Electrical Only Summary
Electrical Items Only Summary
This was created to contain all of the electrical summary items that are in the full inspection report summary in one location for easy reference.
Electrical Only Summary
Due Diligence Items
- EDF-2 Electrical Distribution and Fixtures - Lighting, Switches and Receptacles:
I was unable to determine what devices were controlled by switches at the areas around the house. They may connect to future ceiling fans. Tracing the devices controlled by all switches exceeds the scope of the general home inspection. Recommend evaluation as needed.
Repairs
- EDF-1 Electrical Distribution and Fixtures - Branch Wiring Circuits:
A 240-Volt receptacle for EV charging was present in the Garage. In California, for new installations, a GFCI (Ground Fault Circuit Interrupter) breaker is required for 240-Volt outlets, like those used for Level 2 EV charging, in Garages, according to the NEC 2020 Section 625. Click here for link
625.54 Ground-Fault Circuit-Interrupter Protection for Personnel. All single-phase receptacles installed for the connection of electric vehicle charging that are rated 150 volts to ground or less, and 50 amperes or less shall have ground-fault circuit-interrupter protection for personnel. Recommend evaluation and repairs as needed.