2) Drinking water coolers and bottle fill stations
(3) High-pressure spray washing machines
(4) Tire inflation machines V
(5) Vending machines
(6) Sump pumps
(7) Dishwashers
(8) Electric ranges
(9) Wall-mounted ovens
(10) Counter-mounted cooking units
(11) Clothes dryers
(13) Microwave ovens
(E) Equipment Requiring Servicing. GFCI protection shall be provided for the receptacles required near Equipment Requiring Servicing.
(F) Outdoor Outlets. For dwellings, all outdoor outlets, including outlets installed in the following locations, and supplied-by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, shall be provided with GFCI protection:
(1) Garages that have floors located at or below grade level.
(2) Accessory buildings
(3) Boathouses
Note: Some exceptions apply, see current standard for a list of all exceptions.
Testing GFCI Function
The inspector uses an electrical tester at accessible 120V electrical receptacles that simulates a remote ground fault current to confirm which areas lack proper GFCI protection at tested 120V electrical receptacles.
Obvious locations lacking GFCI protection are listed in the body of the report.
Obvious broken, non working and improperly wired GFCI receptacles or breakers are listed in the summary of the report.
GFCI Some
Some GFCI protection was present. Multiple areas would benefit from adding further GFCI protection. Consider modernizing electrical installation adding this shock protection, where missing, for all electrical areas where GFCI protection is known to improve safety. If installation of additional GFCI protection is desired, consult a knowledgeable, competent, qualified electrical contractor for specific requirements in your area.
Receptacle Outlets
Cover Plates: Continuous Use
Damage: Physical Damage
Electrical Receptacle Outlet Damaged Basement
One or more damaged electrical receptacles were observed. Properly correct damaged electrical receptacles where needed for function and safety.
- The electrical receptacle in the basement hall was loose and damaged. Replace where needed.
Lighting/Ceiling Fans
Correct Lighting Where Needed
Lighting/fans - Make lighting/fans functional and safe where needed.
- Some lighting was inoperative when inspected.
- Some lighting was not fully functional when inspected.
- Some light fixtures were damaged.
Check all lighting/fans making functional and safe where needed.
Representative Photos Provided
Switches
Switch Location Informational Note
Regarding Lighting Switch Locations:
While exact placement of lighting switches is considered a design issue, installing lighting switches at appropriate locations is useful to improve safety. Generally, a light switch would be located within arms length of the entry point of a room so that the lighting for the room you are entering may be switched on from an area near the doorway. Installing a switch at an inconvenient location, such as on the hinge side of a door, would not be desirable. Where the stairway between floor levels has six risers or more, a wall switch would be located at each floor level and at each landing level that includes an entryway to control the lighting for the stairway. Evaluate your need in regard to lighting switch locations. Consider updating switch locations for improved safety if desired.
Switches Erroneous
Switches
The inspector was unable to determine the function of all switches present. Switches may operate flood lights, receptacles, or other items. They may also be an unused extra switch.
Smoke Alarms
Smoke Alarm Installation: Where Should Smoke Alarms be Installed?, Smoke Alarms Were Present
Depending on the age and location of the home, installation of smoke alarms are either recommended or required for improved safety.
Modern smoke alarm systems typically are hardwired to the electrical system and will have battery backup so that they will function when the power is off to the building. Modern smoke alarm systems typically have all smoke alarms interconnected so that when one alarm sounds then all smoke alarms will sound simultaneously. This is useful for heavy sleepers and in larger homes.
Modern smoke alarm systems typically have smoke alarms installed at the following locations:
- In the immediate vicinity outside sleeping areas
- Inside sleeping areas
- At least one per floor level including basements
- Near stairs
- In unfinished basements
- (some installations will require additional smoke alarms)
It is important to note that a single smoke alarm can satisfy multiple areas if carefully placed.
It is common to have a single smoke alarm near the top of the stairs and just outside multiple sleeping areas.
Properly maintain smoke alarm system as needed for life safety.
Regarding Testing Smoke Alarms:
Test smoke alarms weekly to ensure proper function for life safety. Replace batteries when needed. Properly replace smoke alarms when not functioning correctly and at least once every ten years. Smoke alarms should be at least the photoelectric type and dual sensor photoelectric and ionization smoke alarms are available, and preferred. Refer to installation and care instructions for proper locations and periodic maintenance.
The inspector does not test smoke alarms. For safety, the inspector only accesses smoke alarms from the installed flooring. To prevent damage, the inspector does not remove smoke alarms or open smoke alarm covers.
Smoke alarms were observed at inspected property for the applicable areas listed above. Properly maintain and test smoke alarms for improved safety.
Irregular Location
Irregular smoke alarm location observed. Typically smoke alarms are mounted on ceilings at least 4" from a wall or when mounted on walls they should be between 4-12" from ceiling. Additionally, smoke alarms should be three feet from duct supply vents and doorways to kitchens or bathrooms. Refer to installation instructions properly correcting where needed.
SMOKE ALARM BELOW CEILING
- Smoke alarm at wall was not 4-12" below upper ceiling at master bedroom.
STRUCTURE
Attic Access
Attic Access: Scuttle Hole
Attic Access: Not Floored
Attic area viewed from access point only due to lack of walk boards. Some areas of attic may not have been viewed.
Roof Framing
Ceiling Framing
Ceiling Framing: Wood
Framing Access: Finished and Insulated Restricted
Finished areas restricted view of structural components. Visibility was limited due to installed insulation in this area. Some areas were not observed by inspector.
Wall Framing
Framing Access: Finished Prevented
Finished areas prevented the view of structural components, so the inspector did not observe structural areas. Concealed areas were not part of the inspection performed.
Underfloor Access
Basement: Semifinished
Basement Semifinished
Some areas were finished. The components behind the finished areas were not observed. Concealed areas are not part of the inspection performed.
Underfloor Description
Attributes: Basement Semi Finished
Underfloor Area
Access:
- Basement walked
Construction Type:
- Basement - Semi Finished
Foundation:
- Poured in Place Concrete
Columns or Piers:
- Load Bearing Wall
Floor Structure:
- Floor Joists - Engineered I Joist
No Adverse Conditions Observed at Floor Framing
INSULATION
Above Ceiling Insulation
Recommended Insulation, Insulation Photo
Recommended attic insulation depth above living spaces for this area of the country is R-38 to R-60 to help lower utility costs. This recommendation comes from the US Department of Energy. Evaluate your comfort level and utility costs correcting insulation depth if needed.
Insulation Photo
Insulation Type: Blown In, Roll or Batt
Observed Insulation Approximate Depth: R - 38, R - 30
Wall Insulation
Insulation: Wall Insulation Not Observed, Undetermined
Underfloor Insulation
Insulation: Roll Batt Underfloor Insulation observed where installed at garage ceiling.
VENTILATION
Attic Ventilation
Attic Exhaust Vents: Ridge Roof Vent
Attic Intake Vents: Soffit Vents Where Installed
ROOF
Roof Covering
Method of Roof Inspection: Viewed from ground with binoculars
Roof Style: Multi Plane
Approximate Age of Roof Covering: 6-8 Years
Roofing Material: Composition Dimensional Shingle
Observation: Serviceable, Fulfilling Its Function
The roof covering overall was found generally serviceable within the parameters of its given service life. All roofing requires periodic maintenance. Properly maintain and correct roof covering as needed, when needed.
Roof Penetrations
Plumbing Vent Flashing
Plumbing Vent Flashing at Roof
Monitor this type of penetration as the flashing around the plumbing waste pipe that penetrates the roof requires periodic replacement. Budget replacement of plumbing vent flashing as the gaskets begin to deteriorate and split. This is needed each 8-10 years after a new plumbing vent flashing is installed.
Gutters and Downspouts
Gutter and Downspout Materials: Metal
Observation: Partial Gutters
Downspout: Near
Gutters: Maintain
Properly maintain rain gutters to meet your needs.
SIDING and TRIM
Siding
Irregularity: Close to Roof Covering
Siding/Trim should be 1-2" away from roofing shingles to facilitate shingle replacement and to prevent siding from wicking moisture from roofing causing damage to siding and adjacent areas. Monitor siding installation budgeting corrections as needed. Consider upgrading area either before painting or when replacing roofing.
Masonry Siding
Brick Veneer
What is Brick Veneer
Brick veneer siding serves as a non-structural outer layer of masonry. In contrast to solid brick constructions, which rely on multiple layers of brick for structural support, brick veneer systems depend on the underlying structure to support the masonry. The removal of the brick veneer would not compromise the building's structural integrity.
Brickwork: Serviceable
Brickwork
The exterior readily visible areas of the brickwork were inspected and appeared to be in overall serviceable condition, fulfilling its function. All siding requires maintenance. Properly maintain siding condition correcting when needed.
Siding - Cement Fiber
Siding Irregularities: Common Irregularities
Cement Fiber Siding/Trim -
Typical siding installation irregularities were observed. Monitor siding installation budgeting corrections when necessary. When corrections are performed, refer to the installation instructions and best installation practices, and correct as required.
Siding Irregularities: Too Close to Roofing, Too Close to Pavement, Blocking and Flashing
Cement Fiber Siding/Trim -
Siding/Trim should be 1-2" away from roofing shingles to facilitate shingle replacement and to prevent siding from wicking moisture from roofing causing damage to siding and adjacent areas. Monitor siding installation budgeting corrections as needed. Consider upgrading area either before painting or when replacing roofing.
Cement Fiber Siding/Trim -
The inspector noted that portions of the siding or trim were too close to pavement, making the siding or substrate subject to damage. Siding and untreated substrate should be a minimum of 1-2" above pavement. Properly provide separation at siding/trim and untreated substrate from pavement. If it is not cost effective to lower the pavement or raise the siding and substrate area then you should budget periodic replacement of affected areas.
Cement Fiber Siding/Trim -
The inspector noted that blocking and flashing details did not meet the Best Practices - Installation Guide for all areas. These areas should be considered for proper correction now. Closely monitor areas if not correcting blocking and flashing details now. Budget immediate correction should negative consequences occur due to a lack of proper blocking and flashing.
Siding: Corrections Needed
Exterior siding was ready for proper corrections when inspected.
Inspector Observations - Representative Photos Provided
- Deferred Maintenance Observed
- Failing Paint Observed
- Loose Siding Observed
- Temporary Repairs Observed
What you should do.
- Refurbish area before painting. A quality paint or stain job will include washing/cleaning all areas to be painted, repair/replacement of damaged siding and trim, seal all gaps, prime all unpainted areas and sufficient paint coverage to achieve desired color without bleed through.
- Properly replace or repair exterior siding and trim as needed. Properly correct any adjacent affected areas damaged by deferred maintenance. Affected adjacent areas that are concealed or not readily accessible are not part of the inspection performed.
Siding - Concrete Tile
What is Concrete Tile Siding?
Concrete Tile Siding, also known as Adhered Concrete Masonry Veneer or Manufactured Masonry Veneer, is a non structural, light weight concrete product that is not made of natural stone. Concrete tile siding resembles stonework because real stone are used to make castings that are filled with light weight concrete and are stained to appear similar to natural stone. Concrete tile siding is absorbent and requires a proper moisture management system be in place before applying the concrete tile to exterior areas. Since the moisture management system is beneath the concrete tile, after the tile are installed the moisture management system is no longer readily visible. The best time to inspect the moisture management system is during installation. Most adhered concrete tile installations should follow the Masonry Veneer Manufacturers Association Installation Guide and Detailing Options for Compliance with ASTM C1780. ACMV.
Irregular Monitor
Concrete Tile Siding
Common installation irregularities were observed. Monitor siding installation budgeting corrections when necessary. Refer to installation instructions and best installation practices, correcting where needed, when performing repairs. Maintain or upgrade this siding to meet your needs.
- Irregular transition was observed at dissimilar materials
- Siding observed too close to Soil and Pavement
Siding - Stucco
Siding - Vinyl
Vinyl Eaves with Metal Trim
Siding: Corrections Needed
Exterior siding/trim was ready for proper corrections when inspected.
Inspector Observations - Representative Photos Provided
- Deferred Maintenance Observed
- Vinyl Siding Was Ready to be Washed
What you should do.
- Properly replace or repair exterior siding and trim as needed. Properly correct any adjacent affected areas damaged by deferred maintenance. Affected adjacent areas that are concealed or not readily accessible are not part of the inspection performed.
- Siding was ready for routine maintenance such as washing and inspecting for damaged areas. Make proper corrections as needed.
DECK
Deck or Wooden Porch Areas Overall Condition Statement
Correct Deck and Fall Areas Now
Inspecting decks which are also known as wooden porches.
Decks and their attached steps are inspected for structural integrity, fall prevention and possible entrapment openings. Concealed areas such as deck footers are not included in the inspection. Most inspected decks will be ready for some correction or upgrade due to age, wear or improper construction. For any areas ready for upgrade, you should evaluate your risk exposure properly correcting as needed for improved structural integrity and improved safety.
Any deck needing correction should be further reviewed and corrections performed by a Competent Qualified Deck Contractor as the deck inspection performed in this report is not meant to discover every possible correction that a deck might need.
Each deck should be properly stained to prolong deck life. A solid deck stain is preferred as it will also protect the deck from sun light damage.
Two useful sources for deck information may be found at the following websites:
https://knoxcounty.org/codes/pdfs/construction_info/DeckInformation.pdf
Deck areas were observed ready for corrections now to improve the structure of the deck and to improve the safety aspects for the fall prevention measures installed at deck areas. Refer to the full report for additional information and photos regarding obvious corrections recommended now for any deck areas. A competent deck contractor should check all deck areas. Make deck areas functional, safe and structurally sound where needed.
Deck or Wooden Porch Location, Attributes and Restrictions
Deck or Wooden Porch Structure
Bolts: Not Present
Deck bolts were not observed. Decks should be properly bolted to the structure every 12", 16" or 24" depending on the span of the floor joists. Deck bolts should be ½” diameter lag bolts with washers. The installed bolts should be staggered top to bottom to prevent splitting of the ledger board. Proper correction should be completed to strengthen the deck connection to the structure.
Girder or Beam: Undersized
Joist Hangers: Missing At End Joist
Ledger Strip: Present, Not Installed Correctly
Joist framing at deck into the side of a ledger board or beam should be properly supported by approved joist hangers. Consider upgrade for outdated ledger strip installation for improved structural integrity and safety at deck by replacing any ledger strip with properly installed joist hangers.
LOTS and GROUNDS
Driveway
Walkway
Stairs and Railings at Exterior
Stairs at Front
________________________________________________________________________________________________________________________________________________________________
Vegetation
Vegetation Maintenance
Properly maintain vegetation to meet your needs. Vegetation should not touch building exterior or overhang roof. Vegetation should not interfere with access or servicing of electrical, gas or heating/cooling equipment.
Retaining Wall
End of Report