Residential Pre-Sale Inspection Report
How to Read This Report
See the video link above. For the best experience, read this report online in its HTML format on a desktop computer as mobile can be tougher to digest this much information. This will allow you to easily expand sections, click blue links for additional information, and view embedded videos that provide important context beyond text and photos. Share the report by copying the web link from your browser, or print/save as a PDF using the buttons at the top, though printed copies greatly limit information. You can also create a custom Request List to generate a PDF of selected items to avoid sharing the entire report if needed.
This report is organized by chapters and sections, with general information in black text and any deficiencies or observations highlighted in colored boxes. Sections without observations were inspected and found to be in satisfactory/serviceable condition at the time of inspection.
Purpose and Scope
Purchasing a Property Involves Risk
Buying a property involves risk and these inspections aim to reduce those risks by providing a professional opinion on its overall condition. However, it's crucial to understand the limitations of these inspections.
Limitations
Home inspections are not warranties, guarantees, or insurance policies. They are limited visual inspections and cannot eliminate all risks inherent in property purchases. Inspections are non-destructive, meaning they involve visually examining accessible areas without dismantling or damaging the structure. Concealed areas and systems that cannot be tested without risk of damage are not covered.
This is Not for Code Compliance
This inspection did not assess code compliance. Building codes constantly evolve, and all buildings fall out of code compliance shortly after they are built, as the codes continually change. There are generally no requirements to bring older homes into compliance unless renovations are being done and permits are needed for the work.
This is Just Our Opinion
Construction techniques and standards vary. There is no one way to build a house or install a system in a house. The observations in this report are opinions of the professional inspector. Other inspectors and contractors are likely to have some differing opinions. You are welcome and encouraged to seek opinions from other professionals.
Scope
While this inspection adheres to ASHI standards of practice (which can be found by Clicking Here) and covers major systems such as the exterior, roof, structure, heating/cooling, etc., it may not include auxiliary systems. This inspection and report are not intended to be technically exhaustive due to cost and time constraints. Such inspections are available but they are generally cost-prohibitive for most people and would involve multiple specialists and engineers. Our goal is to help you understand the property's overall condition, ensure your expectations are realistic, and help you make informed decisions moving forward.
Observation Labels
All narrative observations are colored, numbered and labeled to help you find, refer to, and understand the severity of the observation. Observations used in this report are:
- Repair:Service, maintenance, repair, or replacement is recommended for these items. These are less severe in nature than Major Concerns, but should be dealt with sooner rather than later.
- Due Diligence:Items that may require specialist evaluation to determine repair severity or urgency, or may warrant additional inquiry to clarify the condition such as a plumbing fixture that was not tested due to the water supply being off.
- Minor Repair:Service, maintenance, repair, or replacement is suggested for these items. These are repairs that are minor in terms of difficulty and cost for the average person.
- Monitor:Items that should be periodically inspected to see if correction may be needed in the future.
- Efficiency Item:Observations that would make the home more energy efficient and to bring the home up to modern standards. This category typically includes windows and insulation.
- Limitation:Conditions present limited the scope of this visual inspection
Summary
Repairs
- E-1 Exterior - Exterior Doors:
Exterior Door Repairs Recommended
Repairs are recommended to the exterior doors. A qualified contractor should repair exterior doors as needed.
Observations noted include:
- Rear exterior door was rubbing on the frame and should be adjusted for durability
- E-2 Exterior - Wall Vent/Exhaust Terminations:
Exterior Vent Terminal Repairs Needed
One or more exterior exhaust vent terminals were damaged, missing, incomplete, or otherwise in need of repair. Exhaust terminals should be properly configured for their intended use and generally include a suitable hood, louvers, and/or backdraft damper to help limit weather, pests, and exterior air from entering the duct. Screens should not be installed on clothes-dryer exhaust terminals because lint can accumulate on the screen and restrict airflow.
Observations noted include:
- Bath fan vent terminals were missing at the North side
- Southside vent terminal was missing
Recommendation: Have a qualified professional repair or replace the affected vent terminal(s) as appropriate for the type of exhaust system.
- RCG-4 Roof Chimney & Gutters - Roof Covering(s):
Metal-to-Shingle Roof Transition Improperly Sealed
The transition where the metal roof ridge cap meets the shingle roof had a large amount of sealant applied, and closure material was not present beneath the ridge cap. Reliance on exposed sealant at this transition may not provide durable, long-term protection against water entry as the sealant ages and moves with the roofing materials.
Recommendation: Have a qualified roofing contractor experienced with metal roofing evaluate this transition and make repairs as needed to provide a durable, weather-resistant connection.
- MV-1 Mechanical Ventilation - Mechanical Ventilation Systems:
Continuous Running Crawl Space Exhaust Ventilation System Noted
A continuously operating exhaust fan was observed and operating correctly in the crawl space. This type of system is commonly used in newer or tighter homes to provide ongoing ventilation by creating slight negative pressure in the building and exhausting air from the crawl space. In this installation, openings between the living space and crawl space allow some indoor air to be drawn toward the crawl space and exhausted outdoors. This is an intentional ventilation design, but performance depends on proper design, air pathways, and fan sizing. The fan should be monitored periodically to ensure it remains operational, as changes in operation or failure of the system may affect indoor moisture conditions, air exchange rates, and radon levels within the home. If the system is modified, disabled, or stops operating, a new radon test is recommended.
- Louvers on register for the intake for the whole house ventilation fan in the crawl space would not open. Suggest replacement or repairs of this register so that it will open and facilitate proper ventilation
- BP-4 Bathroom - Primary - Bathtub / Shower:
Tile Surround - Maintenance Recommended
Recommended necessary maintenance and repairs to protect the tile shower surrounds. The tile and grout in shower surrounds should be water tight to prevent damage. This is important regular maintenance to ensure reliable service life. All loose and failing caulking and grout should be repaired. For inside corners, sanded caulking is recommended. This caulking can be purchased to match the tile grout and will expand and contract and resist cracking. Areas should be thoroughly cleaned before applying caulking or it will not adhere. Please note that tile is difficult to inspect visually. The reliability of a tile installation depends on what the tile is mounted on and what it is mounted with but unfortunately none of this is visible after installation.
- RMS-1 Radon Mitigation System - System Components:
Possible Unlabeled Passive Radon Mitigation System Noted?
A PVC vent pipe was observed that did not appear to be connected to any active plumbing venting. The pipe may serve as a passive radon vent system, which is sometimes installed in homes to allow soil gases to escape naturally through the roof. However, the pipe was unlabeled and its purpose was not confirmed.
Recommendation: The function of this pipe should be verified by the builder or a qualified contractor. If confirmed to be part of a passive radon mitigation system, proper labeling and inspection of the vent stack are advised to ensure it complies with current radon mitigation standards and is functioning as intended.
- The ventilation pipe should be capped or installed below the vapor barrier to allow the house's ventilation fan to function properly
- CS-4 Crawl Space - Moisture Control:
Mold-Like Substances Noted On Floor Framing in Crawl Space
Mold like substances/stains were noted on some of the wood framing below the house. This was likely from the time of construction. It is common for framing lumber to have stains from construction or even for this to form during construction from weather at that time. As long as the wood remains dry, risks to air quality would seem to be low indoors but mold air samples are advisable in living areas. This should be reviewed by a mold remediation contractor and cleaned as advised.
Due Diligence Items
- G1-5 Grounds - Irrigation:
Irrigation System Present
An irrigation system was observed. We apologize, but these are out of the scope of this inspection. Recommend inquiring with the seller/builder about the condition and operation, and having a qualified irrigation professional inspect it if a detailed report is desired. PLEASE REMEMBER TO WINTERIZE THE SYSTEM EVERY FALL TO PREVENT COSTLY REPAIRS.
- AP-1 Additional Plumbing - Fire Suppression:
Fire Suppression System Noted
An interior fire sprinkler system was noted in this building. Fire suppression systems are beyond the scope of this inspection. Inquire with the builder for any additional information; are there any required or recommended maintenance schedules?
- SS1-3 Sewer Scope - Scope Findings:
Functional Sewer Line with Concerns
The sewer line was functional and flowing at the time of the inspection; however, conditions were observed that may affect long-term performance or require maintenance or repair. Future service or repairs should be anticipated depending on the nature and progression of the noted conditions. The entire sewer scope video should be reviewed, as it may contain additional observations and context not fully captured in this written report.
Specific observations noted include:
Bellies (Low Spots)
- Moderate sag(s) noted: A sag is considered moderate if it is 25 percent to 50 percent of the pipe diameter. Moderate sags can be ok if they don't collect debris, but other times may require repair if blockages become a problem. Please note, that when the camera goes underwater, it makes visual inspection of the pipe at these areas difficult or impossible.
Recommendation: Have a qualified sewer contractor evaluate the observed conditions and perform maintenance or repairs as recommended. It can be sometimes be helpful to them to share this report with them.
Minor Repairs
- EDF-5 Electric Distribution & Fixtures - Smoke and Carbon Monoxide Alarm Systems:
Smoke Alarm Repairs are Needed
Repairs or updates are needed for the smoke alarms. Modern standards require them inside each bedroom and on every level of the home, including the basement. On levels without bedrooms, install alarms in the living room (or den or family room) or near the stairway to the upper level, or in both locations. They should be on the ceiling at least 4 inches from the wall but may be on wall, no lower than 12 inches from the ceiling. Smoke alarms should be replaced every 10 years per the manufacturers instructions.
Specific observations noted include:
- Battery tabs or dust covers were not removed from the new alarms.
Recommendation: Have a qualified person repair the smoke alarms so they conform to modern standards for safety.
- HCF-9 Heating Cooling & Fireplaces/Stoves - Air Filter(s):
Air Filter - Incorrect Size
The air filter for the forced air furnace was not correctly sized and was allowing air to bypass the filter. Install the proper sized filter or consult with a qualified HVAC contractor as needed to install a properly fitting filter.
- The correct filter is likely four or five inches thick
- HCF-11 Heating Cooling & Fireplaces/Stoves - Heat and Cooling Distribution System(s):
Repair the Floor Register
Floor register in the primary bedroom closet would not sit flush on the floor. Adjustments are needed here.
- I-1 Interior - Doors:
Door Repairs Recommended
Interior door repairs are recommended. A qualified person should further evaluate and repair or adjust interior doors as needed for reliable performance.
Examples of observations noted include:
- Door stop for the hallway closet door looks like it had been kicked and ripped out of the wall. This should be repaired
- BH-1 Bathroom - Hallway - General:
Re-Caulk Tub/Shower Floor Juncture
The caulking between the bathtub and the floor was observed to be deteriorated or incomplete and should be repaired or replaced to help prevent water from damaging the floor structure below. The urgency of this repair depends on how frequently the bathroom is used and how much water is splashed out during normal use.
Items for Monitoring
- G1-2 Grounds - Grading and Drainage:
Important Catch Basins Noted
Important catch basins were noted around the property. These are designed to capture surface runoff and divert water around the building. Be sure to keep these drains clear and below grade, especially before large rain storms. Suggest monitoring them during heavy rains to ensure they are not backing up and performing as intended.
Efficiency Items
- WH-5 Water Heater - Unit Components:
No Timer Found For Hot Water Circulation Pump
The water heating system has a circulation pump. This appeared to be operating at the time of inspection. For improved efficiency these are often put on timers so the pump can be timed to go off at night and in the middle of the day. I did not see a timer set up for this pump.
Limitations
- A-2 Attic - Access & Type:
Partially Walked/Crawled
Only partially walked/crawled the attic due to deep insulation. Entering attics that are heavily insulated can cause damage to the insulation, wiring, and attic framing and cannot be safely inspected due to limited visibility of the framing members upon which the inspector must walk. In such cases, the attic is only partially walked/crawled, thereby partially limiting the review of the attic area. Inspectors will not crawl the attic area when they believe it is a danger to them or that they might damage the attic insulation, wiring, or framing. This is a limited review of the attic area. Recommend consulting owners for any additional information.
- CS-3 Crawl Space - Foundation/Floor Insulation:
Stem Wall Was Covered with Insulation Limiting the View
The stem-wall of the crawlspace was covered with insulation. This does make detection of latent defects very difficult or impossible to find with out removal of the insulation. This is considered a limited review of this area as inspectors do not remove or damage insulation during general building inspections.
✅Complete Report
Grounds
Elevation Photos
Grading and Drainage
Driveways/Walkways/Flatwork
Fencing
Trees and Vegetation
Irrigation
Exterior Stairs and Guardrails
Retaining Wall(s)
Electric Service
Service Entrance
Main Electrical Panel
Electrical Grounding System
Electrical Bonding System
Appliance Disconnects
Electric Distribution & Fixtures
Branch Wiring
Receptacles & GFCI's
Lighting
Ceiling Fans
Smoke and Carbon Monoxide Alarm Systems
Low Voltage Wiring
Plumbing
Water Supply
Distribution Piping
Drain Waste & Vent
Floor Drains, Sump & Ejector Pumps
Exterior Hose Bibs
Heating Cooling & Fireplaces/Stoves
Heating System
Air Conditioning / Heat Pump
Exhaust Vents/Flues
Air Filter(s)
Heat and Cooling Distribution System(s)
General Information
Building Characteristics, Conditions and Limitations
Type of Inspection: General Home Inspection
Primary Building Type: Single Family (Attached Garage, 1 Story)
Building Foundation Type(s): Crawlspace (Traditional Stem Wall)
Additional Buildings Inspected: None
Approximate Square Footage: 1507
Approximate Year of Original Construction: 2026
Newer Building - Preserve Construction Records
As this was a newer construction building, the building plans, permits, drainage plans, construction records, a list of sub-contractors and warranty information should be available. Recommend trying to obtain and keep this information for your records and for future re-sale.
Additional Services Performed with Inspection: Radon Test
Occupancy: Unoccupied but staged with furniture
Building was vacant / unoccupied at the time of inspection. Vacant and unoccupied buildings present unique challenges, especially the piping and wiring systems which have not be subject to regular use prior to the inspection. While these systems can be tested, this one-time test is different than regular use and it is difficult to know how these systems will respond to regular use after the inspection. For example, septic systems may initially function and then fail under regular daily use. Plumbing traps may operate with no signs of leaks and then let go when being actively used for a few days. Shower pans may only leak when someone is standing in the shower and taking a shower. Seals for plumbing fixtures can dry up and leak when not is use. Sewer lines with roots may allow water flow, but then fail when waste and tissue are flushed; it can take a few days for that to backup. Please understand we tried our best to look for clues of past or existing problems to paint a realistic picture of the reliability of these systems during this inspection.
Animals Present: No
Access to the Property Was Granted By: Door Was Left Unlocked (By Buyers Agent)
Attending the Inspection: Client(s)
Approximate temperature during the inspection: 70F to 90F
Weather during the inspection: Clear, Dry
Ground/Soil surface conditions: Dry
Rain or Snow in Last 3 Days: No
The Main Entrance Faces: East
Approximate Start and End Times: 8:00am, 11:00am
Thermal Imaging Was Used During This Inspection
During this inspection, a thermal imaging camera was used to check walls, ceilings, electrical components and appliances for thermal anomalies. Thermal imaging cameras use the infrared light spectrum to build a picture based on temperature differentials. Experienced thermographers look for clues in these thermal images that could lead us to "see" otherwise-concealed moisture control problems, overheating electrical components and inadequate thermal barriers or air leaks. We can also use them for appliance verification. In older structures, incomplete air and thermal barriers are so common we will only report on items that look significantly deficient and seem worthy of correction.
This service is included with our inspection; it is limited and is not a complete thermal mapping of the building. The use of an infrared camera is well beyond the minimum standards of practice of this inspection. We offer this service because we know it is valuable and helps us help our clients by improving our inspection services.
Please note that this tool has limitations when done in conjunction with a property inspection. Environmental conditions at the time of inspection present limitations to the information that can be gathered during the course of a property inspection. For example, occupant behavior, the time of day, time of year, and weather conditions can all impact the usefulness of the data that can be gathered.
Relevant thermal images are included in this report and most are just for general documentation purposes. If any issues are noted within them, they will be clearly identified as such.
Grounds
Grading and Drainage
Site Drainage: Moderate Slope - OK, Catch Basins (Keep Clear & Monitor)
Building Clearance to Grade: Standard
Downspouts: Above grade
Important Catch Basins Noted
Important catch basins were noted around the property. These are designed to capture surface runoff and divert water around the building. Be sure to keep these drains clear and below grade, especially before large rain storms. Suggest monitoring them during heavy rains to ensure they are not backing up and performing as intended.
Driveways/Walkways/Flatwork
Driveway Material(s): Concrete
Walkway Material(s): Concrete
Patio Material(s): Concrete
Fencing
Present - No significant Issues
Trees and Vegetation
Trees & Vegetation: OK - No Issues Observed
Irrigation
Irrigation System: Present - Not Inspected (Buyer)
Backflow Prevention Device Present: Yes
This house has a backflow prevention device installed to protect your domestic water supply system from cross-connection with the irrigation system. An annual inspection of backflow devices is recommended as these perform a surprisingly critical safety task: keeping your drinking water and possibly even your neighbor's drinking water safe from contamination. This article has more information about recommended scheduled inspections for backflow prevention devices.
Irrigation System Present
An irrigation system was observed. We apologize, but these are out of the scope of this inspection. Recommend inquiring with the seller/builder about the condition and operation, and having a qualified irrigation professional inspect it if a detailed report is desired. PLEASE REMEMBER TO WINTERIZE THE SYSTEM EVERY FALL TO PREVENT COSTLY REPAIRS.
Exterior Stairs and Guardrails
Standard - OK
Retaining Wall(s)
Material(s): Masonry Block
Condition: Inspected - OK
Exterior
Siding and Trim
Trim Material: Engineered Wood
Siding Material: Stucco
Exterior Doors
Style(s): Glass panel doors
Exterior Door Repairs Recommended
Repairs are recommended to the exterior doors. A qualified contractor should repair exterior doors as needed.
Observations noted include:
- Rear exterior door was rubbing on the frame and should be adjusted for durability
Window Frames
Frame Material(s): Vinyl
Wall Vent/Exhaust Terminations
Condition: Inspected - Repairs Recommended
Exterior Vent Terminal Repairs Needed
One or more exterior exhaust vent terminals were damaged, missing, incomplete, or otherwise in need of repair. Exhaust terminals should be properly configured for their intended use and generally include a suitable hood, louvers, and/or backdraft damper to help limit weather, pests, and exterior air from entering the duct. Screens should not be installed on clothes-dryer exhaust terminals because lint can accumulate on the screen and restrict airflow.
Observations noted include:
- Bath fan vent terminals were missing at the North side
- Southside vent terminal was missing
Recommendation: Have a qualified professional repair or replace the affected vent terminal(s) as appropriate for the type of exhaust system.
Roof Chimney & Gutters
Roof Covering(s)
Condition: Further Evaluation Recommended
Method of Inspection: Walked on roof
Style(s): Hip, Gable
Valleys: Present and Visually Standard
Covering Material(s): Architectural Composition Shingle
Shingle Impact Rating Cannot Be Determined By Visual Inspection
The installed asphalt shingles were observed to be architectural in style, but it was not possible to determine if they are UL 2218 impact-rated products. Impact-resistant shingles cannot be identified by visual inspection alone because the UL rating is only printed on the original packaging or listed in manufacturer documentation. Insurance companies often request this information for discounts or underwriting, so it is advised that the seller or roofing contractor provide written confirmation of the shingle manufacturer, model, and impact rating if this information is required.
Overlayed Roof Covering: No
Shingle Fastening Accessible For Inspection : No
Please note that when inspecting composition roof installations, we attempt and look under shingles to see how they have been fastened. Proper fastening is critical for successful roof performance. Often the shingles are bonding so well, they cannot be lifted to inspect the fastening. In this case, the shingles could not be lifted to see the fastening pattern because they were bonded well and prying them apart may cause damage. While this limits the visual inspection, this is a good sign, as loose, un-bonded shingles can be easily damaged by wind and would be written up as a defect.
Metal-to-Shingle Roof Transition Improperly Sealed
The transition where the metal roof ridge cap meets the shingle roof had a large amount of sealant applied, and closure material was not present beneath the ridge cap. Reliance on exposed sealant at this transition may not provide durable, long-term protection against water entry as the sealant ages and moves with the roofing materials.
Recommendation: Have a qualified roofing contractor experienced with metal roofing evaluate this transition and make repairs as needed to provide a durable, weather-resistant connection.
Flashings and Penetrations
Condition: Present and Visually Standard
Gutters and Downspouts
Gutter and Downspout Material(s): Aluminum
Skylights
Type(s): None noted
Attic
Access & Type
Access Location(s): Garage
Inspection Methods: Partially Crawled/Walked/Viewed
Partially Walked/Crawled
Only partially walked/crawled the attic due to deep insulation. Entering attics that are heavily insulated can cause damage to the insulation, wiring, and attic framing and cannot be safely inspected due to limited visibility of the framing members upon which the inspector must walk. In such cases, the attic is only partially walked/crawled, thereby partially limiting the review of the attic area. Inspectors will not crawl the attic area when they believe it is a danger to them or that they might damage the attic insulation, wiring, or framing. This is a limited review of the attic area. Recommend consulting owners for any additional information.
Roof Framing and Sheathing
Framing Material: Trusses
Sheathing Material: OSB
Attic Insulation
Insulation Type: Blown in Cellulose
Attic Floor - Approximate R-Value: 49
Attic Cavity Ventilation
Condition: Inspected - OK
Attic Cavity Ventilation Method: Soffit vents, Hooded Roof vents
Unconditioned Attic Cavity Ventilation Note
Attic/roof cavity ventilation is a frequently misunderstood element of building construction and its primary job is moisture reduction. All unconditioned attic cavities are required to have ventilation. The general default standard is 1 to 150 of the attic area and ideally, this comes from at least 60% lower roof cavity ventilation and 40% upper, but this is an over-simplification of the subject. As a good guiding principle the most important elements for healthy attic spaces, which are traditionally insulated and ventilated are:
- Make sure the ceiling between the living space and the attic is airtight
- Ventilate consistently across the whole lower part of the roof cavity with low, intake soffit venting
- Upper roof cavity venting is less important and if over-installed can exacerbate air migration into the attic from the living space by creating negative pressure in the attic.
- Avoid power ventilators when possible which can depressurize the attic and exacerbate air migration from the house into the attic.
For more information, please check out this crash course on attic cavity ventilation by Clicking Here
Electric Service
Service Entrance
Main Electrical Panel
Main Electric Panel Location : Exterior - North Side
Service Entrance (SE) conductor Size: Not Visible
Main Panel Listed Max Amperage Capacity: 200 amps
Main Panel Breaker Total Amperage Rating: 200 amps
Main Panel Manufacturer: Siemens
Surge Protection: Present
Surge Protection Noted
This building has a surge protector installed to protect the electrical system which is a wonderful thing. Please note that the 2020 edition of the National Electrical Code requires type 1 or type 2 surge protection on new or renovated houses. This code change reflects the growing complexity of our electrical appliances and the risk of damage to these appliances from electrical surges.
Overcurrent Protection Devices: Breakers
Panel Full?: No - Breaker slots were available in this panel
AFCI Breakers: Present - Tested OK
All AFCI (Arc Fault Circuit Interrupters) breakers in this panel were tested/tripped and reset with no issues.
GFCI Breakers: Present - Tested OK
All GFCI Breakers (Ground Fault Circuit Interrupters) in this panel were tripped/tested and reset with no issues.
Electrical Grounding System
Present - Could Not Confirm
During a property inspection, every effort is made to inspect the visible components of the electrical system grounding. The grounding system is critical for safely discharging electrical surges, especially in the case of lightning strikes. However, there is no way in the context of a property inspection to verify the "effectiveness" of the grounding system as much of the system is not visible, and there are no practical tests one can perform in the way we can test a furnace or a plumbing fixture. However, if any defects were found, they will be documented in the observations of this report.
Electrical Bonding System
Could Not Confirm
Attempts were made to visually inspect the electrical system bonding. However, there is no way in the context of a property inspection to verify the "effectiveness" of system bonding. All metallic systems in the building are required to be "bonded" (connected) to the the building's electrical grounding system. Bonding creates a pathway to shunt static charges (that would otherwise build up on the system) to earth, and to provide a pathway to trip a breaker in the event that these bonded metallic components became energized. If any issues were observed, they will be documented as repair items in the observations below.
Appliance Disconnects
Air Conditioner
Electric Distribution & Fixtures
Branch Wiring
Wire Material: Copper
Wiring Method: Non-Metallic Sheathed Cable
Receptacles & GFCI's
Receptacle Inspection Method: Tested All Accessible
During inspection an effort was made to test and inspect all accessible electric receptacles and switches. In general, the scope of testing is directly related to access; where personal belonging and furniture obstruct access to receptacles and fixtures, fewer of them can be reasonably tested during inspection. All defects found during the inspection today will be listed in this report. Inspection/testing of the electrical system can be challenging. It should be anticipated that not all defects will be discovered and that some issues found may actually not be defects at all. Tools used to verify proper wiring and function can vary wildly in reliability/consistency. The kinds of tools that could be used to confidently analyze the system and its function cannot typically be done in the context of a standard Home Inspection. Issues identified, will be further discussed with recommendations in the electrical section below.
Receptacle Type(s): Three wire receptacles
Receptacles Condition: OK - No Issues Noted
GFCI Receptacle Testing Method: All Accessible GFCI's Tested
All readily accessible Ground Fault Circuit Interrupter (GFCI) receptacles (the ones with the “Test” and “Reset” buttons) were tested during the inspection. Standard-looking receptacles located in areas where modern standards recommend or require GFCI protection, including bathrooms, kitchens, garages, basements, laundry areas, exterior locations, crawl spaces, and near sinks, were also tested for GFCI protection using a plug-in ground fault tester. Any deficiencies observed with GFCI protection will be noted elsewhere in this report.
GFCI devices are important safety components designed to reduce the risk of severe electrical shock and electrocution by quickly shutting power off during a fault condition. Occasionally, a GFCI device may fail during testing and require replacement before power can be restored. Manufacturers generally recommend homeowners test GFCI devices monthly using the built-in “Test” and “Reset” buttons.
The video below provides additional information about GFCI protection and homeowner testing procedures.
GFCI Protection/Receptacles: Tested - OK
Lighting
Tested - OK
Ceiling Fans
None Noted
Smoke and Carbon Monoxide Alarm Systems
CO Alarm Locations: Outside All Sleeping Areas, On Main Floor
CO Alarms: Present in all Recommended Locations
Carbon Monoxide (CO) alarms were present in all recommended locations. For reference, they are required in homes with fuel burning appliances and attached garages and should be located within 15 feet of the bedroom entrance(s) and on each level. It is also recommend they be installed in rooms with fireplaces, wood stoves, gas heaters, or any fuel burning appliance for safety. Also, CO alarms should be replaced every 10 years per the manufacturers instructions.
Smoke Alarm Locations: In All Bedrooms, On Main Floor
Smoke Alarms: Repairs are Needed
Smoke Alarm Repairs are Needed
Repairs or updates are needed for the smoke alarms. Modern standards require them inside each bedroom and on every level of the home, including the basement. On levels without bedrooms, install alarms in the living room (or den or family room) or near the stairway to the upper level, or in both locations. They should be on the ceiling at least 4 inches from the wall but may be on wall, no lower than 12 inches from the ceiling. Smoke alarms should be replaced every 10 years per the manufacturers instructions.
Specific observations noted include:
- Battery tabs or dust covers were not removed from the new alarms.
Recommendation: Have a qualified person repair the smoke alarms so they conform to modern standards for safety.
Smoke and Carbon Monoxide Alarm Testing Procedure and Information:
During this inspection, we tested a representative sample of the smoke and carbon monoxide alarms by using the test button on the alarms. However, this is NOT an accurate test of the sensor, just a test to see if the unit is powered and makes a noise. For reliability, fire marshals and manufacturers recommended updating smoke alarms every 10 years and changing batteries bi-annually (if not powered by a 10yr battery). The latest data also indicates that we should be using photoelectric technology in our smoke alarms for improved fire detection and reducing problems with false alarms. It is surprisingly complex to accurately test a smoke/CO alarm system. A complete evaluation of of these is beyond the scope of this inspection per our ASHI Standards of practice. For more information about smoke alarm testing, maintenance, and replacement, see the National Fire Protection Association (NFPA) smoke alarm safety guidance.
Low Voltage Wiring
Doorbell: Present - OK
Alarm or Surveillance System: Not Present
Smart/Connected Devices: None Noted
Low Voltage Panel: None Noted
Plumbing
Water Supply
Water Pressure: 45 PSI
This shows the water pressure tested during the inspection. Generally, "normal water pressure" should be between 30-80 PSI, though pressures near or below 30 can result in poor functional flow to fixtures. Water pressures in excess of 80 PSI risk damaging supply piping components and should be controlled with a pressure-reducing valve.
Pressure Reducing Valve: Present
This building was properly equipped with a pressure-reducing valve to lower the utility water pressure (typically >100psi) to a safe level of 40-80 psi. These are usually adjustable if the need arises however, they are a maintenance item that can fail at any time which may cause high water pressure, or water flow issues.
Water Supply Source: Public water
Buried Water Supply Pipe Material: PEX
Main Water Shut-off Location: Noted In Media
The main water shut off for the building was located in the media below.
Automatic Water Shut Off Valve Present: No
Automatic Water Shut-Off Valve Not Present
An automatic water shut-off valve was not observed on the plumbing system. These devices can automatically stop the water supply when a leak or abnormal water usage pattern is detected, helping reduce the potential for water damage from plumbing failures. Some insurance providers may offer discounts or other incentives when approved leak detection and automatic shut-off systems are installed. If interested, contact a licensed plumber for more information.
Water Treatment/Conditioners: Not Present
Distribution Piping
Supply Pipe Materials: PEX, Copper
PEX Piping Note
This building uses PEX (cross-linked polyethylene) tubing for water supply piping. PEX is a widely used material in modern plumbing systems, and its crimp ring connections require precise installation methods to ensure long-term reliability. Like with most piping systems, the majority of these connections are concealed and not visible during a standard non-invasive inspection, making it impossible to fully evaluate their condition. If any leaks or installation defects are observed, this may indicate a broader concern and should prompt further evaluation by a licensed plumber familiar with PEX systems and connection methods.
Functional Flow: Average
Drain Waste & Vent
Discharge Type: Public Sewer - Scope Recommended - Buyer
Waste and Vent Pipe Materials: PVC
Location of Sewer Cleanout: See Sewer Scope Chapter
Floor Drains, Sump & Ejector Pumps
Floor Drains: None noted
Sump Pumps: None noted
Sump Pump Discharge Location: N/A
Sewage Ejector Pumps: None Noted
Exterior Hose Bibs
Condition: Tested - OK
Additional Plumbing
Fire Suppression
Water Heater
Hot Water Temperature
Water Temperature: 99
Water Temperature Too Low
The water temperature has been intentionally set low and outside of the normal operating range of 115 to 135 degrees F. Many homeowners lower the temperature for a variety of reasons. Recommend consulting the owners/seller for additional information, and a licensed plumbing contractor if an issue is present.
General Information
Condition: Operated Correctly
System Type: Conventional Storage Tank
Tanked Water Heater Maintenance Awareness
Storage-type (tanked) water heaters require periodic maintenance to perform as intended over their service life, though many homeowners are unaware that maintenance is recommended. Manufacturer guidance and general industry practices commonly include periodic flushing to reduce sediment accumulation and inspection of internal components such as heating elements or burners and the sacrificial anode rod, if equipped. If maintenance records or other evidence of recent servicing cannot be verified, having the water heater serviced may be appropriate to establish a known maintenance baseline and help maximize performance and remaining service life.
Manufacturer: Rheem
Capacity: 50 Gallons
Age: 2025
Energy Source: Gas
Unit Components
Expansion Tank: Inspected - OK
TPR (Temperature and Pressure Relief) Valve & Piping: Visually Inspected OK - Not Tested
Circulation Pump: No Timer
Drain Pan: Not Needed
Condensate Drain System: Not Applicable
Venting System: Inspected - OK
No Timer Found For Hot Water Circulation Pump
The water heating system has a circulation pump. This appeared to be operating at the time of inspection. For improved efficiency these are often put on timers so the pump can be timed to go off at night and in the middle of the day. I did not see a timer set up for this pump.
Sewer Scope
Sewer Type & Access
Scope Findings
Pipe Materials: PVC, SDR
Anomalous Findings: Further Evaluation Recommended
Functional Sewer Line with Concerns
The sewer line was functional and flowing at the time of the inspection; however, conditions were observed that may affect long-term performance or require maintenance or repair. Future service or repairs should be anticipated depending on the nature and progression of the noted conditions. The entire sewer scope video should be reviewed, as it may contain additional observations and context not fully captured in this written report.
Specific observations noted include:
Bellies (Low Spots)
- Moderate sag(s) noted: A sag is considered moderate if it is 25 percent to 50 percent of the pipe diameter. Moderate sags can be ok if they don't collect debris, but other times may require repair if blockages become a problem. Please note, that when the camera goes underwater, it makes visual inspection of the pipe at these areas difficult or impossible.
Recommendation: Have a qualified sewer contractor evaluate the observed conditions and perform maintenance or repairs as recommended. It can be sometimes be helpful to them to share this report with them.
Fuel Storage & Distribution
Gas Meter
Fuel Piping
Gas Piping Materials Noted: Steel, CSST
Gas/Fuel Odors Noted: No
Heating Cooling & Fireplaces/Stoves
Heating System
Condition: Operated Correctly
Type: Gas forced air - High Efficiency
This building has a gas forced air furnace. A critical component of all combustion heating equipment is the heat exchanger. This is the welded metal assembly inside the furnace that contains the products of combustion so that moisture, carbon monoxide and other products of combustion do not mix with interior air and get safely vented to the exterior. Heat exchangers on modern furnaces have an average life expectancy of 15-20 years. Unfortunately, heat exchangers are concealed inside the heating equipment; they are not visible and specifically excluded from this inspection. Cracks in heat exchangers may be concealed and can pose a potential safety hazard and therefore we recommended ensuring carbon monoxide monitors are present at all recommended locations (see electrical section) and to have a professional HVAC contractor service and check these units at least bi-annually.
Energy Source: Gas
Manufacturer: Lennox
Age: 2026
Temperature Difference Measurements: Normal
The output temperature of the heating system was tested after at least 5 minutes of operation and was within the normal operating range.
Thermostat(s): Tested
Number of Thermostats/Zones: 1
Condensate Drain System: Present & Correct
Air Conditioning / Heat Pump
Compressor Location: Exterior (North Side)
Type: Air Conditioning Present
The following list is a minimum set of requirements to be expected of heat pump or air conditioning servicing. These are provided as a courtesy to show they types of check-ups that should be expected from a professional servicing.
- Check compressor efficiency
- Check refrigerant level
- Clean the condenser coil
- Change or clean air filters
- Inspect contactors and wiring
- Inspect drive-sheaves, pulleys and belts
- Check and adjust for proper air flow
- Clean the blower motor as needed
- Lubricate all motors and shaft bearings
- Check, calibrate and program the thermostats and be sure the thermostat has adequate batteries as needed
Condition: Operated Correctly
Data Plate - Compressor: Data Plate Image
Manufacturer - Compressor: Lennox
Age - Compressor: Air Source (2025)
Energy Source: Electric
Heat Exchanger Type: Air Source
Refrigerant Type: R454B
Approximate Tonnage (BTU / 12,000): 2.5
Temperature Difference Measurements: Normal - Cooling - Actual Delta T
Temperature Drop Normal: An actual temperature drop measurement was performed across the evaporator coil of this unit. When tested, temperature at return register was 70 degrees, temperature at supply was 51 degrees, a difference of 19 degrees which is in the 14 to 28 degree normal operating range. This indicates the unit functioned properly when tested.
Thermostat(s): Tested OK
Number of Thermostats/Zones: 1
Emergency Overflow Pan: Not Applicable
Condensate Drain System: Present & Correct
Exhaust Vents/Flues
Condition: Inspected - OK
Air Filter(s)
Filter Location(s): At the Air Handler
Number of Filters: 1
Filter Size(s): Unknown
Filtration Type and Condition: Incorrect Filter Size
Air Filter - Incorrect Size
The air filter for the forced air furnace was not correctly sized and was allowing air to bypass the filter. Install the proper sized filter or consult with a qualified HVAC contractor as needed to install a properly fitting filter.
- The correct filter is likely four or five inches thick
Heat and Cooling Distribution System(s)
Heat Source in Each Room: Present
Mechanical Ventilation
Mechanical Ventilation Systems
Whole Building Fans and HRV/ERV(s): Whole House Exhaust Fan (Continuous Running Crawl Space Fan)
Bath Fan Ducting: Ducted to Exterior
Kitchen Fan Ducting: Ducted to Exterior
Dryer Ducting: Ducted to Exterior
Continuous Running Crawl Space Exhaust Ventilation System Noted
A continuously operating exhaust fan was observed and operating correctly in the crawl space. This type of system is commonly used in newer or tighter homes to provide ongoing ventilation by creating slight negative pressure in the building and exhausting air from the crawl space. In this installation, openings between the living space and crawl space allow some indoor air to be drawn toward the crawl space and exhausted outdoors. This is an intentional ventilation design, but performance depends on proper design, air pathways, and fan sizing. The fan should be monitored periodically to ensure it remains operational, as changes in operation or failure of the system may affect indoor moisture conditions, air exchange rates, and radon levels within the home. If the system is modified, disabled, or stops operating, a new radon test is recommended.
- Louvers on register for the intake for the whole house ventilation fan in the crawl space would not open. Suggest replacement or repairs of this register so that it will open and facilitate proper ventilation
Garage
General
Garage Type: Two Car Garage
Fire Separation: Inspected - OK
Floor
Concrete
Doors and Automatic Openers/Closers
Overhead Door Type: Insulated Metal
Overhead Door Condition: Tested - OK
Automatic Door Opener: Present & Tested
Overhead Garage Door Testing Note
The overhead garage doors were inspected, and a complete operating cycle was attempted, including testing of the electric safety sensors and the auto-reversing feature. However, the force-reverse function (if present) was not tested, as this test can potentially damage the door if the system is not functioning properly or the door is already compromised. We recommend that you—or a garage door specialist—perform this test by placing a solid object, such as a 2x4 laid flat, on the ground in the door’s path to verify that it reverses upon contact. If the door does not reverse promptly, or if there is any hesitation or visible damage, a qualified garage door technician should inspect, adjust, and repair the system as needed. Regular inspection and maintenance are recommended to ensure safe and reliable operation of all overhead doors.
Occupant Door Into Building: Fire Rated with Functional Self Closer
Laundry Facilities
Dryer Connection(s)
Energy Source: 120V Electric, 240V Electric
Transition Duct: Not Present
Dryer Make up Air: Appears Adequate
Washing Machine Connections
Condition: Visually Inspected - OK
Cabinet and Countertop(s)
Countertop Material(s): Natural Stone
This is a great document From the Natural Stone Institute that covers maintenance and installation recommendations for slab surface stone countertops.
Cabinet Material(s): Wood & Engineered Wood
Kitchen
Cabinet and Countertop(s)
Countertop Material(s): Natural Stone
This is a great document From the Natural Stone Institute that covers maintenance and installation recommendations for slab surface stone countertops.
Cabinet Material(s): Wood & Engineered Wood
Sink(s)
Condition: Inspected - OK
Food Waste Disposer(s)
Disposer(s): Operated
Video(s) demonstrate the food waste disposer(s) operating.
Dishwasher
Dishwasher: Operated (Tested Note)
Dishwasher Air Gaps and Johnson Tees: Air Gap Present
Range, Oven and Cooktop(s)
Power Source(s): 120V Electric, 240V Electric
Condition: Operated with IR, No Anti-Tip
Range Missing Anti-Tip Device
An anti-tip over device should be installed on this unit. If a child steps on the open door or if a heavy weight is placed on the door it may cause the stove tip forward and anything on the range top may slide forward causing injury. A properly installed anti tip bracket will allow the unit to slide in and out but not tip, preventing injury.
Ventilation
Operable Window, Fan Ducted Out Of Kitchen 📸
Fan Operating
This shows the kitchen fan operating and venting to location outside of the kitchen. If issues with ducting are noted, they will be noted in the mechanical ventilation section.
Installed Microwave(s)
Tested - OK
Microwave Tested OK
The video below shows the operation of the built-in microwave. It was tested as a courtesy using neon capsules which react when microwaves are present.
Refrigerator(s) & Freezer(s)
Refrigerator: None noted
Interior
Floor Coverings
Floor Material(s): Tile, Carpet, Laminate
Walls, Ceilings, Trim, and Closets
Wall and Ceiling Material(s): Drywall
Cracks & Blemishes: None Noted
Wall Insulation: Unknown/Not Visible
Doors
Door Material and Style(s): Hollow Core, Barn Style
Door Repairs Recommended
Interior door repairs are recommended. A qualified person should further evaluate and repair or adjust interior doors as needed for reliable performance.
Examples of observations noted include:
- Door stop for the hallway closet door looks like it had been kicked and ripped out of the wall. This should be repaired
Windows
Window Inspection Method: Inspected All
All Windows Inspected
All accessible windows were opened, closed, and checked for general operation during the inspection. The inspection included observing the condition of the frames, glazing, hardware, and overall function (where operable), as well as the visible condition of the surrounding trim, sills, and adjacent wall surfaces for signs of damage or moisture intrusion. Any significant deficiencies noted during testing are described elsewhere in this report.
Window Frame Material(s): Vinyl
Window Glazing(s): Double pane
Safety Glazing: Present Where Required
Escape and Rescue Openings
Escape and Rescue: Present - Meets Current Standards
IRC 2021 R310 - Escape and Rescue Openings
The following passage is from the 2021 International Residential Code and is meant as a reference for you. While older homes are not required to meet current code, escape and rescue openings are an important means of life safety in emergencies. They allow people to get out of home and first responders to get in. It states.....
"Basements, habitable attics, and every sleeping room shall have not less than one operable emergency escape and rescue opening. Where basements contain one or more sleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room. Emergency escape and rescue openings shall open directly into a public way, or to a yard or court having a minimum width of 36 inches that opens to a public way."
Bathroom - Primary
General
Testing Procedure Note
Bathroom Testing Procedures
During inspection today all plumbing fixtures in the bathrooms were operated. A moisture meter was ran around toilets and tile shower enclosures to check for concealed leaks and sounded for loose tile and finishes in shower and tub enclosures. However, bathtub overflow drains are not tested as this risks damaging finishes around the tub. Monitor tubs while filling and avoid pushing water into the overflow. Even well-installed overflow drains can leak, as the gaskets that seal the overflow will dry out over time and may no longer provide a watertight seal. Monitor plumbing after moving into a new home as testing during inspection presents less stress on plumbing than daily use. Please note that vacant homes present additional risk as it can be difficult to distinguish how the plumbing system will respond to daily use. Any defects uncovered during inspection are listed in this report.
Sink(s)
Condition: Inspected - OK
Cabinet and Countertop(s)
Countertop Material(s): Natural Stone
This is a great document From the Natural Stone Institute that covers maintenance and installation recommendations for slab surface stone countertops.
Cabinet Material(s): Wood & Engineered Wood
Toilet
Condition: Inspected - OK
Bathtub / Shower
Condition: Repairs Recommended
Shower Surround Type: Tile
Tile Shower Surround Noted
Tile shower surrounds require regular maintenance to remain watertight and functional. Their long-term reliability depends on installation materials and methods (such as backer board and waterproofing), which are not visible during a non-invasive home inspection. We make our best guesses about tile reliability using visual inspection and sounding for loose tiles. Moisture meters can also be used in some wall applications, but the moisture meter presents a false positive on most tile floors or pans. We recommend ensuring all corners and transitions are properly sealed with caulk and applying a grout sealer annually to help prevent moisture intrusion and prolong the life of the tile. Poor maintenance may lead to loose tiles or hidden water damage behind the surface.
Tub Type: Not Present
Tile Surround - Maintenance Recommended
Recommended necessary maintenance and repairs to protect the tile shower surrounds. The tile and grout in shower surrounds should be water tight to prevent damage. This is important regular maintenance to ensure reliable service life. All loose and failing caulking and grout should be repaired. For inside corners, sanded caulking is recommended. This caulking can be purchased to match the tile grout and will expand and contract and resist cracking. Areas should be thoroughly cleaned before applying caulking or it will not adhere. Please note that tile is difficult to inspect visually. The reliability of a tile installation depends on what the tile is mounted on and what it is mounted with but unfortunately none of this is visible after installation.
Ventilation
Type & Condition: Bath Fan (Operated OK)
Bathroom - Hallway
General
Caulking (Re-Caulking Needed Between Tub and Floor)
Re-Caulk Tub/Shower Floor Juncture
The caulking between the bathtub and the floor was observed to be deteriorated or incomplete and should be repaired or replaced to help prevent water from damaging the floor structure below. The urgency of this repair depends on how frequently the bathroom is used and how much water is splashed out during normal use.
Sink(s)
Condition: Inspected - OK
Cabinet and Countertop(s)
Countertop Material(s): Natural Stone
This is a great document From the Natural Stone Institute that covers maintenance and installation recommendations for slab surface stone countertops.
Cabinet Material(s): Wood & Engineered Wood
Toilet
Condition: Inspected - OK
Bathtub / Shower
Condition: Inspected - OK
Shower Surround Type: Tile
Tile Shower Surround Noted
Tile shower surrounds require regular maintenance to remain watertight and functional. Their long-term reliability depends on installation materials and methods (such as backer board and waterproofing), which are not visible during a non-invasive home inspection. We make our best guesses about tile reliability using visual inspection and sounding for loose tiles. Moisture meters can also be used in some wall applications, but the moisture meter presents a false positive on most tile floors or pans. We recommend ensuring all corners and transitions are properly sealed with caulk and applying a grout sealer annually to help prevent moisture intrusion and prolong the life of the tile. Poor maintenance may lead to loose tiles or hidden water damage behind the surface.
Tub Type: Cast Iron/Steel
Ventilation
Type & Condition: Bath Fan (Operated OK), Operable Window
Radon Mitigation System
System Components
Type & Condition: Possible Passive System?
Possible Unlabeled Passive Radon Mitigation System Noted?
A PVC vent pipe was observed that did not appear to be connected to any active plumbing venting. The pipe may serve as a passive radon vent system, which is sometimes installed in homes to allow soil gases to escape naturally through the roof. However, the pipe was unlabeled and its purpose was not confirmed.
Recommendation: The function of this pipe should be verified by the builder or a qualified contractor. If confirmed to be part of a passive radon mitigation system, proper labeling and inspection of the vent stack are advised to ensure it complies with current radon mitigation standards and is functioning as intended.
- The ventilation pipe should be capped or installed below the vapor barrier to allow the house's ventilation fan to function properly
Pests
No Significant Pest Issues Noted
Crawl Space
Access
Crawl Space Access Location: Interior Access (Bedroom Closet)
Crawl Space Access & General Condition
Photos show the location(s) of the crawl space access and general condition of it.
Method of Inspection: Fully Traversed or Viewed
During inspection of the crawl space, every effort was made to inspect the entire space. Visual inspection of crawl spaces is difficult and limited as access is often restricted by pipes, ducts and sub-floor insulation as well as limited clearances.
Foundation/Floor Insulation
Insulation Type & Location: Fiberglass Blankets, Sprayed Foam, Stem Wall Insulated, Rim Joist Insulated
Approximate R-Value: R-6-10
Stem Wall Was Covered with Insulation Limiting the View
The stem-wall of the crawlspace was covered with insulation. This does make detection of latent defects very difficult or impossible to find with out removal of the insulation. This is considered a limited review of this area as inspectors do not remove or damage insulation during general building inspections.
Moisture Control
Approximate Relative Humidity: 35%
Ventilation Method: Appeared Adequate, Ventilation Fan
Vapor Barrier: Plastic Sealed to Foundation - OK
Condition: No moisture control problems were noted at the time of inspection
Mold / Deterioration: Dry (Likely From Time of Construction)
Mold-Like Substances Noted On Floor Framing in Crawl Space
Mold like substances/stains were noted on some of the wood framing below the house. This was likely from the time of construction. It is common for framing lumber to have stains from construction or even for this to form during construction from weather at that time. As long as the wood remains dry, risks to air quality would seem to be low indoors but mold air samples are advisable in living areas. This should be reviewed by a mold remediation contractor and cleaned as advised.
Structural Systems
Foundation
Condition: Inspected - OK
Evidence of Significant Renovations or Additions: No
Approximate Percentage of Foundation Visible: 30%
Primary Foundation Type: Crawl Space (Poured Concrete Footers, Poured Concrete Stem Walls)
Primary Foundation Location: Under Entire Building
Columns Posts & Beams
Condition: Inspected - OK
Floors Walls & Ceilings - Structural
Floor Structure Material(s): Engineered Wood Beams/Girders, Wood I-Beams/Joists (Engineered)
Sub-Floor Material(s): OSB
Sloping Floors: No Significant Slopes Noted w/o Tools
Wall Framing Material(s): Not Visible/Unknown
Wall Sheathing Material(s): Not Visible/Unknown
Ceiling Framing Material(s): Bottom Cord of Truss
Structural Cracking: None Noted
Trim or Cabinet Separation: None Noted
Check Out Procedure
Oven: Off
Dishwasher: Off / Finishing Cycle
Heating and Cooling: Restored to Pre-inspection Settings
Lights: Client and Agent Still In House
Exterior Doors: Not Locked - Client and Agent Still Present
Service Providers
Below is a list of local contractors we have come up with to help you with any repairs or consultation you may need. We have no affiliation or financial interest with these contractors and have put this list together from our own experiences and from people we work with. We make no guarantee on their ability to do the work, or the quality of the work itself. If any of these contractors performs exceptionally well or very poorly, we would appreciate you letting us know.
Appliance Repair: Genesis Appliance : 970-361-0733
Crawl Space Moisture Control: Square One Radon : Rob Hartop: 970-712-4570
Electrician: Unified Service Solutions: Justin Sack: 970-640-1311
Dave Fisher Electric: 970-242-4012
Excavation: Brian's Backhoe Service : 970-245-0268
Environmental Testing
Asbestos: Grand River Environmental : 970-424-4749
Mesa Environmental (Asbestos Testing) : John Witkamp: 970-201-7070
Meth: Grand River Environmental : 970-424-4749
Lead Paint: Grand River Environmental : 970-424-4749
Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Radiation (Mill Tailings): Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Phase 1 Environmental Site Assessments: Grand River Environmental : 970-424-4749
Environmental Remediation, Abatement, Mitigation:
Radon: Square One Radon : Rob Hartop: 970-712-4570
Click here for NRPP approved radon mitigation professionals
Asbestos: Regional Asbestos: 970-242-0016
Lead Paint: Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Radiation (Mill Tailings): Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Mold: Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Foundation Repair: DWT & Assoc: Dale Thome: 970-261-1517
Mays Construction Specialties Inc.: 970-245-0834
Groundworks: 844-252-4383
Aspen Foundation Repairs LLC : 970-446-5453
Garage Door Installation and Repair: Monument Garage Door: Ryan Reimer: 970-201-5840
Mesa Door Systems: Walt McGinley: 970-234-2123
Gutters: Installation, Repair, & Cleaning: Top Tier Seamless Gutters: Chad Gardner: 406-860-1958
HVAC: Local Plumbing and Heating: Cory Smith: 970-644-1194
Junk Removal: Square U Away : 970-444-5865
Landscaping, Grading, and Drainage: PTL Landscaping : 970-985-9442
Masonry: L E Dangler Masonry Contractor: 970-523-4550
Mobile/Manufactured Home Leveling & Foundation Repairs: DWT & Assoc: Dale Thome: 970-261-1517
Plumbing: Local Plumbing and Heating: Cory Smith: 970-644-1194
True Plumbing: Stephan Hedemark: 970-946-7922
Pool Cleaning, Maintenance, & Inspections: Rocky Mountain Aquatics: Patrick Kitson: 970-424-7366
Roof Restoration (Asphalt Composition Shingles) with Minor Repairs: Roof Maxx of Grand Junction: Nate Anderson: 970-846-8010
Roof Service(Residential): JP's Roofing: Jake Palmer: 970-683-0962
Bro's Roofing: 970-651-7947
Olivera Roofing: 970-208-7149
Roof Service (Commercial): Full Curl Roofing Co: Jake wood: 970-985-1350
Bro's Roofing: 970-651-7947
Sewer/Septic
Septic System Inspections: Scope It Out: Chris Heineman: 970-210-2471
Sewer Line Repairs: Rocky Mountain Sewer Pros: 970-307-4667
Sewer Line Inspections (Reversed - From Main into the Building) : Sightline Solutions: 970-623-2652
(When no accessible cleanout is found near building or sewer main was too far from cleanout and could not be inspected during our scope)
Structural/Civil Engineer: SGM: 970-930-8228
Termite & Pest Control: Chrome Pest Control: 970-300-3307
Additional Resources
Home Repair Manual & Seasonal Maintenance Checklist
Below are helpful links that will educate you on your property and its systems. Taking the time to learn about your home may save you time and money in the future! As always, please do not hesitate to contact us if you have any questions!










 (1) (1).png)