Residential Pre-Sale Inspection Report
How to Read This Report
See the video link above. For the best experience, read this report online in its HTML format on a desktop computer as mobile can be tougher to digest this much information. This will allow you to easily expand sections, click blue links for additional information, and view embedded videos that provide important context beyond text and photos. Share the report by copying the web link from your browser, or print/save as a PDF using the buttons at the top, though printed copies greatly limit information. You can also create a custom Request List to generate a PDF of selected items to avoid sharing the entire report if needed.
This report is organized by chapters and sections, with general information in black text and any deficiencies or observations highlighted in colored boxes. Sections without observations were inspected and found to be in satisfactory/serviceable condition at the time of inspection.
Purpose and Scope
Purchasing a Property Involves Risk
Buying a property involves risk and these inspections aim to reduce those risks by providing a professional opinion on its overall condition. However, it's crucial to understand the limitations of these inspections.
Limitations
Home inspections are not warranties, guarantees, or insurance policies. They are limited visual inspections and cannot eliminate all risks inherent in property purchases. Inspections are non-destructive, meaning they involve visually examining accessible areas without dismantling or damaging the structure. Concealed areas and systems that cannot be tested without risk of damage are not covered.
This is Not for Code Compliance
This inspection did not assess code compliance. Building codes constantly evolve, and all buildings fall out of code compliance shortly after they are built, as the codes continually change. There are generally no requirements to bring older homes into compliance unless renovations are being done and permits are needed for the work.
This is Just Our Opinion
Construction techniques and standards vary. There is no one way to build a house or install a system in a house. The observations in this report are opinions of the professional inspector. Other inspectors and contractors are likely to have some differing opinions. You are welcome and encouraged to seek opinions from other professionals.
Scope
While this inspection adheres to ASHI standards of practice (which can be found by Clicking Here) and covers major systems such as the exterior, roof, structure, heating/cooling, etc., it may not include auxiliary systems. This inspection and report are not intended to be technically exhaustive due to cost and time constraints. Such inspections are available but they are generally cost-prohibitive for most people and would involve multiple specialists and engineers. Our goal is to help you understand the property's overall condition, ensure your expectations are realistic, and help you make informed decisions moving forward.
Observation Labels
All narrative observations are colored, numbered and labeled to help you find, refer to, and understand the severity of the observation. Observations used in this report are:
- Major Concern:Repair items that may cost significant money to correct now or in the near future, or items that require immediate attention to prevent additional damage or eliminate safety hazards.
- Repair:Service, maintenance, repair, or replacement is recommended for theses items. These are less severe in nature than Major Concerns, but should be dealt with sooner rather than later.
- Due Diligence:Items that may require specialist evaluation to determine repair severity or urgency, or may warrant additional inquiry to clarify the condition such as a plumbing fixture that was not tested due to the water supply being off.
- Future Project/Repair:A repair that may be deferred for some time but should be on the radar for repair or replacement in the near future.
- Routine Maintenance:These are repair items that should be considered "routine" and are part of normal property ownership such as servicing the furnace, cleaning the gutters, painting, or changing the air filters in the furnace.
- Improve or Upgrade:Observations that are not necessarily defects, but which could be improved for safety, efficiency, or reliability reasons. These are often items which reflect changes in building codes or standards.
- Minor Repair:Service, maintenance, repair, or replacement is suggested for theses items. These are repairs that are minor in terms of difficulty and cost for the average person.
- Monitor:Items that should be periodically inspected to see if correction may be needed in the future.
- Efficiency Item:Observations that would make the home more energy efficient and to bring the home up to modern standards. This category typically includes windows and insulation.
- Limitation:Conditions present limited the scope of this visual inspection
- Inspection Note:Information and/or comments that you may find useful for purchase decisions or general property ownership.
Summary
Major Concerns
- RCG-4 Roof Chimney & Gutters - Roof Covering(s) - Garage:
Roof Replacement Recommended
The roof was done in a three tab composition shingle. The roof looks to be at the end of its reliable service life. Roof replacement is recommended to ensure reliable roof performance. If this is a real estate transaction, the insurability of the roof should be verified.
Examples of observations noted include:
Recommendation: Hire a qualified roofing contractor to further evaluate and replace this roof.
- WH-5 Water Heater - General Information:
Water Heater Inoperative
This water heater was inoperative at the time of inspection. Did not determine why and although this may be a simple cheap fix, if it's not, there is a potential high cost associated with water heater replacement. A licensed plumber should further evaluate and repair as needed if its not a simple fix. Suggest verifying correct hot water all fixtures and that the temperature is between 115 and 130 degrees F after repairs or replacement.
Specific observations noted include:
- While running hot water hot water initially came out and then stopped so the tankless water heater was inspected and found to be beeping with a code 10 flashing on the screen. The unit was turned off and back on again and the same result happened a second time
- SS-3 Sewer Scope - Scope Findings:
Limited Camera Access - Blockage
Due to a blockage within the sewer pipe, the entire line all the way to the sewer tap was not scoped. The blockage was encountered approximately 40 feet from the access point. This should be cleared and then the remainder of the side sewer pipe should be scoped as deficiencies may be present in portions of the pipe concealed by murky water or beyond the obstruction. Suggest cleaning and further evaluation by a sewer line specialist.
- The end of the scope was located with green paint for your convenience and can be found in the media below.
Repairs
- G1-2 Grounds - Grading and Drainage:
Siding to Soil Contact Noted
Eliminate siding / soil contact at all areas to reduce the chances for deterioration and pest damage and repair any concealed damage as needed. Generally, a 6-inch clearance between soils and siding is recommended. This is often not realistic on older homes, but repairs should be made to achieve as much clearance as possible, and all direct soil contact should be eliminated. Maintaining this clearance is important not only to protect the siding, but also to help safeguard the underlying wall framing from moisture intrusion, rot, and wood-destroying pests. When creating this clearance, current standards recommend the grading adjacent to the building should be positively sloped at a 5% grade within 10 feet of the building.
See media for examples of locations:
- G1-8 Grounds - Outbuilding:
Repairs Recommended to the Detached Garage
Implement repairs to this building as deemed necessary by a qualified general contractor.
Specific observations noted include:
- The garage circuits did not appear to have any power
- Corner of the garage appears to have been damaged by impact and needs to be repaired. Repairing this at the time of redoing the roof would be a good idea
- E-2 Exterior - Exterior Doors:
Exterior Door Repairs Recommended
Repairs are recommended to the exterior doors. A qualified contractor should repair exterior doors as needed.
Observations noted include:
- Main entry door deadbolt was very difficult to use / turn the knob. It appears to be rubbing on the strike plate and adjustments are needed so that it can be locked and unlocked easily
- RCG-2 Roof Chimney & Gutters - Roof Covering(s) - House:
Roof Repairs Needed
Tune up repairs are needed on the roof covering.
Specific observations noted include:
- cracked ridge cap tiles were noted. These should be replaced.
Recommendation: Have a qualified roofing contractor proficient with this roofing system review and repair as advised.
- ES-12 Electric Service - Sub Panel - Basement (Small):
Incorrect Wiring to a 4+ Conductor Feed Sub-Panel
The wiring to this sub-panel requires repair. The neutrals should be on a floating bus bar (not connected to the panel) and should be separated/isolated from the equipment grounds (attached to the panel) to eliminate stray voltage. A licensed electrician should further evaluate and repair this condition.
- EDF-3 Electric Distribution & Fixtures - Receptacles & GFCI's:
Receptacle(s) - Open Neutral
Circuit tester showed open neutral (white wire) on receptacle(s). With no neutral connected, this renders the receptacle inoperative. Have this further investigated and repaired as recommended by a qualified electrician to ensure safe and reliable performance.
Location(s) noted include:
- Ground floor en suite bathroom
- EDF-4 Electric Distribution & Fixtures - Receptacles & GFCI's:
Inoperative Receptacles Noted
Inoperative electric receptacles were noted. These may be on a switched or GFCI protected circuit, but no switch or tripped GFCI was found during the inspection.
Recommendation: Have inoperative electric receptacles further evaluated and repaired by a licensed electrician as needed.
See media for locations and details:
- EDF-10 Electric Distribution & Fixtures - Smoke and Carbon Monoxide Alarm Systems:
Incorrect Location(s)
Enough Carbon Monoxide alarm/detector(s) were present, however, some detectors have not been installed in the correct location(s). Ensure they are located within 15 feet of the bedroom entrance(s) and on each level. It is also recommend they be installed in rooms with fireplaces, wood stoves, gas heaters, or any fuel burning appliance for safety. CO alarms should be replaced every 10 years per the manufacturers instructions.
- No carbon monoxide alarm was noted on the second story in the primary or near the primary bedroom
- P-4 Plumbing - Water Supply:
High Water Pressure Noted
When static water pressure exceeds 80 psi (pounds per square inch), a pressure reducing valve is recommended to control water pressure and prevent damage to the supply piping system and appliances. High water pressure is typically due to high pressure delivered from the water utility and a lack of a or failing pressure reducing valve.
Recommendation: Have a licensed plumber evaluate and repair as needed.
- WH-7 Water Heater - Unit Components:
Thermal Expansion Device Recommended
When a storage tank water heater or tankless water heater (with a recirculation system) is present, a thermal expansion tank or valve should be installed to prevent a leak at the TPR (Temperature Pressure Relief) valve. Expansion tanks help reduce pressure on the plumbing system by creating a buffer or a place for water to expand into as water expands with thermal expansion (50gal of cold water becomes 52gal of hot water). Installation of an expansion device or pressure tank is modern installation practice and will be required if a pressure reducing valve has been installed on a public water supply or if the plumbing system is closed for any reason. Open systems do not require a thermal expansion device though they can still be an excellent way to help prevent build-up of pressures in the piping system. Consult with a qualified plumber to install.
- BP-3 Bathroom - Primary - Toilet:
Toilet Mounting Issues Noted
The toilet needs to be reset, and the wax ring and flange should be checked and replaced as needed to ensure reliable performance and prevent leaks. This is a some what simple job unless the bolts that fasten the toilet also require repair. Sometimes, loose toilets can even be shimmed for a tight and proper seal by qualified plumbers, and sometimes simply caulking can help prevent the toilet from rocking and twisting.
- The toilet was loose on the floor and rocking or twisting.
- No caulking was noted between the floor and the toilet - caulking is recommended to keep unpleasant bathroom liquids from entering here and to help adhere the toilet to the floor.
- No moisture was noted around this toilet
Recommendation: Hire a licensed plumber to evaluate further and repair this toilet.
- BP-7 Bathroom - Primary - Ventilation:
Bath Fan Inoperative
The bath fan did not appear to be fully operational. These are necessary to prevent moisture and mold issues in the bathroom. Its possible that its controlled by a sensor or hidden switch. Suggest a qualified contractor review for repairs.
- Bath and above the tub did not work, but the bath fan in the lavatory did operate.
- BB-1 Bathroom - Basement - Sink(s):
Leaking Drain
The drain plumbing was leaking and requires immediate repair to prevent damage to the cabinet. This only leaks when the faucet is used. Hire a qualified plumber to repair.
- BB-2 Bathroom - Basement - Toilet:
Tank Leaking
Toilet water storage tank was leaking when flushed. This requires immediate repair as it could start to leak and cause water damage. Repair or replace this toilet as needed.
Due Diligence Items
- G1-6 Grounds - Irrigation:
Irrigation System Present
An irrigation system was observed. We apologize, but these are out of the scope of this inspection. Recommend inquiring with the sellers about the condition and operation, and having a qualified irrigation professional inspect it if a detailed report is desired. PLEASE REMEMBER TO WINTERIZE THE SYSTEM EVERY FALL TO PREVENT COSTLY REPAIRS.
- P-7 Plumbing - Exterior Hose Bibs:
Inoperative Hose Bib
An inoperative hose bib was noted at the west side. This is quite often due to closed valve. Repair, update, or make operative as needed.
- WH-8 Water Heater - Unit Components:
Water Heater Circulation Pump Unplugged
The water heater had a circulation pump but was not plugged in. These pumps circulate hot water through the house to reduce wait times for hot water a fixtures, which is a really nice feature. If concerned, Inquire with the seller why it was not in use. Its common to unplug it to save energy costs, although adding a timer to these is great so the pump can be timed to go off at night and in the middle of the day. If it is not operational and use of it is desired, a licensed plumber should review and repair as needed.
- K-9 Kitchen - Refrigerator(s) & Freezer(s):
Ice Maker Off
The refrigerator ice maker was off during the inspection, so its functionality was not verified. Recommend verifying function before closing.
Future Projects/Repairs
- G1-3 Grounds - Grading and Drainage:
Poor Site Grading
The grade of the yard sloped toward the building. Standards recommend at least a quarter-inch / foot slope away from the building for 10ft if possible to prevent water from draining toward the building. Over time, negative grading, as this is often called, can lead to moisture and even structural problems with the building, especially when roof drainage discharges to this area. Have this repaired as feasible by a qualified contractor. Often, a swale can be used to create a low point away from the house into which water can be diverted safely away from and around the building.
See media for details and locations:
Recommended Maintenance
- G1-5 Grounds - Trees and Vegetation:
Tree And Vegetation Pruning Recommended
Pruning trees, branches and vegetation away from the building is recommended. Where trees, branches and large shrubs can provide rodent access to the roof, a minimum 6-foot clearance is recommended as many rodents can jump 6-feet. All vegetation, including smaller landscaping such as grasses, flowers and shrubs should be kept 1-foot off the house to eliminate contact which could trap moisture against the building or eventually cause mechanical damage.
- E-1 Exterior - Siding and Trim:
Painting Repairs Recommended
Localized painting repairs are recommended to the exterior of the building. This is common recommended maintenance between complete exterior paint jobs to ensure that the more exposed areas continue to perform reliably without rot or decay from weather. Implement repairs as recommended by a qualified contractor.
- Repainting may be needed to meet lending or appraisal requirements. FHA, VA, and USDA often require painted surfaces to be free from peeling paint.
See media for examples and locations:
- RCG-5 Roof Chimney & Gutters - Gutters and Downspouts:
Gutter Cleaning Recommended
The gutters had excess debris in them and should be cleaned to ensure proper control of roof runoff. Ensure they are unobstructed, leak-free and properly sloped to drain as part of routine maintenance. Ensure the downspouts are clear as well as these can be clogged causing the gutters to fill which may cause damage to them or the building.
- HCF-13 Heating Cooling & Fireplaces/Stoves - Air Conditioning / Heat Pump:
Outside Condenser Cooling Fins Dirty - Clean
The outside condenser coil fins were dirty and need to be cleaned by a qualified HVAC contractor. Dirty fins restrict the air flow and will reduce efficiency, decrease equipment life, and increase cooling costs.
Improve Or Upgrade Items
- G1-7 Grounds - Window and Stair Wells:
Add Covers Window Wells
Ideally, a clear plastic cover should be installed over window wells to allow light in, but keep debris, rain, and snow out also but be able to opened easily from the inside for emergency egress (or ingress should the need arise).
- E-3 Exterior - Exterior Doors:
Exterior Door Has A Keyed Interior Lock
The lock for the south side entry door door requires a key rather than a thumb-toggle from the inside to open/unlock. This can inhibit emergency egress. Recommend switching this lock with a thumb-toggle one for improved safety. This is required for the main egress door, but recommended for all doors for improved safety.
- ES-3 Electric Service - Main Electrical Panel:
No Surge Protection Noted
No surge protection was noted at the electrical equipment today. The 2020 edition of the National Electric Code requires type I or type 2 surge protection on new or renovated homes. This code change reflects the growing complexity of electric appliances in our houses and the growing risk of damage to electrical equipment due to internal or external electrical surges. This short video explains more about electrical surges and surge protection. Recommend upgrading and adding surge protection for improved protection of the electrical appliances/devices in this building. Suggest doing this in the context of other electrical repairs or upgrades.
- ES-9 Electric Service - Sub Panel - Basement (Large):
AFCI Protection was Inconsistent with Modern Standards
AFCI (Arc Fault Circuit Interrupter) breakers, which were introduced around 2002, are designed to detect dangerous electrical arcing caused by damaged, loose, or aging wiring that standard breakers can not sense. These arcing conditions can generate high heat without drawing enough current to trip a conventional breaker, which increases fire risk🔥. Modern electrical safety standards now call for AFCI protection on most residential circuits, so it is common for older homes to fall short of these standards. While upgrades are not required for existing homes, improving AFCI protection is considered a meaningful safety improvement, especially when other electrical work is being performed.
- EDF-5 Electric Distribution & Fixtures - Receptacles & GFCI's:
GFCI Protection Improvements Recommended
Since the 1970s, requirements for GFCI (Ground Fault Circuit Interruption) protection have changed, and locations requiring GFCI protection seem to get added with every code cycle. It is common for older residential buildings to have some or even many electric receptacles that do not meet modern safety standards. GFCIs have proven successful at reducing electrocutions, and it seems likely that someday, every circuit, receptacle, and appliance in the building will require GFCI protection. The first chart below shows how successful GFCIs have been at reducing risks from electrocution. The second illustration shows where GFCI protection is required as of the 2020 NEC. In terms of safety, its recommended to bring GFCI protection up to modern safety standards.
GFCI protection was lacking for receptacles in the following locations:
- Basement Bathroom
- I-7 Interior - Windows:
Safety Glass Not Present at All Hazardous Locations (Older Construction)
Window glass did not appear to be safety (tempered) glazing at all locations where modern standards typically call for it, based on the absence of an etched safety label on the glass panes noted. Safety glass is designed to reduce the risk of injury if broken; tempered or laminated glazing is manufactured to break into small, less-sharp pieces rather than large hazardous shards. In older homes, this type of glazing was often not required at the time of construction, so standard glass may still be present. Modern construction practices generally call for safety glazing in hazardous locations such as near doors, stairways, walkways, and bathing fixtures to reduce the likelihood of serious injury if accidental impact occurs.
Recommendation: This is common in older construction. For improved occupant safety and to better align with modern practices, upgrading to properly labeled safety glazing may be considered. If windows or doors in the areas noted are replaced in the future, safety glass will typically be required at that time. If safety upgrades are desired, evaluation by a qualified glazing or window contractor is advised.
See media for locations:
- Ground level Hall bathroom
- I-10 Interior - Interior Stairs and Guardrails:
Handrail Repairs Recommended
The graspable handrail for the interior stairs was missing. This should be a round railing 1 1/4 - 2 inches in diameter. If the railing is not round it must have a finger groove that is 3/4 of an inch down from the tallest point of the rail. The graspable handrail should also be 1.5 inches from the wall and have returns into the wall and run the length of the stairs. Have a qualified contractor build suitable railings to reduce the potential for falls.
Minor Repairs
- G1-4 Grounds - Grading and Drainage:
Downspout Drainage Improvements Needed
Deficiencies were noted with the roof drainage system. Downspouts should collect roof runoff and discharge it away from foundations, slabs, retaining walls, posts, and other structural elements. When water is concentrated in these areas, excess moisture can contribute to settlement, erosion, water intrusion, movement of flatwork, deterioration of building materials, and other moisture-related issues over time. Depending on the specific condition, corrections may range from simple maintenance or adjustment to more substantial improvements by a qualified gutter, drainage, or landscape contractor.
Examples of observations noted include:
- Please 🙏 keep the downspout extensions folded down.
- Plastic corrugated extension are unreliable. Replacing them with a more permanent durable solution is preferred.
- Downspouts discharged adjacent to the foundation or flatwork/footings.
- Downspouts discharged on an area that slopes back toward the building.
- E-4 Exterior - Wall Vent/Exhaust Terminations:
Vent Terminal - Repair
Replace or repair the vent terminal at the east side. The terminal was missing. Vent terminals should have a hood to prevent weather entry and a backdraft damper to prevent air and pests from entering. If this is a dryer vent, it should not be covered with a screen as it will plug with lint.
- EDF-6 Electric Distribution & Fixtures - Receptacles & GFCI's:
Missing Electrical Cover Plates
The missing cover plates to all electric receptacles, switches, and junction boxes should be installed to cover all access to the wiring and terminals for safety.
See media for locations:
- EDF-7 Electric Distribution & Fixtures - Lighting:
Inoperative Lights
Inoperative lights were found. Have these further investigated and repaired as needed. If a new bulb does not correct the problem, consult with a licensed electrical contractor.
Note: Unfortunately some newer LED fixtures do not have a replaceable lighting element and these fixtures will have to be replaced if the LED has failed.
See media below for locations of inoperative lights:
- EDF-8 Electric Distribution & Fixtures - Ceiling Fans:
Wobbly Ceiling Fan(s) Noted
The ceiling fan(s) were wobbling during operation. This can be a simple matter of balancing the fan blades, but it could also indicate an inadequately secured fan, which can present a safety hazard. Have this further evaluated and repaired as recommended by a qualified electrical contractor.
Location(s) noted:
- HCF-14 Heating Cooling & Fireplaces/Stoves - Air Filter(s):
Incorrect or Poor Fitting Air Filter(s)
Improperly sized or poor fitting air filters can allow unfiltered air to bypass the filter, reducing overall air quality and allowing debris to accumulate within the HVAC system. Repairs or adjustments are recommended to ensure the filter seals properly and all air passes through it as intended.
- HCF-16 Heating Cooling & Fireplaces/Stoves - Heat and Cooling Distribution System(s):
Register Covers Missing
The HVAC air register covers were missing in places and should be installed so that duct flow can be adjusted as desired, keep debris, pests and kids out, and for a proper finish.
See media for locations and details:
- K-2 Kitchen - Sink(s):
Sink Repairs Recommended
Repairs are recommended to this sink and a qualified plumber should further evaluate and repair as needed.
Observations noted include:
- The aerator was missing from the faucet
- K-7 Kitchen - Ventilation:
Fan Operating
This shows the kitchen fan operating and venting to location outside of the kitchen. If issues with ducting are noted, they will be noted in the mechanical ventilation section.
- The light was inoperative, repair/replace as desired.
- I-4 Interior - Doors:
Door Repairs Recommended
Interior door repairs are recommended. A qualified person should further evaluate and repair or adjust interior doors as needed for reliable performance.
Examples of observations noted include:
- Pocket door pool was missing for the upstairs primary bathroom lavatory. This makes it difficult to pull the door out of the pocket.
- Ground floor middle bedroom closet door would not latch
- BGFM-1 Bathroom - Ground Floor Main - Sink(s):
Slow Drain Noted
A slow drain was noted at the sink. This may be from the disposer or a clog in the waste plumbing in another location. Hire a qualified plumber to further evaluate and correct the slow drain as needed.
Items for Monitoring
- WH-6 Water Heater - General Information:
Older Water Heater Noted
Water heater was older and statistically may be nearing the end of its useful life. The average life of a water heater is statistically 8-12 years though in practice, they can vary widely between 8-20 years, or more, depending on water quality and maintenance schedule such as frequency of flushing the tank and replacing sacrificial anodes. Water heater was functioning as expecting at the time of inspection, but it would be wise to budget for replacement. Suggest monitoring this unit frequently for signs of leakage or corrosion.
- HCF-5 Heating Cooling & Fireplaces/Stoves - Heating System:
Condensate Lift Pump Noted - Not Tested
Condensate lift pump was observed and visually inspected only. These pump the condensate produced by the appliance up to a higher location where it can drain via gravity. Testing the operation of these devices is beyond the scope of this inspection but they are a maintenance item that can fail at any time. These can be tested by pouring water into them forcing them to pump it out. Suggest periodic checks on this pump to prevent water damage to surrounding areas from overflows.
Efficiency Items
- I-3 Interior - Walls, Ceilings, Trim, and Closets:
Thermal Anomalies Noted - Dry
Based on our experience, these thermal images likely indicate disturbed, missing, or under-performing insulation or poor air sealing at the areas pictured. Areas were dry at inspection. Suggest a qualified person review the areas to determine if repairs would be cost effective for increased thermal efficiency/comfort.
See media for details and locations:
Limitations
- A-1 Attic - Access & Type:
Missing Attic Access
Based on the roof and ceiling design, there appears to be an attic cavity. However, the access to this area was missing or not found above the 2nd Story. Therefore, we were unable to view the attic in this area to note possible evidence of leaking, the amount and type of insulation, the condition of the components, etc. Standards recommend an access opening of 30 inches x 22 inches when there is greater than 30 sq/ft of attic space. Recommend arranging access and fully inspecting this area if possible to ensure safety and serviceability.
- WH-1 Water Heater - Hot Water Temperature:
Hot Water Temperature Not Tested - Water Heater Inoperative
The water temperature at time of inspection could not be tested because the water heater was inoperative. Suggest verifying correct hot and cold plumbing at all fixtures and that the temperature is between 115 and 130 degrees F when the water heater is repaired or replaced for safety.
- G-2 Garage - Doors and Automatic Openers/Closers:
Overhead Door Blocked - Not Operated
The garage door was not operated because it was blocked by personal belongings. Recommend consulting with the sellers about the condition and operation of the door.
- CS-1 Crawl Space - Access - Rear:
Viewed Crawl Space From Basement/Pit Area Only
Access to the crawlspace areas was limited due to minimal clearances. The only visible portions were those observable from the basement or pit area. In older buildings, it is common for floor framing to be built directly over soil or with minimal clearance, leaving no accessible crawlspace for inspection. As a result, much of the subfloor structure and foundation conditions could not be evaluated. When components such as plumbing or electrical systems in these areas require service or replacement, sections of the floor system may need to be removed to provide access. In some cases, excavation beneath the home may also be necessary to allow access for repairs or improvements.
- CS-3 Crawl Space - Access - Front :
Limited Access in Crawl Space - Viewed from Entry Only
The crawlspace was viewed from the entry only. Inspectors are not required to enter crawlspaces that in the inspector's opinion are unsafe due to low clearances, standing water, biohazards, etc. We were unable to fully inspect the entire crawlspace to note possible evidence of water leaks, the amount and type of insulation, the condition of the components, etc.
The reason it was only viewed from the entry was:
Reasons for Limited Inspection
- The access opening was simply too small to safely fit into. General standards recommend an 18 by 24-inch access opening.
Recommendation:
- The entire crawlspace could be seen from the entry and its doubtful if new observations would be made by crawling the entire space.
✅Complete Report
Grounds
Elevation Photos
Grading and Drainage
Driveways/Walkways/Flatwork
Fencing
Trees and Vegetation
Irrigation
Window and Stair Wells
Exterior Stairs and Guardrails
Retaining Wall(s)
Outbuilding
Roof Chimney & Gutters
Roof Covering(s) - House
Roof Covering(s) - Garage
Flashings and Penetrations
Gutters and Downspouts
Skylights
Electric Service
Service Entrance
Main Electrical Panel
Electrical Grounding System
Electrical Bonding System
Sub Panel - Basement (Large)
Sub Panel - Basement (Small)
Appliance Disconnects
Electric Distribution & Fixtures
Branch Wiring
Receptacles & GFCI's
Lighting
Ceiling Fans
Smoke and Carbon Monoxide Alarm Systems
Low Voltage Wiring
Plumbing
Water Supply
Distribution Piping
Drain Waste & Vent
Exterior Hose Bibs
Floor Drains, Sump & Ejector Pumps
Heating Cooling & Fireplaces/Stoves
Heating System
Space Heaters
Air Conditioning / Heat Pump
Exhaust Vents/Flues
Air Filter(s)
Heat and Cooling Distribution System(s)
Kitchen
Cabinet and Countertop(s)
Sink(s)
Food Waste Disposer(s)
Dishwasher
Range, Oven and Cooktop(s)
Ventilation
Installed Microwave(s)
Refrigerator(s) & Freezer(s)
Other Appliances
Interior
Floor Coverings
Walls, Ceilings, Trim, and Closets
Doors
Windows
Escape and Rescue Openings
Interior Stairs and Guardrails
General Information
Building Characteristics, Conditions and Limitations
Type of Inspection: General Home Inspection
Primary Building Type: Single Family (No Attached Garage, 2 Story w/ Basement)
Building Foundation Type(s): Basement, Crawlspace (Traditional Stem Wall)
Additional Buildings Inspected: Detached Garage
Approximate Square Footage: 3577
Approximate Year of Original Construction: 1921
Unless the wiring in the building has been fully updated, this building likely has wiring that predates the late 1980's. Branch circuit wiring installed in buildings built prior to the late 1980's is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring. It is beyond the scope of this inspection to determine if any such incompatible components are installed. Based on the age of this building, be aware that such components may be present.
Additional Services Performed with Inspection: Radon Test, Sewer Scope, Elevation Survey
Occupancy: Occupied
Occupied Building Note
This building was occupied at the time of the inspection. This presents some challenges as occupant belongings can obstruct visual inspection of and access to parts of the building. We do our best during the inspection to work around belongings to discover as much as possible about the building without moving or damaging personal property, however, the presence of personal items does somewhat limit the inspection.
Animals Present: No
Access to the Property Was Granted By: Client's Agent
Attending the Inspection: Client's Agent
Approximate temperature during the inspection: 80F to 100F
Weather during the inspection: Hot and Dry
Ground/Soil surface conditions: Dry
Rain or Snow in Last 3 Days: No
For the Purposes of This Report, the Front Door Faces: West
Approximate Start and End Times: 1:00pm, 6:30pm
Old Buildings May Contain Lead and Asbestos
In 1978, federal laws were passed to prohibit use of lead and asbestos in building materials. Manufacturers of building materials were allowed to sell existing stocks of materials that were manufactured with lead and asbestos, so even buildings constructed as late as the mid-1980's could possibly contain lead or asbestos. Identification and testing for lead and asbestos and other environmental testing is beyond the scope of this inspection. If you wish to seek additional information, please visit https://www.epa.gov/ or contact an environmental lab or industrial hygienist.
Thermal Imaging Was Used During This Inspection
During this inspection, a thermal imaging camera was used to check walls, ceilings, electrical components and appliances for thermal anomalies. Thermal imaging cameras use the infrared light spectrum to build a picture based on temperature differentials. Experienced thermographers look for clues in these thermal images that could lead us to "see" otherwise-concealed moisture control problems, overheating electrical components and inadequate thermal barriers or air leaks. We can also use them for appliance verification. In older structures, incomplete air and thermal barriers are so common we will only report on items that look significantly deficient and seem worthy of correction.
This service is included with our inspection; it is limited and is not a complete thermal mapping of the building. The use of an infrared camera is well beyond the minimum standards of practice of this inspection. We offer this service because we know it is valuable and helps us help our clients by improving our inspection services.
Please note that this tool has limitations when done in conjunction with a property inspection. Environmental conditions at the time of inspection present limitations to the information that can be gathered during the course of a property inspection. For example, occupant behavior, the time of day, time of year, and weather conditions can all impact the usefulness of the data that can be gathered.
Relevant thermal images will be included in this report.
Grounds
Grading and Drainage
Site Drainage: Negative Slope (Noted - Repair)
Building Clearance to Grade: Siding Too Close to Soils - Repair
Downspouts: Improvements Needed
Siding to Soil Contact Noted
Eliminate siding / soil contact at all areas to reduce the chances for deterioration and pest damage and repair any concealed damage as needed. Generally, a 6-inch clearance between soils and siding is recommended. This is often not realistic on older homes, but repairs should be made to achieve as much clearance as possible, and all direct soil contact should be eliminated. Maintaining this clearance is important not only to protect the siding, but also to help safeguard the underlying wall framing from moisture intrusion, rot, and wood-destroying pests. When creating this clearance, current standards recommend the grading adjacent to the building should be positively sloped at a 5% grade within 10 feet of the building.
See media for examples of locations:
Poor Site Grading
The grade of the yard sloped toward the building. Standards recommend at least a quarter-inch / foot slope away from the building for 10ft if possible to prevent water from draining toward the building. Over time, negative grading, as this is often called, can lead to moisture and even structural problems with the building, especially when roof drainage discharges to this area. Have this repaired as feasible by a qualified contractor. Often, a swale can be used to create a low point away from the house into which water can be diverted safely away from and around the building.
See media for details and locations:
Downspout Drainage Improvements Needed
Deficiencies were noted with the roof drainage system. Downspouts should collect roof runoff and discharge it away from foundations, slabs, retaining walls, posts, and other structural elements. When water is concentrated in these areas, excess moisture can contribute to settlement, erosion, water intrusion, movement of flatwork, deterioration of building materials, and other moisture-related issues over time. Depending on the specific condition, corrections may range from simple maintenance or adjustment to more substantial improvements by a qualified gutter, drainage, or landscape contractor.
Examples of observations noted include:
- Please 🙏 keep the downspout extensions folded down.
- Plastic corrugated extension are unreliable. Replacing them with a more permanent durable solution is preferred.
- Downspouts discharged adjacent to the foundation or flatwork/footings.
- Downspouts discharged on an area that slopes back toward the building.
Driveways/Walkways/Flatwork
Driveway Material(s): Gravel
Walkway Material(s): Concrete
Patio Material(s): Concrete
Fencing
Present - No significant Issues
Trees and Vegetation
Trees & Vegetation: Prune Vegetation away from the Building
Tree And Vegetation Pruning Recommended
Pruning trees, branches and vegetation away from the building is recommended. Where trees, branches and large shrubs can provide rodent access to the roof, a minimum 6-foot clearance is recommended as many rodents can jump 6-feet. All vegetation, including smaller landscaping such as grasses, flowers and shrubs should be kept 1-foot off the house to eliminate contact which could trap moisture against the building or eventually cause mechanical damage.
Irrigation
Irrigation System: Present - Not Inspected (Buyer)
Irrigation System Present
An irrigation system was observed. We apologize, but these are out of the scope of this inspection. Recommend inquiring with the sellers about the condition and operation, and having a qualified irrigation professional inspect it if a detailed report is desired. PLEASE REMEMBER TO WINTERIZE THE SYSTEM EVERY FALL TO PREVENT COSTLY REPAIRS.
Window and Stair Wells
Window Well (Not Covered)
Exterior Stairs and Guardrails
Standard - OK
Retaining Wall(s)
Material(s): None Noted
Outbuilding
Type: Detached Garage
Condition: Repairs Recommended
Repairs Recommended to the Detached Garage
Implement repairs to this building as deemed necessary by a qualified general contractor.
Specific observations noted include:
- The garage circuits did not appear to have any power
- Corner of the garage appears to have been damaged by impact and needs to be repaired. Repairing this at the time of redoing the roof would be a good idea
Exterior
Siding and Trim
Trim Material: Wood
Siding Material: Wood
Painting Repairs Recommended
Localized painting repairs are recommended to the exterior of the building. This is common recommended maintenance between complete exterior paint jobs to ensure that the more exposed areas continue to perform reliably without rot or decay from weather. Implement repairs as recommended by a qualified contractor.
- Repainting may be needed to meet lending or appraisal requirements. FHA, VA, and USDA often require painted surfaces to be free from peeling paint.
See media for examples and locations:
Exterior Doors
Style(s): Solid core, Glass panel doors
Exterior Door Repairs Recommended
Repairs are recommended to the exterior doors. A qualified contractor should repair exterior doors as needed.
Observations noted include:
- Main entry door deadbolt was very difficult to use / turn the knob. It appears to be rubbing on the strike plate and adjustments are needed so that it can be locked and unlocked easily
Exterior Door Has A Keyed Interior Lock
The lock for the south side entry door door requires a key rather than a thumb-toggle from the inside to open/unlock. This can inhibit emergency egress. Recommend switching this lock with a thumb-toggle one for improved safety. This is required for the main egress door, but recommended for all doors for improved safety.
Window Frames
Frame Material(s): Vinyl, Wood
Wall Vent/Exhaust Terminations
Condition: Inspected - OK
Vent Terminal - Repair
Replace or repair the vent terminal at the east side. The terminal was missing. Vent terminals should have a hood to prevent weather entry and a backdraft damper to prevent air and pests from entering. If this is a dryer vent, it should not be covered with a screen as it will plug with lint.
Roof Chimney & Gutters
Roof Covering(s) - House
Method of Inspection: Walked on roof
Style(s): Gable
Valleys: Present and Visually Standard
Covering Material(s): Synthetic/Composite Shingles
Overlayed Roof Covering: No
Roof Repairs Needed
Tune up repairs are needed on the roof covering.
Specific observations noted include:
- cracked ridge cap tiles were noted. These should be replaced.
Recommendation: Have a qualified roofing contractor proficient with this roofing system review and repair as advised.
Roof Covering(s) - Garage
Condition: Repairs Recommended
Media pictured here illustrates the general condition of the roof(s).
Method of Inspection: Viewed from ground
Style(s): Gable
Valleys: None
Covering Material(s): Three-tab composition shingle (Buyer)
Overlayed Roof Covering: Yes
Roof Replacement Recommended
The roof was done in a three tab composition shingle. The roof looks to be at the end of its reliable service life. Roof replacement is recommended to ensure reliable roof performance. If this is a real estate transaction, the insurability of the roof should be verified.
Examples of observations noted include:
Recommendation: Hire a qualified roofing contractor to further evaluate and replace this roof.
Flashings and Penetrations
Condition: Present and Visually Standard
Gutters and Downspouts
Gutter and Downspout Material(s): Aluminum
Gutter Cleaning Recommended
The gutters had excess debris in them and should be cleaned to ensure proper control of roof runoff. Ensure they are unobstructed, leak-free and properly sloped to drain as part of routine maintenance. Ensure the downspouts are clear as well as these can be clogged causing the gutters to fill which may cause damage to them or the building.
Skylights
Type(s): Insulated curb style
Condition: Inspected - OK
Attic
Access & Type
Access Location(s): Inaccessible
Inspection Methods: No Access (Could Not Locate - Attic Cavity Present)
Missing Attic Access
Based on the roof and ceiling design, there appears to be an attic cavity. However, the access to this area was missing or not found above the 2nd Story. Therefore, we were unable to view the attic in this area to note possible evidence of leaking, the amount and type of insulation, the condition of the components, etc. Standards recommend an access opening of 30 inches x 22 inches when there is greater than 30 sq/ft of attic space. Recommend arranging access and fully inspecting this area if possible to ensure safety and serviceability.
Electric Service
Service Entrance
Main Electrical Panel
Main Electric Panel Location : Exterior - North Side
Service Entrance (SE) conductor Size: Not Visible
Main Panel Listed Max Amperage Capacity: 200 amps
Main Panel Breaker Total Amperage Rating: 200 amps
Main Panel Manufacturer: Square D
Surge Protection: Not Present
Overcurrent Protection Devices: Breakers
AFCI Breakers: Not Present
GFCI Breakers: Not Present
No Surge Protection Noted
No surge protection was noted at the electrical equipment today. The 2020 edition of the National Electric Code requires type I or type 2 surge protection on new or renovated homes. This code change reflects the growing complexity of electric appliances in our houses and the growing risk of damage to electrical equipment due to internal or external electrical surges. This short video explains more about electrical surges and surge protection. Recommend upgrading and adding surge protection for improved protection of the electrical appliances/devices in this building. Suggest doing this in the context of other electrical repairs or upgrades.
Electrical Grounding System
Present - Could Not Confirm, Grounding Rod Noted
During a property inspection, every effort is made to inspect the visible components of the electrical system grounding. The grounding system is critical for safely discharging electrical surges, especially in the case of lightning strikes. However, there is no way in the context of a property inspection to verify the "effectiveness" of the grounding system as much of the system is not visible, and there are no practical tests one can perform in the way we can test a furnace or a plumbing fixture. However, if any defects were found, they will be documented in the observations of this report.
Electrical Bonding System
Bonding Noted on Water Pipes
Bonding connections were noted on the water pipes.
Sub Panel - Basement (Large)
Sub Panel Location: Interior (Basement)
Sub Panel Voltage: 120/240 volt
Feeder Conductor Size: Aluminum, 4/0, 200 amps
Sub Panel Listed Max Amperage Capacity: 200 amps
Sub Panel Breaker Amperage Rating: 200 amps
Sub Panel Manufacturer: General Electric
AFCI Breakers: Present - Tested OK, Inconsistent with Modern Standards
All AFCI (Arc Fault Circuit Interrupters) breakers in this panel were tested/tripped and reset with no issues.
GFCI Breakers: Not Present
AFCI Protection was Inconsistent with Modern Standards
AFCI (Arc Fault Circuit Interrupter) breakers, which were introduced around 2002, are designed to detect dangerous electrical arcing caused by damaged, loose, or aging wiring that standard breakers can not sense. These arcing conditions can generate high heat without drawing enough current to trip a conventional breaker, which increases fire risk🔥. Modern electrical safety standards now call for AFCI protection on most residential circuits, so it is common for older homes to fall short of these standards. While upgrades are not required for existing homes, improving AFCI protection is considered a meaningful safety improvement, especially when other electrical work is being performed.
Sub Panel - Basement (Small)
Sub Panel Location: Interior (Basement)
Sub Panel Voltage: 120/240 volt
Feeder Conductor Size: Aluminum, #2, 100 amps
Sub Panel Listed Max Amperage Capacity: 125 amps
Sub Panel Breaker Amperage Rating: 100 amps
Sub Panel Manufacturer: General Electric
AFCI Breakers: Not Present
GFCI Breakers: Not Present
Incorrect Wiring to a 4+ Conductor Feed Sub-Panel
The wiring to this sub-panel requires repair. The neutrals should be on a floating bus bar (not connected to the panel) and should be separated/isolated from the equipment grounds (attached to the panel) to eliminate stray voltage. A licensed electrician should further evaluate and repair this condition.
Appliance Disconnects
Air Conditioner
Electric Distribution & Fixtures
Branch Wiring
Wire Material: Copper, Multi-strand Aluminum
Wiring Method: Non-Metallic Sheathed Cable, Rigid Conduit
Receptacles & GFCI's
Receptacle Inspection Method: Tested All Accessible
During inspection an effort was made to test and inspect all accessible electric receptacles and switches. In general, the scope of testing is directly related to access; where personal belonging and furniture obstruct access to receptacles and fixtures, fewer of them can be reasonably tested during inspection. All defects found during the inspection today will be listed in this report. Inspection/testing of the electrical system can be challenging. It should be anticipated that not all defects will be discovered and that some issues found may actually not be defects at all. Tools used to verify proper wiring and function can vary wildly in reliability/consistency. The kinds of tools that could be used to confidently analyze the system and its function cannot typically be done in the context of a standard Home Inspection. Issues identified, will be further discussed with recommendations in the electrical section below.
Electric Receptacles: Missing Cover Plates, Open Neutral(s), Inoperative Receptacles
GFCI Receptacle Testing Method: All Accessible GFCI's Tested
All readily accessible Ground Fault Circuit Interrupter (GFCI) receptacles (the ones with the “Test” and “Reset” buttons) were tested during the inspection. Standard-looking receptacles located in areas where modern standards recommend or require GFCI protection, including bathrooms, kitchens, garages, basements, laundry areas, exterior locations, crawl spaces, and near sinks, were also tested for GFCI protection using a plug-in ground fault tester. Any deficiencies observed with GFCI protection will be noted elsewhere in this report.
GFCI devices are important safety components designed to reduce the risk of severe electrical shock and electrocution by quickly shutting power off during a fault condition. Occasionally, a GFCI device may fail during testing and require replacement before power can be restored. Manufacturers generally recommend homeowners test GFCI devices monthly using the built-in “Test” and “Reset” buttons.
The video below provides additional information about GFCI protection and homeowner testing procedures.
GFCI Protection/Receptacles: Inconsistent With Modern Standards
Receptacle(s) - Open Neutral
Circuit tester showed open neutral (white wire) on receptacle(s). With no neutral connected, this renders the receptacle inoperative. Have this further investigated and repaired as recommended by a qualified electrician to ensure safe and reliable performance.
Location(s) noted include:
- Ground floor en suite bathroom
Inoperative Receptacles Noted
Inoperative electric receptacles were noted. These may be on a switched or GFCI protected circuit, but no switch or tripped GFCI was found during the inspection.
Recommendation: Have inoperative electric receptacles further evaluated and repaired by a licensed electrician as needed.
See media for locations and details:
GFCI Protection Improvements Recommended
Since the 1970s, requirements for GFCI (Ground Fault Circuit Interruption) protection have changed, and locations requiring GFCI protection seem to get added with every code cycle. It is common for older residential buildings to have some or even many electric receptacles that do not meet modern safety standards. GFCIs have proven successful at reducing electrocutions, and it seems likely that someday, every circuit, receptacle, and appliance in the building will require GFCI protection. The first chart below shows how successful GFCIs have been at reducing risks from electrocution. The second illustration shows where GFCI protection is required as of the 2020 NEC. In terms of safety, its recommended to bring GFCI protection up to modern safety standards.
GFCI protection was lacking for receptacles in the following locations:
- Basement Bathroom
Missing Electrical Cover Plates
The missing cover plates to all electric receptacles, switches, and junction boxes should be installed to cover all access to the wiring and terminals for safety.
See media for locations:
Lighting
Inoperative Light Fixtures
Inoperative Lights
Inoperative lights were found. Have these further investigated and repaired as needed. If a new bulb does not correct the problem, consult with a licensed electrical contractor.
Note: Unfortunately some newer LED fixtures do not have a replaceable lighting element and these fixtures will have to be replaced if the LED has failed.
See media below for locations of inoperative lights:
Ceiling Fans
Wobbling - Need Balancing
Wobbly Ceiling Fan(s) Noted
The ceiling fan(s) were wobbling during operation. This can be a simple matter of balancing the fan blades, but it could also indicate an inadequately secured fan, which can present a safety hazard. Have this further evaluated and repaired as recommended by a qualified electrical contractor.
Location(s) noted:
Smoke and Carbon Monoxide Alarm Systems
CO Alarm Locations: Outside Some Sleeping Areas, On Main Floor, In Basement
CO Alarms: Incorrect Location
Smoke Alarm Locations: In All Bedrooms, On Main Floor, In Basement, On 2nd Floor
Smoke Alarms: Present in all Recommended Locations
During the home inspection, we test a representative sample of the smoke alarms by using the test button on the alarms. However, this is NOT an accurate test of the sensor, just a test to see if the unit is powered and make a noise. For reliability, fire marshals and manufacturers recommended updating smoke alarms every 10 years and changing batteries bi-annually. The latest data indicate that we should be using photoelectric technology in our smoke alarms for improved fire detection and reducing problems with false alarms, which can lead to disabling of this critical safety system. It is surprisingly complex to accurately test a smoke alarm system. A complete evaluation of smoke alarms is beyond the scope of this inspection. For optimal fire safety, we suggest learning about how to service and maintain your smoke alarm system to keep the building occupants safe.
Incorrect Location(s)
Enough Carbon Monoxide alarm/detector(s) were present, however, some detectors have not been installed in the correct location(s). Ensure they are located within 15 feet of the bedroom entrance(s) and on each level. It is also recommend they be installed in rooms with fireplaces, wood stoves, gas heaters, or any fuel burning appliance for safety. CO alarms should be replaced every 10 years per the manufacturers instructions.
- No carbon monoxide alarm was noted on the second story in the primary or near the primary bedroom
Low Voltage Wiring
Doorbell: Present - OK
Alarm or Surveillance System: Not Present
Smart/Connected Devices: None Noted
Plumbing
Water Supply
Water Pressure: 90 PSI
Pressure Reducing Valve: None noted
Water Supply Source: Public water
Buried Water Supply Pipe Material: Copper
Copper Main Water Line Noted: The buried main water line for the building was copper. While copper water pipes can last indefinitely above ground, they have a estimated life span of 50-100 years when buried and less in highly alkaline or acidic soils. Over time, this line will corrode from the soil contact. While no evidence of leaking was observed at the inspection, it is nearly impossible to determine the condition of the line during an inspection because it is buried. By using the age of the home, or if permits were pulled for the line, the age may be able to be determined for an estimate of life remaining. If concerned, a licensed plumbing contractor should be consulted.
Main Water Shut-off Location: Noted In Media
The main water shut off for the building was located in the media below.
Automatic Water Shut Off Valve Present: No
Automatic Water Shut-Off Valve Not Present
An automatic water shut-off valve was not observed on the plumbing system. These devices can automatically stop the water supply when a leak or abnormal water usage pattern is detected, helping reduce the potential for water damage from plumbing failures. Some insurance providers may offer discounts or other incentives when approved leak detection and automatic shut-off systems are installed. If interested, contact a licensed plumber for more information.
Water Treatment/Conditioners: Not Present
High Water Pressure Noted
When static water pressure exceeds 80 psi (pounds per square inch), a pressure reducing valve is recommended to control water pressure and prevent damage to the supply piping system and appliances. High water pressure is typically due to high pressure delivered from the water utility and a lack of a or failing pressure reducing valve.
Recommendation: Have a licensed plumber evaluate and repair as needed.
Distribution Piping
Supply Pipe Materials: Copper, PEX
Copper water supply pipes were installed. Copper pipes installed prior to the late 1980's may be joined with solder that contains lead, which is a known health hazard especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained approximately 50% lead. Note that testing for toxic materials such as lead, is beyond the scope of this inspection. Consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions include:
- Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than 6 hours
- Install appropriate filters at points of use
- Use only cold water for cooking and drinking, as hot water dissolves lead more quickly than cold water
- Treat well water to make it less corrosive
- Have a qualified plumber replace supply pipes and/or plumbing components as necessary
PEX Piping Note
This building uses PEX (cross-linked polyethylene) tubing for water supply piping. PEX is a widely used material in modern plumbing systems, and its crimp ring connections require precise installation methods to ensure long-term reliability. Like with most piping systems, the majority of these connections are concealed and not visible during a standard home inspection, making it impossible to fully evaluate their condition. If any leaks or installation defects are observed, this may indicate a broader concern and should prompt further evaluation by a licensed plumber familiar with PEX systems and connection methods.
Functional Flow: Average
Drain Waste & Vent
Discharge Type: Public Sewer
Waste and Vent Pipe Materials: PVC
Location of Sewer Cleanout: See Sewer Scope Chapter
Exterior Hose Bibs
Condition: Inoperative
Floor Drains, Sump & Ejector Pumps
Floor Drains: None noted
Sump Pumps: None noted
Sump Pump Discharge Location: N/A
Sewage Ejector Pumps: None Noted
Water Heater
Hot Water Temperature
Water Temperature: Not Tested (Inoperative)
Hot Water Temperature Not Tested - Water Heater Inoperative
The water temperature at time of inspection could not be tested because the water heater was inoperative. Suggest verifying correct hot and cold plumbing at all fixtures and that the temperature is between 115 and 130 degrees F when the water heater is repaired or replaced for safety.
General Information
Condition: Inoperative
System Type: Tankless - Gas
Tankless water heater observed. These water heaters consist of gas burners or electric heating elements enclosed in a small module. Instead of warming a large amount of water stored in a tank, a tankless unit heats only the water that flows through it. When a hot water faucet is turned on, the module senses the change in flow, and the heating system immediately switches on. Shut off the faucet, and the heater stops immediately. The energy savings with this technology can be significant by not having to keep a tank of water hot at all times. If an electronic water conditioning system is not present, these should be flushed about every year (more often with hard water) with vinegar to remove the scale build up inside of the heat exchanger. A licensed plumber should flush this water heater if no water conditioners or records are present.
Manufacturer: Rinnai
Capacity: Tankless
Age: 2008
Energy Source: Gas
Water Heater Inoperative
This water heater was inoperative at the time of inspection. Did not determine why and although this may be a simple cheap fix, if it's not, there is a potential high cost associated with water heater replacement. A licensed plumber should further evaluate and repair as needed if its not a simple fix. Suggest verifying correct hot water all fixtures and that the temperature is between 115 and 130 degrees F after repairs or replacement.
Specific observations noted include:
- While running hot water hot water initially came out and then stopped so the tankless water heater was inspected and found to be beeping with a code 10 flashing on the screen. The unit was turned off and back on again and the same result happened a second time
Older Water Heater Noted
Water heater was older and statistically may be nearing the end of its useful life. The average life of a water heater is statistically 8-12 years though in practice, they can vary widely between 8-20 years, or more, depending on water quality and maintenance schedule such as frequency of flushing the tank and replacing sacrificial anodes. Water heater was functioning as expecting at the time of inspection, but it would be wise to budget for replacement. Suggest monitoring this unit frequently for signs of leakage or corrosion.
Unit Components
Expansion Tank: None Noted - Recommended Because Tankless has Recirculation System
TPR (Temperature and Pressure Relief) Valve & Piping: Present - Not Tested
Circulation Pump: Unplugged
Drain Pan: Not Needed
Condensate Drain System: Not Applicable
Venting System: Inspected - OK
Thermal Expansion Device Recommended
When a storage tank water heater or tankless water heater (with a recirculation system) is present, a thermal expansion tank or valve should be installed to prevent a leak at the TPR (Temperature Pressure Relief) valve. Expansion tanks help reduce pressure on the plumbing system by creating a buffer or a place for water to expand into as water expands with thermal expansion (50gal of cold water becomes 52gal of hot water). Installation of an expansion device or pressure tank is modern installation practice and will be required if a pressure reducing valve has been installed on a public water supply or if the plumbing system is closed for any reason. Open systems do not require a thermal expansion device though they can still be an excellent way to help prevent build-up of pressures in the piping system. Consult with a qualified plumber to install.
Water Heater Circulation Pump Unplugged
The water heater had a circulation pump but was not plugged in. These pumps circulate hot water through the house to reduce wait times for hot water a fixtures, which is a really nice feature. If concerned, Inquire with the seller why it was not in use. Its common to unplug it to save energy costs, although adding a timer to these is great so the pump can be timed to go off at night and in the middle of the day. If it is not operational and use of it is desired, a licensed plumber should review and repair as needed.
Sewer Scope
Sewer Type & Access
Type: Public Sewer System
Public Sewer System
The side sewer serving this property was connected to a public sewer system.
Access: Clean Out
Sewer Line Accessed Through Clean out
The sewer line was accessed through one cleanout located in the basement.
Scope Findings
Pipe Materials: PVC, Cast Iron, Clay
Anomalous Findings: Repairs Needed
Limitations: Tap Not Inspected (Blockage)
Limited Camera Access - Blockage
Due to a blockage within the sewer pipe, the entire line all the way to the sewer tap was not scoped. The blockage was encountered approximately 40 feet from the access point. This should be cleared and then the remainder of the side sewer pipe should be scoped as deficiencies may be present in portions of the pipe concealed by murky water or beyond the obstruction. Suggest cleaning and further evaluation by a sewer line specialist.
- The end of the scope was located with green paint for your convenience and can be found in the media below.
Fuel Storage & Distribution
Gas Meter
Fuel Piping
Gas Piping Materials Noted: Steel, CSST
Gas/Fuel Odors Noted: No
Heating Cooling & Fireplaces/Stoves
Heating System
Condition: Operated Correctly
Type: Gas forced air - High Efficiency
This building has a gas forced air furnace. A critical component of all combustion heating equipment is the heat exchanger. This is the welded metal assembly inside the furnace that contains the products of combustion so that moisture, carbon monoxide and other products of combustion do not mix with interior air and get safely vented to the exterior. Heat exchangers on modern furnaces have an average life expectancy of 15-20 years. Unfortunately, heat exchangers are concealed inside the heating equipment; they are not visible and specifically excluded from this inspection. Cracks in heat exchangers may be concealed and can pose a potential safety hazard and therefore we recommended ensuring carbon monoxide monitors are present at all recommended locations (see electrical section) and to have a professional HVAC contractor service and check these units at least bi-annually.
Energy Source: Gas
Manufacturer: American Standard
Age: 2008
Temperature Difference Measurements: Normal
Thermostat(s): Tested
Number of Thermostats/Zones: 1
Condensate Drain System: Present & Correct, Lift Pump Present
Condensate Lift Pump Noted - Not Tested
Condensate lift pump was observed and visually inspected only. These pump the condensate produced by the appliance up to a higher location where it can drain via gravity. Testing the operation of these devices is beyond the scope of this inspection but they are a maintenance item that can fail at any time. These can be tested by pouring water into them forcing them to pump it out. Suggest periodic checks on this pump to prevent water damage to surrounding areas from overflows.
Space Heaters
Type(s): Electric Fireplace, Electric Radiant Floor
Air Conditioning / Heat Pump
Location: Basement, Exterior (North Side)
Type: Air Conditioning Present
The following list is a minimum set of requirements to be expected of heat pump or air conditioning servicing. These are provided as a courtesy to show they types of check-ups that should be expected from a professional servicing.
- Check compressor efficiency
- Check refrigerant level
- Clean the condenser coil
- Change or clean air filters
- Inspect contactors and wiring
- Inspect drive-sheaves, pulleys and belts
- Check and adjust for proper air flow
- Clean the blower motor as needed
- Lubricate all motors and shaft bearings
- Check, calibrate and program the thermostats and be sure the thermostat has adequate batteries as needed
Condition: Operated Correctly
Manufacturer: American Standard
Age: Air Source (2008)
"Older" A/C or Heat Pump System Noted
The air conditioning system was considered "older" and should be considered unreliable. The compressors have fairly unreliable service lives that can range from as little as 7 to as many as 30 years. Service life is dependent on keeping a proper refrigerant charge, reliable return air flow, and how frequently the system has been used. A/C tends to last longer than heat pumps as the compressor only runs part of the year. If no maintenance records are present, suggest having this system serviced by a professional HVAC contractor and have the refrigerant charge checked. Given the age of this unit it would be prudent to budget for a replacement unit, should the need arise. As a side note, as the government continues to change refrigerant requirements, it makes it increasingly difficult for contractors to obtain older refrigerants which can make repairs extremely costly, or even impossible.
Energy Source: Electric
Heat Exchanger Type: Air Source
Refrigerant Type: R410A
Approximate Tonnage (BTU / 12,000): 6
Temperature Difference Measurements: Normal - Cooling - Actual Delta T
Temperature Drop Normal: An actual temperature drop measurement was performed across the evaporator coil of this unit. When tested, temperature at return register was 70 degrees, temperature at supply was 48 degrees, a difference of 22 degrees which is in the 14 to 28 degree normal operating range. This indicates the unit functioned properly when tested.
Thermostat(s): Tested OK
Number of Thermostats/Zones: 1
Emergency Overflow Pan: Not Applicable
Condensate Drain System: Present & Correct, See Heating System Section
Exhaust Vents/Flues
Condition: Inspected - OK
Air Filter(s)
Filter Location(s): At the Air Handler
Number of Filters: 1
Filter Size(s): 16x25x1
Filtration Type and Condition: Disposable - Poorly Installed - Air Will Bypass
Incorrect or Poor Fitting Air Filter(s)
Improperly sized or poor fitting air filters can allow unfiltered air to bypass the filter, reducing overall air quality and allowing debris to accumulate within the HVAC system. Repairs or adjustments are recommended to ensure the filter seals properly and all air passes through it as intended.
Heat and Cooling Distribution System(s)
Heat Source in Each Room: Present
Register Covers Missing
The HVAC air register covers were missing in places and should be installed so that duct flow can be adjusted as desired, keep debris, pests and kids out, and for a proper finish.
See media for locations and details:
Mechanical Ventilation
Mechanical Ventilation Systems
Whole Building Fans and HRV/ERV(s): No Whole Building Mechanical Ventilation Noted
Bath Fan Ducting: Ducted to Exterior
Kitchen Fan Ducting: Ducted to Exterior
Dryer Ducting: Ducted to Exterior
Garage
General
Garage Type: One Car Garage
Fire Separation: Not Applicable - Detached Garage
Floor
Old Buildings (Cracking/Deteriorating Concrete)
Old Concrete was Cracking and Deteriorating
The old garage floor had areas of cracking and surface deterioration consistent with its age. This is common in older slabs and typically considered a cosmetic issue rather than a structural concern. Repair or replacement is discretionary and generally based on appearance or usability preferences rather than necessity.
Doors and Automatic Openers/Closers
Overhead Door Type: Uninsulated Metal
Overhead Door Condition: Limitations (Blocked - Could Not Operate)
Automatic Door Opener: None Noted
Occupant Door Into Building: Detached Garage - Not Applicable
Laundry Facilities
Dryer Connection(s)
Energy Source: 120V Electric, 240V Electric
Transition Duct: Foil / Mylar
Dryer Make up Air: Appears Adequate
Washing Machine Connections
Condition: Visually Inspected - OK
Kitchen
Cabinet and Countertop(s)
Countertop Material(s): Natural Stone
This is a great document From the Natural Stone Institute that covers maintenance and installation recommendations for slab surface stone countertops.
Cabinet Material(s): Wood & Engineered Wood
Sink(s)
Condition: Repairs Recommended
Sink Repairs Recommended
Repairs are recommended to this sink and a qualified plumber should further evaluate and repair as needed.
Observations noted include:
- The aerator was missing from the faucet
Food Waste Disposer(s)
Disposer(s): Operated
Video(s) demonstrate the food waste disposer(s) operating.
Dishwasher
Dishwasher: Operated (Tested Note)
Dishwasher Air Gaps and Johnson Tees: No High Loop
No High Loop in Dishwasher Drain Line
The dishwasher drain line should be looped upward near the top of the cabinet underside in order to prevent possible contamination of clean dishes which can occur when water from the sink flows into the dishwasher. This may not have been required when the dishwasher was installed, recommend the installation of a high loop as a plumbing upgrade.
Range, Oven and Cooktop(s)
Power Source(s): 120V Electric, Gas
Condition: Operated with IR
Ventilation
Operable Window, Fan Ducted Out Of Kitchen 📸
Fan Operating
This shows the kitchen fan operating and venting to location outside of the kitchen. If issues with ducting are noted, they will be noted in the mechanical ventilation section.
- The light was inoperative, repair/replace as desired.
Installed Microwave(s)
Not Present
Refrigerator(s) & Freezer(s)
Ice Maker Off
The refrigerator ice maker was off during the inspection, so its functionality was not verified. Recommend verifying function before closing.
Other Appliances
Trash Compactor: Operated
Video demonstrates the trash compactor operating as a courtesy. Its difficult to evaluate how these perform without actually having trash to compact, so by it making noise and "running" we are assuming it worked.
Interior
Floor Coverings
Floor Material(s): Tile, Hardwood
Walls, Ceilings, Trim, and Closets
Wall and Ceiling Material(s): Drywall, Lath and Plaster
Cracks & Blemishes: Plaster (Typical Cracks), Drywall (Common Cracks & Blemishes)
Typical Plaster Cracking Noted
Plaster walls and/or ceilings were present and had typical small cracks. Cracking in plaster is very common due to normal building movement, seasonal expansion and contraction, and the rigid nature of traditional plaster materials. These cracks are generally considered cosmetic unless otherwise noted. Repairs are subjective and can be made as desired.
Typical Cracks and Blemishes Observed
Blemishes, such as small cracks were noted in the ceiling/wall finishes. These types of finish issues can be due to routine settlement or moderate seasonal expansion and contraction of the structure or even related to the workmanship of the framing or installation of the drywall. Seasonal types of cracking can be frustrating as they can re-open after repair. There are certain stress points in a house where cracking is common, for example, where large beams land on a wall or at the peak of a vaulted ceiling. Cracks/blemishes noted here were not consistent with structural problems.
Recommendation: Repair blemishes as desired and monitor. The best way to monitor a crack is to patch it (with a proper drywall repair) and repaint it, to see if the crack reappears.
See media for examples and locations.
Wall Insulation: Unknown/Not Visible
Thermal Anomalies Noted - Dry
Based on our experience, these thermal images likely indicate disturbed, missing, or under-performing insulation or poor air sealing at the areas pictured. Areas were dry at inspection. Suggest a qualified person review the areas to determine if repairs would be cost effective for increased thermal efficiency/comfort.
See media for details and locations:
Doors
Door Material and Style(s): Pocket, Solid Core
Door Repairs Recommended
Interior door repairs are recommended. A qualified person should further evaluate and repair or adjust interior doors as needed for reliable performance.
Examples of observations noted include:
- Pocket door pool was missing for the upstairs primary bathroom lavatory. This makes it difficult to pull the door out of the pocket.
- Ground floor middle bedroom closet door would not latch
Windows
Window Inspection Method: Inspected All
All Windows Inspected
All accessible windows were opened, closed, and checked for general operation during the inspection. The inspection included observing the condition of the frames, glazing, hardware, and overall function (where operable), as well as the visible condition of the surrounding trim, sills, and adjacent wall surfaces for signs of damage or moisture intrusion. Any significant deficiencies noted during testing are described elsewhere in this report.
Window Frame Material(s): Vinyl, Wood
Window Glazing(s): Double pane
Safety Glazing: Missing Where Recommended - Older House
Safety Glass Not Present at All Hazardous Locations (Older Construction)
Window glass did not appear to be safety (tempered) glazing at all locations where modern standards typically call for it, based on the absence of an etched safety label on the glass panes noted. Safety glass is designed to reduce the risk of injury if broken; tempered or laminated glazing is manufactured to break into small, less-sharp pieces rather than large hazardous shards. In older homes, this type of glazing was often not required at the time of construction, so standard glass may still be present. Modern construction practices generally call for safety glazing in hazardous locations such as near doors, stairways, walkways, and bathing fixtures to reduce the likelihood of serious injury if accidental impact occurs.
Recommendation: This is common in older construction. For improved occupant safety and to better align with modern practices, upgrading to properly labeled safety glazing may be considered. If windows or doors in the areas noted are replaced in the future, safety glass will typically be required at that time. If safety upgrades are desired, evaluation by a qualified glazing or window contractor is advised.
See media for locations:
- Ground level Hall bathroom
Energy Coating Failure
The energy coating for the windows pictured below seems to have failed as evidenced by the cloudy/blotchy stains between the panes of glass. This failure should not be confused with a broken window seal and will not cause any harm other than reduced clarity and thermal efficiency. This typically requires glazing replacement to repair. If replacement is desired, a glass replacement specialist should be consulted.
See media for locations and details:
Escape and Rescue Openings
Escape and Rescue: Present - Meets Current Standards
IRC 2021 R310 - Escape and Rescue Openings
The following passage is from the 2021 International Residential Code and is meant as a reference for you. While older homes are not required to meet current code, escape and rescue openings are an important means of life safety in emergencies. They allow people to get out of home and first responders to get in. It states.....
"Basements, habitable attics, and every sleeping room shall have not less than one operable emergency escape and rescue opening. Where basements contain one or more sleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room. Emergency escape and rescue openings shall open directly into a public way, or to a yard or court having a minimum width of 36 inches that opens to a public way."
Interior Stairs and Guardrails
Handrail (Missing or Incomplete, No Wall Returns)
Handrail Repairs Recommended
The graspable handrail for the interior stairs was missing. This should be a round railing 1 1/4 - 2 inches in diameter. If the railing is not round it must have a finger groove that is 3/4 of an inch down from the tallest point of the rail. The graspable handrail should also be 1.5 inches from the wall and have returns into the wall and run the length of the stairs. Have a qualified contractor build suitable railings to reduce the potential for falls.
Bathroom - Primary
General
Testing Procedure Note
Bathroom Testing Procedures
During inspection today all plumbing fixtures in the bathrooms were operated. A moisture meter was ran around toilets and tile shower enclosures to check for concealed leaks and sounded for loose tile and finishes in shower and tub enclosures. However, bathtub overflow drains are not tested as this risks damaging finishes around the tub. Monitor tubs while filling and avoid pushing water into the overflow. Even well-installed overflow drains can leak, as the gaskets that seal the overflow will dry out over time and may no longer provide a watertight seal. Monitor plumbing after moving into a new home as testing during inspection presents less stress on plumbing than daily use. Please note that vacant homes present additional risk as it can be difficult to distinguish how the plumbing system will respond to daily use. Any defects uncovered during inspection are listed in this report.
Sink(s)
Condition: Tested - OK
Cabinet and Countertop(s)
Countertop Material(s): Natural Stone
This is a great document From the Natural Stone Institute that covers maintenance and installation recommendations for slab surface stone countertops.
Cabinet Material(s): Wood & Engineered Wood
Toilet
Condition: Mounting Issues Noted
Toilet Mounting Issues Noted
The toilet needs to be reset, and the wax ring and flange should be checked and replaced as needed to ensure reliable performance and prevent leaks. This is a some what simple job unless the bolts that fasten the toilet also require repair. Sometimes, loose toilets can even be shimmed for a tight and proper seal by qualified plumbers, and sometimes simply caulking can help prevent the toilet from rocking and twisting.
- The toilet was loose on the floor and rocking or twisting.
- No caulking was noted between the floor and the toilet - caulking is recommended to keep unpleasant bathroom liquids from entering here and to help adhere the toilet to the floor.
- No moisture was noted around this toilet
Recommendation: Hire a licensed plumber to evaluate further and repair this toilet.
Bathtub / Shower
Condition: Inspected - OK
Shower Surround Type: Tile
Tile Shower Surround Noted
Tile shower surrounds require regular maintenance to remain watertight and functional. Their long-term reliability depends on installation materials and methods (such as backer board and waterproofing), which are not visible during a non-invasive home inspection. We make our best guesses about tile reliability using visual inspection and sounding for loose tiles. Moisture meters can also be used in some wall applications, but the moisture meter presents a false positive on most tile floors or pans. We recommend ensuring all corners and transitions are properly sealed with caulk and applying a grout sealer annually to help prevent moisture intrusion and prolong the life of the tile. Poor maintenance may lead to loose tiles or hidden water damage behind the surface.
Tub Type: Acrylic/Fiberglass, Air Jetted
Jetted Bathtub - Tested OK
The air jetted tub was filled and tested OK during the inspection.
Ventilation
Type & Condition: Bath Fan (Operated OK, Inoperative), Operable Window
Bath Fan Inoperative
The bath fan did not appear to be fully operational. These are necessary to prevent moisture and mold issues in the bathroom. Its possible that its controlled by a sensor or hidden switch. Suggest a qualified contractor review for repairs.
- Bath and above the tub did not work, but the bath fan in the lavatory did operate.
Bathroom - Ground Floor Main
Sink(s)
Condition: Waste (Slow Drain)
Toilet
Condition: Tested - OK
Bathtub / Shower
Condition: Inspected - OK
Shower Surround Type: Tile
Tile Shower Surround Noted
Tile shower surrounds require regular maintenance to remain watertight and functional. Their long-term reliability depends on installation materials and methods (such as backer board and waterproofing), which are not visible during a non-invasive home inspection. We make our best guesses about tile reliability using visual inspection and sounding for loose tiles. Moisture meters can also be used in some wall applications, but the moisture meter presents a false positive on most tile floors or pans. We recommend ensuring all corners and transitions are properly sealed with caulk and applying a grout sealer annually to help prevent moisture intrusion and prolong the life of the tile. Poor maintenance may lead to loose tiles or hidden water damage behind the surface.
Tub Type: Cast Iron/Steel
Ventilation
Type & Condition: Bath Fan (Operated OK), Operable Window
Bathroom - En Suite
Sink(s)
Condition: Tested - OK
Cabinet and Countertop(s)
Countertop Material(s): None
Cabinet Material(s): None
Toilet
Condition: Tested - OK
Ventilation
Type & Condition: Operable Window Only - No Shower or Tub - OK
Bathroom - Basement
Sink(s)
Condition: Waste (Leaking)
Leaking Drain
The drain plumbing was leaking and requires immediate repair to prevent damage to the cabinet. This only leaks when the faucet is used. Hire a qualified plumber to repair.
Cabinet and Countertop(s)
Countertop Material(s): Glass
Cabinet Material(s): Wood & Engineered Wood
Toilet
Condition: Leaking
Tank Leaking
Toilet water storage tank was leaking when flushed. This requires immediate repair as it could start to leak and cause water damage. Repair or replace this toilet as needed.
Ventilation
Type & Condition: Operable Window, Bath Fan (Operated OK)
Pests
No Significant Pest Issues Noted
Crawl Space
Access - Rear
Crawl Space Access Location: Old Building (Minimal Clearance - Viewed From Basement/Pit Area Only)
Viewed Crawl Space From Basement/Pit Area Only
Access to the crawlspace areas was limited due to minimal clearances. The only visible portions were those observable from the basement or pit area. In older buildings, it is common for floor framing to be built directly over soil or with minimal clearance, leaving no accessible crawlspace for inspection. As a result, much of the subfloor structure and foundation conditions could not be evaluated. When components such as plumbing or electrical systems in these areas require service or replacement, sections of the floor system may need to be removed to provide access. In some cases, excavation beneath the home may also be necessary to allow access for repairs or improvements.
Access - Front
Crawl Space Access Location: Interior Access (Basement)
Method of Inspection: Viewed from Access Only
Limited Access in Crawl Space - Viewed from Entry Only
The crawlspace was viewed from the entry only. Inspectors are not required to enter crawlspaces that in the inspector's opinion are unsafe due to low clearances, standing water, biohazards, etc. We were unable to fully inspect the entire crawlspace to note possible evidence of water leaks, the amount and type of insulation, the condition of the components, etc.
The reason it was only viewed from the entry was:
Reasons for Limited Inspection
- The access opening was simply too small to safely fit into. General standards recommend an 18 by 24-inch access opening.
Recommendation:
- The entire crawlspace could be seen from the entry and its doubtful if new observations would be made by crawling the entire space.
Foundation/Floor Insulation
Insulation Type & Location: Rim Joist Insulated, Sprayed Foam
Approximate R-Value: R-6-10
Ventilation and Vapor Barrier
Ventilation Method: Appeared Adequate, Conditioned Crawl Space (Conditioned Design Note)
Conditioned Crawlspace Note
This crawl space has been done as a conditioned crawl space. This mean there are no exterior vents and a thick vapor barrier that has been used on the floor was also sealed to the foundation. Conditioned crawlspaces also have supply air vents from the HVAC ducts in them as they now considered an interior space which is normal. At the time of inspection there were no visible signs of moisture problems in this space, indicating it has performed well to date.
Vapor Barrier: Plastic on earth
Moisture
Approximate Relative Humidity: 30%
Condition: No water was visible or present at the time of inspection
Mold / Deterioration: No visible mold or building material deterioration noted
Basement
Basement
Type: Partial
Moisture
Condition: None noted
Structural Systems
Foundation
Condition: Inspected - OK
Evidence of Significant Renovations or Additions: Yes
Additions and/or renovations to the property appear to have been made. This inspection does not review permits or determine if they exist and have been closed. That determination should be made through the local building officials or with the owners.
Approximate Percentage of Foundation Visible: 30%
Primary Foundation Type: Basement Sub-Structure
Primary Foundation Location: Under Main Living Area
2nd Foundation Type: Crawl Space (Poured Concrete Footers, Poured Concrete Stem Walls)
Columns Posts & Beams
Condition: Inspected - OK
Floors Walls & Ceilings - Structural
Floor Structure Material(s): 2x10 Wood Joists
Sub-Floor Material(s): Wood Plank
Sloping Floors: No Significant Slopes Noted Using Leveling Tools
Wall Framing Material(s): 2x4
Wall Sheathing Material(s): Not Visible/Unknown
Ceiling Framing Material(s): Unknown/Not Visible
Structural Cracking: None Noted
Trim or Cabinet Separation: None Noted
Check Out Procedure
Check Out List
Oven: Off
Dishwasher: Off / Finishing Cycle
Heating and Cooling: Restored to Pre-inspection Settings
Lights: Off
Exterior Doors: Locked By Agent
Service Providers
Below is a list of local contractors we have come up with to help you with any repairs or consultation you may need. We have no affiliation or financial interest with these contractors and have put this list together from our own experiences and from people we work with. We make no guarantee on their ability to do the work, or the quality of the work itself. If any of these contractors performs exceptionally well or very poorly, we would appreciate you letting us know.
Appliance Repair: Genesis Appliance : 970-361-0733
Crawl Space Moisture Control: Square One Radon : Rob Hartop: 970-712-4570
Electrician: Unified Service Solutions: Justin Sack: 970-640-1311
Dave Fisher Electric: 970-242-4012
Excavation: Brian's Backhoe Service : 970-245-0268
Environmental Testing
Asbestos: Grand River Environmental : 970-424-4749
Mesa Environmental (Asbestos Testing) : John Witkamp: 970-201-7070
Meth: Grand River Environmental : 970-424-4749
Lead Paint: Grand River Environmental : 970-424-4749
Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Radiation (Mill Tailings): Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Phase 1 Environmental Site Assessments: Grand River Environmental : 970-424-4749
Environmental Remediation, Abatement, Mitigation:
Radon: Square One Radon : Rob Hartop: 970-712-4570
Click here for NRPP approved radon mitigation professionals
Asbestos: Regional Asbestos: 970-242-0016
Lead Paint: Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Radiation (Mill Tailings): Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Mold: Environmental Engineering Consultants: Stacy Skinner: 970-433-2004
Foundation Repair: DWT & Assoc: Dale Thome: 970-261-1517
Mays Construction Specialties Inc.: 970-245-0834
Groundworks: 844-252-4383
Aspen Foundation Repairs LLC : 970-446-5453
Garage Door Installation and Repair: Monument Garage Door: Ryan Reimer: 970-201-5840
Mesa Door Systems: Walt McGinley: 970-234-2123
Gutters: Installation, Repair, & Cleaning: Top Tier Seamless Gutters: Chad Gardner: 406-860-1958
HVAC: Local Plumbing and Heating: Cory Smith: 970-644-1194
Junk Removal: Square U Away : 970-444-5865
Landscaping, Grading, and Drainage: PTL Landscaping : 970-985-9442
Masonry: L E Dangler Masonry Contractor: 970-523-4550
Mobile/Manufactured Home Leveling & Foundation Repairs: DWT & Assoc: Dale Thome: 970-261-1517
Plumbing: Local Plumbing and Heating: Cory Smith: 970-644-1194
True Plumbing: Stephan Hedemark: 970-946-7922
Pool Cleaning, Maintenance, & Inspections: Rocky Mountain Aquatics: Patrick Kitson: 970-424-7366
Roof Restoration (Asphalt Composition Shingles) with Minor Repairs: Roof Maxx of Grand Junction: Nate Anderson: 970-846-8010
Roof Service(Residential): JP's Roofing: Jake Palmer: 970-683-0962
Bro's Roofing: 970-651-7947
Olivera Roofing: 970-208-7149
Roof Service (Commercial): Full Curl Roofing Co: Jake wood: 970-985-1350
Bro's Roofing: 970-651-7947
Sewer/Septic
Septic System Inspections: Scope It Out: Chris Heineman: 970-210-2471
Sewer Line Repairs: Rocky Mountain Sewer Pros: 970-307-4667
Sewer Line Inspections (Reversed - From Main into the Building) : Sightline Solutions: 970-623-2652
(When no accessible cleanout is found near building or sewer main was too far from cleanout and could not be inspected during our scope)
Structural/Civil Engineer: SGM: 970-930-8228
Termite & Pest Control: Chrome Pest Control: 970-300-3307
Additional Resources
Home Repair Manual & Seasonal Maintenance Checklist